Topic: Fault Fundamentals

What are the two broad categories of power-system faults?

95 questions

  1. 1

    What are the two broad categories of power-system faults?

    Model answer

    The two categories are open-circuit faults and short-circuit faults, also called closed-circuit faults.

    Explanation

    Open-circuit faults involve discontinuities, whereas short-circuit faults create unintended low-impedance current paths.

  2. 2

    Define a short-circuit fault.

    Model answer

    A short-circuit fault occurs when current travels along an unintended path to ground or another phase through very low impedance compared with the intended circuit.

    Explanation

    The defining features are an unintended current path and substantially lower impedance than the normal circuit path.

  3. 3

    How does an open-circuit fault differ from a short-circuit fault?

    Model answer

    An open-circuit fault is a break that prevents current from flowing normally, while a short-circuit fault creates an unintended path that allows excessive current to flow.

    Explanation

    The two fault categories represent interruption of continuity versus unwanted additional continuity.

  4. 4

    What is the difference between symmetrical and asymmetrical faults?

    Model answer

    A symmetrical fault has equal fault currents in all phases, while an asymmetrical fault has unequal fault currents among the phases.

    Explanation

    The distinction matters because the calculation methods differ for balanced and unbalanced faults.

  5. 5

    Why are short-circuit faults divided into symmetrical and asymmetrical categories for analysis?

    Model answer

    They are divided into these categories because the calculations for fault-current values depend on whether the fault is balanced or unbalanced.

    Explanation

    A balanced three-phase fault can be analyzed differently from faults involving only one or two phases.

  6. 6

    What electrical systems are primarily addressed by the fault discussion?

    Model answer

    The discussion primarily addresses faults in three-phase power systems.

    Explanation

    Three-phase systems are the main operating context for the power systems considered.

  7. 7

    What are the four main types of short-circuit faults, listed from most to least common?

    Model answer

    They are single line-to-ground, line-to-line, double line-to-ground, and three-phase or three-phase-to-ground faults.

    Explanation

    These four types describe which phases and whether ground are involved in the fault.

  8. 8

    What is a single line-to-ground fault?

    Model answer

    It occurs when one phase unintentionally connects to ground through an electrical path.

    Explanation

    Only one phase is faulted, so the fault is unbalanced.

  9. 9

    How common are single line-to-ground faults?

    Model answer

    They account for approximately 70% to 80% of all faults.

    Explanation

    They are the most common short-circuit fault type.

  10. 10

    What determines the magnitude of a single line-to-ground fault current?

    Model answer

    Its magnitude depends strongly on the impedance of the fault path to ground and on the system's grounding method and configuration.

    Explanation

    Ground-related impedance and grounding design largely control the current available during the fault.

  11. 11

    Why is a single line-to-ground fault classified as asymmetrical?

    Model answer

    It is asymmetrical because only one phase is faulted and carries the substantially higher fault current.

    Explanation

    The other two phases do not experience the same fault current.

  12. 12

    What is a line-to-line fault?

    Model answer

    A line-to-line fault occurs when any two phases of a three-phase circuit unintentionally connect without involving ground.

    Explanation

    The fault can involve any pair of phases, not only a specific phase combination.

  13. 13

    How common are line-to-line faults?

    Model answer

    They account for approximately 10% to 15% of all faults.

    Explanation

    They are the second most common fault category described.

  14. 14

    Why is a line-to-line fault asymmetrical?

    Model answer

    It is asymmetrical because the two faulted phases experience the higher fault current while the unfaulted phase does not.

    Explanation

    The unequal phase involvement makes the fault unbalanced.

  15. 15

    What voltage effect occurs during a line-to-line fault?

    Model answer

    Voltage decreases on the two faulted phases, while the unfaulted phase is affected much less.

    Explanation

    The voltage depression is concentrated on the phases involved in the fault.

  16. 16

    Why is a connection between a phase and neutral not classified as a line-to-line fault?

    Model answer

    Neutral is a separate system conductor, not a phase, so a phase-to-neutral fault is not a line-to-line fault.

    Explanation

    A line-to-line fault must involve two phase conductors.

  17. 17

    What is a double line-to-ground fault?

    Model answer

    It occurs when two phases unintentionally connect to each other and also connect to an unintended path to ground.

    Explanation

    The fault involves two phases plus ground and is therefore unbalanced.

