2×4 Frame Platform Construction
Transcript
Welcome back. Last week, we talked about forces and we talked about how loads are weights or items or things that impart forces on objects. We talked about how stresses are the kind of internal forces that structural members see internally that resists forces that act on them. And we talked about a couple of different kinds of stresses; axial and tangential. And we talked about the notion of equilibrium and how that's kind of our gold standard, right, all of our structures,
we don't want them to move, so that we want them to be in static equilibrium. And those concepts help us to understand how forces interact within a structure so that we can build them correctly so they don't fall down. Today we're going to talk about one of the most common pre-engineered construction techniques in stage technology, and that is the 2 by 4 frame platform. We're going to talk about how they work structurally, so we can understand how we're supposed to assemble them and why they are assembled the way they're assembled. So, and we're going to keep coming back to that concept of going to ground, how the forces need to be transferred from one structural element to another all the way down to the earth that doesn't move so that we stay in static equilibrium. So, when we think about 2 by 4 frame platform which is sort of our, again, our standard typical old school scenic floor construction technique, there are really three structural components.
There is the lid or the cover which for our purposes will consider as a beam structurally, there are 2 by 4 toggles that run across the grain that are four feet long. We're going to call those joists later on, and then there are the eight foot long members that run the length of the grain of the plywood sheet. So those are the three structural components of a 2 by 4 framed platform. When we look at that and those components, how do the forces of somebody standing on it get from the person, down to the ground? How does the 2 by 4 framed platform transfer those forces around? Well, it's, it should be obvious maybe it's not. But it seems obvious to me that when we look down at that platform, the first thing that's carrying the load is that plywood cover. It is the top most structural member. And as we talked about last time, we're going to think about sort of
a person being on if, we're going to kind of expand that to the idea of a uniformly distributed load across the whole thing. That is how these kinds of structures are rated in terms of loading capacity over its whole area. And so the plywood then is carrying that full load across its whole area. What then is carrying the plywood? Well, pre-engineered construction techniques tell us that it's the four foot toggles that act as Joist carrying the plywood.
They run perpendicular to the grain and they actually carry the plywood itself. And it's sort of structural engineering standpoint, the long members don't carry the plywood at all, so if the plywood carries the load and the joists or the toggles carry the plywood, what carries the joists? Well, that would be what the eight foot members are doing, we're gonna call those girders but those long eight foot members are what actually carry the 2 by 4 foot members which carry the plywood lid which carries the load. And eventually, we'll talk about how all of that gets transferred to some kind of a support a leg or some other structural element that carries the girders, all right. So that's great. Bridge says that the plywood is carried by the toggles who says, how does he come up with that? So the first place we're going to look here in the United States is to APA
the Engineered Wood Association, APA is American Plywood Association, they like to go by the longer title of the Engineered Wood Association. This trade group defines grades of plywood, they define construction methods for plywood, and other specifications of engineered materials. So, ply lamps and engineered joists and that sort of thing, but plywood is kind of their biggest thing. And this trade group provides construction guidance for the use of plywood panels,
and that document is called the Panel Design Specification. You can download that for free from the APA website. There's a link on the Brightspace page. If you search for publications, sorry if you search the publication's page for the panel design specification or document ID, D as in dog 510, you can find this very long document that talks about how we're supposed to use plywood based on how it's been constructed. So, that is where we find these pre-engineered construction guidance techniques.
The panel design specification tells us a whole lot about plywood. And for our purposes, it kind of breaks plywood up into two groups. First are rated panels, and you'll see these stamped as sturdy floor or rated sheathing. These panels when used as flooring, they can also be used for walls or for rooms but when uses flooring, it must be supported by joists running across the grain at least 24 inches apart on center, just tells us that right off the bat. We're going to use them, that's how we use them and they will support a load equal to what we would normally see on a residential floor, or a load capacity of at least 50 pounds per square foot. The other group of plywood panels that we might talk about are visually graded veneer panels and this is what I grew up with, is what I'm most familiar with the so called AB or CD style of plywood. Those letters refer to the niceness of the face grains, right? For those kinds of plywood sheets,
we don't get any sort of information about how far apart supports must be. But they provide calculations so that we could determine the appropriate size of panel, the appropriate thickness of panel, the right species and grade for a given loading condition. Those can be a little tedious to work through if you're not familiar with them, and that's not the purpose of today to learn how to do that, so we're going to not talk about that in detail. However, we can look at a CD sheet of plywood, assuming the weakest species group that we could have them constructed under. And are constructed with at a three quarter inch thickness will support a load of at least 95 pounds per square foot provided that the supports are running across the grain at least 24 inches apart on center. So whether we're using sturdy floor, or rated sheathing, or sort of the ugliest, weakest plywood that we could find kind of seedy, weak species. If those panels are three quarters of an inch thick,
we're gonna want always to have toggles, or joists running perpendicular to the grain 24 inches apart at most 24 inches apart on center,. And we know in both of those cases then, that we will support at least 50 pounds per square foot closer to like 100 pounds per square foot, and that's fantastic. Because, we now can dispense with thinking anymore about plywood and just go any kind of plywood sheet that we get that's going to be better than the weakest we can find that three quarters of an inch thick, is going to be more than enough to satisfy our, Loading condition of 50 pounds per square foot. However, that's only true if we follow the pre-engineered construction guidelines. Meaning, it must be supported by structural members that run across the grain, and it must be supported every 24 inches or less, and it must be fastened down securely. The panel design specification provides information about the pull out strength
of fasteners. But honestly, this really applies to when loads will want to force the screws out, think about plywood on a wall that might see a wind load. Typically, we don't have a lot of things pushing upward on the plywood, that we have to worry about a pullout load, so basically any fasteners that we might typically use are probably gonna be sufficient. And we could add glue, that might help with squeaking, but probably isn't necessary for the structural capacity of the plywood to carry the load that we're talking about here. Okay, so that's the topmost layer. We've dispensed with thinking about plywood. The plywood, we said, it has to be carried by 2 by 4, or some kind of structural member that runs across the grain every 24 inches or less. So, how do we know what kind of a load those can carry, and how big they must be? So some things we need to know. We typically call them toggles or joists, they are 48 inches across. And we're gonna call that the span,
because there's nothing gonna support them across that 48 inches, right? They're just gonna be attached to the 8 foot members. And so that's the span they're gonna have, is 48 inches, nominally, and they're gonna be spaced every 24 inches. Well, what load are those gonna have to carry, right? Let's assume a 50 pound per square foot load uniformly distributed over the whole platform. And that is what we would want to see for a loading capacity for a stage platform.
Each one of those joists carries some portion of that total load. We call that portion the tributary area. Each joist will carry an area that stretches the length of the joist, and from half the distance to the joists on either side. Better with picture. Let's draw a picture. We imagine a top view of the frame of a 2 by 4 framed platform. This is obviously not to scale, 8 foot members and the 4 foot joists, right? We know that these are spaced 2 feet apart, and these are spaced 2 feet apart, right? This joist here is go carry,
This much of the plywood load from halfway between these two to halfway between these two. That distance is gonna be 2 feet. So on a 2 by 4 framed platform, each of these interior joists is gonna carry an area of 2 feet by 4 feet. Now these external joists, on either end, are gonna carry half of that, right? 1 foot by 4 feet, or 4 square feet. That makes sense? Hope so. So in this 2 by 4 frame platform, these joists in the interior are gonna carry the largest load.
So let's just think about those. If we build to that capacity, then we're gonna be fine here if we use the same material, right? So this is gonna carry a tributary area of 2 feet by 4 feet or 8 square feet. And if the uniform load is 50 pounds per square foot, we just multiply 50 times 8 to get the total weight that this joist is gonna carry. So 80 times 50, or sorry, 8 times 50 is 400 pounds, that's the load this, this, and this joist is gonna carry, and
this joist and this joist are gonna carry half of that, or 200 pounds. Before we were talking about the lids, the plywood, we refer to the panel design specification generated by the Engineered Wood Association, the APA. For sawn lumber, like 2 by 4, we are gonna talk about or refer to a document called the National Design Specification for Wood Construction, generated by the American Forest and Paper Association, the American Wood Council. I love these long names. A rule of thumb for number 2 grade 2 by 4 lumber of basically any species. At these kinds of loads around about 400 pounds total, or sorry, about 100 pounds per linear foot, we need for every 1 foot of span, 1 inch of nominal depth. So, for a load of approximately 100 pounds per linear foot along this length, or that is 400 pounds, right? For number 2, any species have 2 by 4 lumber, we need for every 1 foot of span an inch of depth. Well, the span of that joist is 4 feet, and
that means we need about 4 inches of depth or a 2 by 4, pretty simple. That's the rule of thumb, that's how we know it works, from the American Forest and Paper Association. Just like the panel design specification, the NDS, the National Design Specification, provides calculations for determining whether a specific species grade and size of sawn lumber will satisfy specific loading requirements. Again, we don't wanna do those calculations for this course, but know that they exist and that's kind of where these rules of thumb come from. I did a quick look at a 4 foot span, using a number 2 Hemlock for
2 by 4, which is one of the weakest species for a bending member like this. On edge, just barely supports a 400 pound load. It's like 401 pounds or something like that, distributed along its whole length. So by both of these approaches, we can confirm that plywood resting on joists that are 4 foot long, supported on either end of number 2, any species of 2 by 4, sufficient capacity to carry the load. That's why a 2 by 4 frame platform works.