  18. 18

    How can a double line-to-ground fault develop from another fault?

    Model answer

    It can begin as a line-to-ground fault that escalates to a second phase or as a line-to-line fault that subsequently connects to ground.

    Explanation

    Faults can expand as physical damage or arcing creates additional connections.

  19. 19

    How does the typical current of a double line-to-ground fault compare with line-to-ground and line-to-line faults?

    Model answer

    It is typically higher, although its magnitude depends on system grounding and the impedance of the fault path.

    Explanation

    Grounding configuration can significantly change the current available in ground-involving faults.

  20. 20

    Which phases experience the main fault-current increase during a double line-to-ground fault?

    Model answer

    The two faulted phases experience the main increase, while the unfaulted phase does not experience the same fault current.

    Explanation

    The unequal involvement of the phases makes the fault asymmetrical.

  21. 21

    What is a three-phase fault?

    Model answer

    A three-phase fault occurs when all three phases are connected together, with or without a connection to ground.

    Explanation

    The defining feature is that all three phase conductors are faulted.

  22. 22

    Why are three-phase and three-phase-to-ground faults generally treated alike in fault-current studies?

    Model answer

    In a symmetrical three-phase fault, the ground connection has minimal or no effect on the fault-current magnitude.

    Explanation

    The balanced three-phase condition dominates the calculation.

  23. 23

    Why is a three-phase fault classified as symmetrical?

    Model answer

    It is symmetrical because all three phases experience equal fault currents.

    Explanation

    The equal phase response makes the fault balanced and simplifies its analysis.

  24. 24

    Why is a three-phase fault commonly the limiting case for equipment ratings?

    Model answer

    It typically produces the highest fault-current magnitude and can cause severe voltage drops or voltage collapse.

    Explanation

    Equipment must be able to withstand or interrupt the most demanding fault condition.

  25. 25

    How common are three-phase faults?

    Model answer

    They account for approximately 2% to 3% of all faults.

    Explanation

    Although relatively rare, they are important because they usually produce the greatest current.

  26. 26

    How can a fallen tree cause different types of short-circuit faults?

    Model answer

    A tree touching one phase can cause a line-to-ground fault; touching two phases can cause a line-to-line or double line-to-ground fault; and touching all three phases can cause a three-phase fault.

    Explanation

    The fault type depends on which conductors the tree contacts and whether it provides a path to ground.

  27. 27

    How can lightning cause a short-circuit fault without directly striking a conductor?

    Model answer

    Lightning ionizes the air, lowering its effective insulation and allowing current to arc from an exposed conductor to ground.

    Explanation

    A nearby lightning strike can therefore create a conductive path even without direct physical contact.

  28. 28

    What are two major ways cable insulation damage can produce a fault?

    Model answer

    Insulation can deteriorate over time because of weather, water, sunlight, and aging, or it can be physically damaged, such as by excavation.

    Explanation

    Either mechanism can expose a conductor to ground or to another conductor.

  29. 29

    Why is it important to call before digging near underground cables?

    Model answer

    Digging can damage cable insulation and expose a conductor to earth or another conductor, creating a short-circuit fault.

    Explanation

    Locating underground utilities helps prevent accidental insulation damage.

  30. 30

    Why can a single fault escalate into a multiple-phase fault?

    Model answer

    The initial fault can cause burning, mechanical damage, or accelerated insulation deterioration that creates additional conductor-to-conductor or conductor-to-ground connections.

    Explanation

    A fault changes local operating and physical conditions, making neighboring insulation or structures more likely to fail.

  31. 31

    Why must protection systems clear faults quickly?

    Model answer

    Rapid clearing limits physical and thermal damage and reduces the chance that a single fault will escalate into a larger fault.

    Explanation

    Early interruption prevents fault energy and heat from creating additional fault paths.

  32. 32

    What immediate electrical changes generally occur during a short-circuit fault?

    Model answer

    Fault current increases and system voltage decreases, particularly on the faulted phases.

    Explanation

    The low-impedance path draws greater current and reduces the potential difference at the affected phases.

  33. 33

    Why does a short circuit cause current to increase and voltage to decrease?

    Model answer

    The fault introduces a low-impedance path, allowing more current to flow while reducing the voltage or potential difference across the faulted portion of the system.

    Explanation

    This is the basic electrical consequence of adding a low-impedance path to ground or another phase.