That's why it exists the way it exists, because 2 by 4 is the smallest lumber size we can get away with using to support what would be a 50 pound per square foot load, which is what we would wanna see on stage. Okay, sorry, let me just say that one more time. I think I said it kinda fast. We can assume a number 2 grade 2 by 4 of most any species used as a joists, in this kinda situation, will suffice to support a 50 pound per square foot load,
provided that the structural members run across the grain. The members themselves are no more than 24 inches apart, and that they are secured to whatever is carrying them, which is kind of the next question. What is carrying them? Well, if the plywood is being carried by these, then these joists are gonna be carried by these 8 foot members. We're gonna call those girders, girders carry joists, right? So if the plywood is carried by these joists, these joists are in turn carried by these girders on either side. Our rule of thumb, from earlier, still holds at these kinds of loads, and if we did some math, we'd see that this is gonna be approximately equivalent to 100 pounds per linear foot. For every 1 foot of span, we need 1 inch of depth.
Wait a minute, the span of a girder on a four by eight platform is eight feet. So for this span we need a two by eight. That doesn't make any sense. What's going on here. We have to ask, what carries the girder? If we assume there are legs in all four corners, then there's one leg in each corner supporting or each edge supporting that eight foot girder. That's an eight foot span. We know though from our rule of thumb, that two by four is carrying these loads can't span more than four feet. That means for a two by four framed platform, we need at least one more leg, smack here in the middle of each long member on each side.
Each girder must be carried by three supports. If we use a number two grade of any species two by four as the long framing member, one at each end and one at the center. We should talk a little bit before we wrap this up about fasteners, haven't really talked about that. We mentioned a little bit that we could use any screw, we don't need glue for the lid but we haven't talked about where these meet these, where the joists meet the girders. If the girder carries those joints, how they're secured to each other matters cuz we got to figure out how to transfer that those forces across. What does that joint look like?
So, a typical scenic practice for well or ill and this will undoubtedly get lots of comments, is to use a sheet walk and dry or drywall screws and to drive those sheet rock screws through the eight foot member into the end grain of the four foot members. So we've got our girder here and our joist is here and we're gonna drive a screw through the girder into the joist. Common practice, we've all done it, I've done it probably a million times. There's some problems with this structurally. First, this puts a pretty significant shear load on the sheetrock screws, right. So, when we talked about shear, if the joists are carried by the girder, the joists want to sink and the girder doesn't, which means those drywall screws are now in shear, which is bad, they're not strong that way.
This is reduced somewhat because the plywood lid rests across that joint and that carry some of the load. But that now means we're putting the plywood in shear along that eight foot member and we haven't really analyzed the plywood for its ability to resist that, that's worth knowing. So, okay practice, cuz we know empirically that it usually will works out just fine is to use sheetrock screws for short term installations of these two by four framed platforms.
Provided we inspect them regularly for things are starting to pull apart or break or if the screws are starting to break. Good practice, better practice, would be to use wood screws. Wood screws are designed to resist shear far better than drywall screws. And so we're increasing the ability of that joint to hold against the shear load that's happening. Best practice, no one ever does this but probably we should, is to use joist hangers. That is the reason joist hangers exist in housing construction is they provide a method for hanging the joist off the girder so that we don't have any shear loads, we just have more tensile or compressive loads if that makes sense. In which the joist hanger is designed to resist, well, that would be best practice. I'm betting no one's gonna go away from this starting to
use joist hangers in their two by four framed platforms. And that's okay because we're gonna use them for shorter lengths of time. They're not in use 100% of the time all the time and we have opportunities to inspect them in between uses, okay, we covered a lot of material. So, just to sum up, loads on a two by four frame platform, there is three basic structural components. There is the plywood lid, there are the two by four joists that run across the grain and then there is the two by four girders that run along the grain.
The plywood is weighted at three quarters of an inch plywood of just about any species CD grade, which is the lowest weakest grade. Any of those would be rated for at least 95 pounds per square foot load provided that those toggles are 24 inches on center, this is why we build it that way, right? That toggles, two by four toggles, number two grade even the weakest species, when they span four feet, can hold a load of about 100 pounds per linear foot, which is what we would see in a two by four frame platform at its greatest capacity that we would want. As long as they're supported at either end of four feet, more than sufficient that's why a two by four framed platform is built the way it is. Those joists are carried then by the eight foot members, the same rules of thumb apply.
If we only want to use a two by four, we can't span that full eight feet, need to have supports at a minimum of four feet, sorry, a maximum of four feet away. So the corners and one in the center. All right, next time we're gonna talk about legs and other methods of supporting those girders for a typical two by four frame platform installation. Thanks.