  34. 34

    What are the two components of short-circuit current?

    Model answer

    Short-circuit current consists of a steady-state AC component and a transient DC component.

    Explanation

    Their combination produces the total asymmetrical fault-current waveform.

  35. 35

    What produces the asymmetrical offset in a fault-current waveform?

    Model answer

    The transient DC component produces the vertical offset of the AC waveform and creates the initially high current peak.

    Explanation

    The system's opposition to sudden change determines the initial offset and its decay.

  36. 36

    How do voltage and current waveforms in a nonfaulted AC system differ from those during an asymmetrical fault?

    Model answer

    In a nonfaulted system, the waveforms are symmetrical about the time-axis, whereas a fault can vertically offset the waveform and create unequal positive and negative peaks.

    Explanation

    The offset can make the initial peak much larger than the corresponding negative or positive peak.

  37. 37

    What does impedance represent in a power circuit?

    Model answer

    Impedance represents the circuit's opposition to the flow of current.

    Explanation

    It includes both resistance and reactance effects.

  38. 38

    What is the system X/RX/RX/R ratio?

    Model answer

    The X/RX/RX/R ratio is the ratio of system reactance to system resistance.

    Explanation

    It is an important factor in determining the magnitude and duration of the DC offset in fault current.

  39. 39

    How does a high system X/RX/RX/R ratio affect asymmetrical fault current?

    Model answer

    A high X/RX/RX/R ratio produces a larger and longer-lasting asymmetrical, or DC-offset, component.

    Explanation

    The fault-current envelope decays more slowly when the system has a high reactance-to-resistance ratio.

  40. 40

    How does increased system impedance affect the symmetrical fault-current component?

    Model answer

    Higher system impedance produces a lower symmetrical fault-current magnitude.

    Explanation

    Greater opposition to current reduces the AC fault-current component.

  41. 41

    How does grounding method affect ground-fault current?

    Model answer

    A solidly grounded system generally produces higher ground-fault currents, while methods such as delta, grounding reactors, or high-resistance grounding reduce them.

    Explanation

    The grounding configuration changes the impedance and available return path for ground-fault current.

  42. 42

    How does system voltage generally affect fault-current magnitude?

    Model answer

    Higher system voltage generally results in higher fault current because the system begins with a greater potential difference.

    Explanation

    A larger voltage driving the low-impedance fault path produces a larger current.

  43. 43

    During a single line-to-ground fault, what happens to the voltage and current of the faulted phase?

    Model answer

    The faulted-phase voltage drops sharply while its current rises significantly.

    Explanation

    The phase is connected through a low-impedance path to ground.

  44. 44

    During a line-to-line fault, what happens to the voltages and currents of the two faulted phases?

    Model answer

    Current increases and voltage decreases in both faulted phases, while the unfaulted phase is affected much less.

    Explanation

    Only the two connected phases are directly involved in the fault.

  45. 45

    What is the characteristic phase response during a three-phase fault?

    Model answer

    All three phases experience equal, symmetrical increases in fault current and corresponding voltage depression.

    Explanation

    The balanced involvement of all phases is the defining electrical behavior of the fault.

  46. 46

    What are the three time-based short-circuit current values commonly used in equipment evaluation?

    Model answer

    They are instantaneous current, typically the first half-cycle peak; momentary current, approximately one to three cycles after fault initiation; and short-time current, approximately five to thirty cycles after initiation.

    Explanation

    These values correspond to different stages of decay of the asymmetrical current component.

  47. 47

    What does the instantaneous short-circuit value represent?

    Model answer

    It represents the maximum peak fault current, typically occurring during the first half-cycle.

    Explanation

    This is normally the highest current magnitude during the fault.

  48. 48

    What does the momentary short-circuit value represent?

    Model answer

    It represents the fault current approximately one to three cycles after fault initiation, when the asymmetrical component has partially decayed.

    Explanation

    The current is still not fully symmetrical during this period.

  49. 49

    What does the short-time short-circuit value represent?

    Model answer

    It represents the mostly symmetrical RMS fault current approximately five to thirty cycles after fault initiation, or up to about half a second.

    Explanation

    By this point, the transient DC component has largely decayed.

  50. 50

    What is the interrupting rating of a circuit breaker?

    Model answer

    It is the current, usually specified as symmetrical RMS current, that the breaker can interrupt without arcing or other failure.

    Explanation

    The rating addresses the breaker's ability to open its terminals and clear the fault.

  51. 51

    What is the closing-and-latching rating of a circuit breaker?

    Model answer

    It is the maximum asymmetrical peak current onto which the breaker can close and remain mechanically latched.

    Explanation

    This rating addresses the breaker's ability to survive the first-cycle peak without mechanical failure.

  52. 52

    What is RMS current, and why is it used for AC equipment ratings?

    Model answer

    RMS is the effective AC value; for a sinusoidal waveform, it equals the peak value divided by sqrt{2}. It provides a single value equivalent to the power-producing value of DC.

    Explanation

    Using RMS simplifies the representation of the heating and power effects of an AC waveform.

  53. 53

    What is the momentary withstand rating of non-interrupting equipment?

    Model answer

    It is the maximum asymmetrical peak current the equipment can withstand during the first cycle without mechanical failure.

    Explanation

    The initial peak creates strong magnetic forces that can physically bend or deform metal components.

  54. 54

    What is the short-time withstand rating?

    Model answer

    It is the maximum RMS current that equipment can carry for a specified duration, commonly from about one-half second to three seconds.

    Explanation

    The rating limits thermal damage caused by prolonged high current rather than instantaneous mechanical forces.

  55. 55

    How do thermal and mechanical withstand ratings differ?

    Model answer

    Thermal withstand concerns allowable temperature rise from current and resistance over a defined time, whereas mechanical withstand concerns the instantaneous peak current and resulting magnetic forces.

    Explanation

    Thermal damage results from heating, while mechanical damage results from electromagnetic forces.

  56. 56

    Which short-circuit ratings are typically required for circuit breakers?

    Model answer

    Circuit breakers typically require both interrupting and closing-and-latching ratings.

    Explanation

    A breaker must both interrupt the fault and survive the initial peak when closing onto it.

  57. 57

    Which short-circuit rating is typically provided for fuses?

    Model answer

    Fuses typically have an interrupting rating because they are intended to operate and clear the fault rather than remain closed through it.

    Explanation

    The primary concern is whether the fuse can safely interrupt the available fault current.

  58. 58

    Which ratings are typically needed for switchgear and switchboards?

    Model answer

    They typically require both momentary withstand and short-time withstand ratings.

    Explanation

    These ratings address both initial mechanical forces and thermal stress during the clearing interval.

  59. 59

    What short-circuit rating is typically provided for disconnect switches?

    Model answer

    Disconnect switches typically have a momentary rating, although short-time data may also be available.

    Explanation

    Their main short-circuit concern is usually the initial magnetic-force effect.

  60. 60

    What withstand capabilities should be evaluated for transformers?

    Model answer

    Both mechanical withstand and thermal withstand should be evaluated for transformers.

    Explanation

    Transformer faults can create both damaging electromagnetic forces and heating.

  61. 61

    What short-circuit capability is typically specified for conductors?

    Model answer

    Conductors typically have a thermal withstand rating, whose allowable duration depends on the conductor and its installation.

    Explanation

    Conductor fault withstand is primarily limited by heating from current and resistance.

  62. 62

    Why do high fault currents create mechanical stress in equipment?

    Model answer

    High current produces strong magnetic fields, and the resulting electromagnetic forces can bend or deform metal equipment.

    Explanation

    This is why momentary and closing-and-latching ratings use peak asymmetrical current.

  63. 63

    Why do prolonged fault currents create thermal stress?

    Model answer

    Current flowing through resistance produces heat, and prolonged high current can raise equipment temperature beyond its safe limit.

    Explanation

    Short-time and thermal withstand ratings limit this heating effect.

  64. 64

    Why can generator short-circuit current contributions help stabilize a power system?

    Model answer

    Generator current helps support system voltage during a fault, allowing generators and loads to remain online long enough for the fault to be cleared.

    Explanation

    Maintaining voltage support helps preserve grid synchronization and connection.

  65. 65

    How can insufficient fault current contribute to a cascading blackout?

    Model answer

    If a nearby generator trips because of a voltage drop, its loss of current support can cause further voltage decline and cause additional generators to trip.

    Explanation

    This domino effect can spread the disturbance through the system.

  66. 66

    How can higher fault current improve protection coordination?

    Model answer

    A fault current much higher than normal load current is easier for protective devices to identify, allowing the appropriate relay or breaker zone to trip quickly.

    Explanation

    Small fault-current increases can be difficult to distinguish from normal operating changes.

  67. 67

    What determines the short-circuit contribution of a synchronous generator?

    Model answer

    It is primarily determined by the generator's transient and subtransient reactances, which are physical properties of the generator.

    Explanation

    These reactances control the generator's current response during successive fault periods.

  68. 68

    Why can synchronous generators produce a large initial asymmetrical fault current?

    Model answer

    They commonly have high X/RX/RX/R ratios, which produce a large DC offset and therefore a high asymmetrical peak current.

    Explanation

    Their initial fault response can reach approximately four to eight times nominal current on a per-unit basis.

  69. 69

    What role does the automatic voltage regulator play during a fault?

    Model answer

    When it senses falling system voltage, the automatic voltage regulator increases excitation current, causing the generator to continue supplying current into the fault.

    Explanation

    This additional current provides short-term voltage support during the transient period.

  70. 70

    Over what approximate period does a synchronous generator provide transient fault-current support?

    Model answer

    It provides significant transient support for approximately three to thirty cycles, or about one-half second, after which it must return toward steady-state operation.

    Explanation

    The generator cannot sustain the elevated response indefinitely without risking its physical capabilities.

  71. 71

    What equipment associated with a generator must withstand fault contributions?

    Model answer

    The generator breaker, relays, transformer, and transformer-protection equipment must withstand both grid fault current entering the generator system and generator fault current contributed to the grid.

    Explanation

    Fault current can flow in both directions through the equipment connected between the generator and grid.

  72. 72

    Why are inverter-based resources limited in their short-circuit contribution?

    Model answer

    Inverter-based resources are current-limited devices and cannot supply the very large fault currents produced by synchronous generators.

    Explanation

    Their fault response is controlled electronically rather than by the large electromagnetic response of a synchronous machine.

  73. 73

    What is a typical short-circuit contribution range for an inverter-based resource?

    Model answer

    A typical inverter may contribute approximately 1.21.21.2 to 1.51.51.5 times its nominal current, often for up to about thirty cycles.

    Explanation

    The exact contribution depends on the inverter design and applicable requirements.

  74. 74

    What are ride-through requirements for inverter-based resources?

    Model answer

    Ride-through requirements specify how long an inverter-based resource must remain operational during fault conditions before it is permitted to trip.

    Explanation

    These requirements help maintain grid operation despite the inverter's limited fault-current contribution.

  75. 75

    What standard governs grid-connected inverter-based resources in the material?

    Model answer

    The material identifies IEEE C28.00 as the governing regulation for inverter-based resources connected to the grid.

    Explanation

    The standard provides the applicable reference for their grid fault behavior and requirements.

  76. 76

    Why can increasing inverter-based generation complicate protection coordination?

    Model answer

    Because inverter-based resources contribute less fault current, older protection schemes designed around synchronous generators may detect faults more slowly or trip zones out of sequence.

    Explanation

    Lower fault current can cause delayed clearing and coordination problems.

  77. 77

    How can long transmission distances reduce fault current at a load center?

    Model answer

    Longer transmission paths add impedance, which reduces the fault current available at the remote load location.

    Explanation

    The load experiences the accumulated impedance between itself and the sources.

  78. 78

    Why is the effect of transmission distance especially important for inverter-based resources?

    Model answer

    Inverter-based resources already provide relatively little fault current, so additional transmission impedance can reduce the available fault current and voltage support even further.

    Explanation

    The source limitation and the transmission limitation compound each other.

  79. 79

    What grid information is needed at the point of interconnection for a short-circuit study?

    Model answer

    The study needs the available fault-current magnitude and the grid's X/RX/RX/R ratio at the point of interconnection.

    Explanation

    These values characterize the grid contribution and the decay of the fault-current waveform.

  80. 80

    Why is the grid X/RX/RX/R ratio needed in a short-circuit study?

    Model answer

    It helps determine the DC offset, fault-current decay, and how stiff or responsive the grid is to the fault.

    Explanation

    A higher ratio generally means a slower-decaying asymmetrical component.

  81. 81

    What system-design information is needed for a short-circuit study?

    Model answer

    The study needs the equipment configuration, equipment specifications and ratings, equipment locations, cable and conductor impedances, and transformer impedances.

    Explanation

    These data determine how current flows through the site and what each device experiences.

  82. 82

    Why are cable, conductor, and transformer impedances important in a short-circuit study?

    Model answer

    Their impedances limit fault current and determine how the fault affects other equipment at the site.

    Explanation

    Impedance losses change both the magnitude and distribution of fault current.

  83. 83

    What information is needed about inverter-based resources in a short-circuit study?

    Model answer

    The study needs the amount of fault current each inverter can contribute.

    Explanation

    Even a relatively small inverter contribution can change whether equipment ratings are exceeded.

  84. 84

    What information is needed about interrupting and protective devices?

    Model answer

    Their interrupting ratings and withstand ratings are needed.

    Explanation

    The study compares available fault current with the devices' abilities to interrupt or withstand it.

  85. 85

    What generator and motor data are required for a short-circuit study?

    Model answer

    Their transient and subtransient reactances are required because these values determine their short-circuit contributions.

    Explanation

    Motors can also contribute fault current, especially during the initial cycles.

  86. 86

    What primary results are obtained from a short-circuit study?

    Model answer

    The study provides fault-current values for the relevant fault types and the X/RX/RX/R ratios seen at each studied voltage level.

    Explanation

    These results support equipment selection, rating verification, and protection analysis.

  87. 87

    Why does a site X/RX/RX/R ratio higher than the equipment's tested X/RX/RX/R ratio require attention?

    Model answer

    A higher site X/RX/RX/R ratio causes slower fault-current decay, so the interrupting capability of the equipment may need to be derated.

    Explanation

    The equipment may experience a more severe asymmetrical current than its test conditions represented.

  88. 88

    What special consideration applies when the system X/RX/RX/R ratio exceeds approximately 171717?

    Model answer

    The slower decay of the short-circuit current must be considered, because the current may remain closer to its momentary value than to its interrupting value.

    Explanation

    High X/RX/RX/R ratios can require more conservative equipment ratings or detailed calculations.

  89. 89

    What two questions does an interrupting-duty analysis answer?

    Model answer

    It determines whether interrupting devices can interrupt the available symmetrical RMS fault current and whether they can withstand the maximum peak fault current.

    Explanation

    The first question concerns the interrupting rating, and the second concerns the closing-and-latching rating.

  90. 90

    What two questions does an equipment-withstand analysis answer?

    Model answer

    It determines whether non-interrupting equipment can withstand the peak fault current without mechanical failure and carry the symmetrical fault current without thermal failure.

    Explanation

    The analysis checks both electromagnetic-force limits and heating limits.

  91. 91

    How should a breaker be evaluated if the available asymmetrical fault current is below its interrupting rating?

    Model answer

    The breaker is acceptable with respect to interrupting capability if its interrupting rating is greater than the available fault current, provided its peak withstand or closing-and-latching rating is also adequate.

    Explanation

    Both the RMS interrupting requirement and the initial peak requirement must be satisfied.

  92. 92

    How should a motor controlled by a variable-frequency drive be modeled in a short-circuit study?

    Model answer

    Its model should account for whether the drive can allow fault current to flow back into the system, based on the specific drive configuration and manufacturer information.

    Explanation

    The contribution depends on the VFD design and should be represented in the study software or calculation.

  93. 93

    Why can motor short-circuit contributions be especially important in arc-flash calculations?

    Model answer

    Arc-flash calculations must consider fault current from all sources and the clearing time associated with those sources, including motor contributions.

    Explanation

    Motor current may not control breaker sizing but can affect incident-energy calculations.

  94. 94

    What happens to an ungrounded three-phase system during a line-to-ground fault?

    Model answer

    Ground-fault current tends to circulate within the system rather than flowing through an intentional grounding path, and the unfaulted phases can experience a voltage rise of approximately sqrt{3} times their normal phase-to-ground voltage.

    Explanation

    The voltage rise can exceed equipment insulation limits, which is one reason ungrounded systems are uncommon for many distribution and low-voltage applications.

  95. 95

    Why can an ungrounded system require special equipment planning during a ground fault?

    Model answer

    The unfaulted phases may experience substantial overvoltage, so the equipment and system must be designed to withstand the increased voltage.

    Explanation

    A system designed for only modest overvoltage may be damaged by the voltage rise during a ground fault.