Boost Converter Control
Current-Mode Control of DC–DC Converters
Converter dynamics and the control problem
A boost converter has two important energy-storage state variables:
Inductor current, iL
Capacitor voltage, vC, which is also the output voltage in the basic model
The switching function q(t) controls the converter. In an averaged model, its local average is represented by the duty ratio, d, the fraction of a switching period for which the switch is on.
A conventional voltage-feedback controller compares the output voltage with a reference, sends the resulting error through a compensator GC(s), and uses the compensator’s output to command the duty ratio. A linearized converter model, often written as H(s), describes how small variations in duty ratio produce variations in output voltage.
Why the converter is challenging to control
Several features make the converter’s dynamics difficult to shape:
The dynamics are often nonlinear. The small-signal behavior depends on the converter’s operating point, including its input and output DC voltages. Changing the input voltage while keeping the output voltage fixed can therefore change the dynamics.
The inductor and capacitor create a second-order response. Their interaction produces oscillations, whose damping depends in part on the load resistance.
The poles can be lightly damped. When the load provides little damping, the converter’s natural oscillations are difficult to control.
A boost converter has a right-half-plane zero. This zero reflects the converter’s physical energy-transfer behavior, rather than an artifact of the mathematics. It persists even when the control strategy changes and makes fast control more difficult.
The inductor and capacitor can be selected to influence the dynamics, but modifying the plant with extra components is another option. For example, an added capacitor that acts nearly as a short circuit near the resonant frequency can let an added resistor provide damping. Such modifications cost hardware, so a control strategy that improves the dynamics without adding components is attractive.
Current-mode control
Current-mode control adds a fast inner loop that controls inductor current, while retaining a slower outer loop that regulates output voltage. Instead of directly commanding duty ratio, the outer voltage loop generates a current reference; the inner loop uses the sensed inductor current to determine when to switch off the transistor.
The arrangement can be described as follows:
The output voltage is compared with a reference voltage.
A voltage compensator GC(s) processes the voltage error and generates a current reference.
The sensed inductor current is compared with that reference.
The current comparison determines the switching action.
The voltage loop is slow relative to the switching cycle: it should not change its command rapidly within a cycle. The current loop is fast because it acts on a cycle-by-cycle basis. A useful, though simplified, interpretation is that the inner loop makes the inductor behave like a controllable current source feeding the output capacitor. The converter remains second order, but its dominant response is often easier to control.
Peak current-mode switching rule
In peak current-mode control, the switch turns on at the beginning of each switching period. The inductor current then rises. The switch turns off when the sensed current reaches a threshold based on the commanded peak current and a compensating ramp.
Let:
Ipeak be the commanded peak current,
T be the switching period,
MC be the positive slope magnitude of the compensating ramp,
M1 be the rising slope of inductor current while the switch is on,
M2 be the magnitude of its falling slope while the switch is off.
Within a cycle, the threshold falls with slope −MC. When the rising inductor current crosses this threshold, the switch turns off. Thus, the duty ratio is determined implicitly by the current crossing rather than being specified directly as a fixed on-time.
For a boost converter, the current slopes are
where u is the input voltage, V is the output voltage, and L is the inductance. Other converter topologies use different expressions for the slopes, but the same general switching principle can apply.
Why current-mode control is useful
Current-mode control offers two main benefits:
Improved dynamics: Controlling inductor current changes the effective behavior of the converter. The resulting voltage response commonly has a dominant low-frequency pole and a higher-frequency pole, rather than two strongly resonant, lightly damped poles. This is generally easier to compensate.
Cycle-by-cycle current limiting: The switch turns off when current reaches its commanded threshold, which limits the current processed by the converter. This can help prevent excessive current and overheating, provided the topology can control the current under the relevant operating condition.
A boost converter has an important limitation: a short circuit at its output cannot necessarily be controlled by this mechanism, because the switch may not be able to control the inductor current in that condition. Current limiting is effective in the usual boost operating regime where the output voltage exceeds the input voltage.
The inductor current can be measured directly. Alternatively, since the current is observed during the switch-on interval, a small resistor in the switch-current path—or the switch’s own resistance—can provide a signal for the current comparison.
How the outer loop responds to a load change
The outer voltage loop adjusts the peak-current command in response to voltage error. If the output voltage falls below its reference, the error grows and the compensator raises the current command. The switch then allows greater inductor current, increasing the energy delivered to the output and helping restore the voltage.
The outer loop therefore still regulates the output voltage. The current reference is an intermediate command that determines how much current—and, indirectly, how much input power—the converter processes.
Relating peak current to the averaged model
The existing averaged converter model uses duty ratio as its control input. To analyze current-mode control using that model, the duty-ratio variation must be related to the peak-current variation. A geometric approximation to the inductor-current waveform provides this relationship.
Geometric approximation over one switching period
Consider the waveform during a switching period:
The current starts at a value and rises with slope M1.
The switch turns off at duty ratio d, after time dT.
The current then falls with slope magnitude M2 for the remaining time (1−d)T.
The peak-current threshold is reduced during the cycle by the compensating ramp, giving a peak value approximately equal to Ipeak−MCdT.
The local average current is approximated as the peak value minus the areas of the two triangles between the peak and the actual current waveform, divided by the period. This gives
This is a geometric approximation to the local average current. Although the average could be taken over a more precisely centered interval, the approximation is generally adequate alongside the other approximations in the averaged model.
Small-signal relation for a boost converter
Let D be the steady-state duty ratio and define D′=1−D. A tilde denotes a small variation about the steady operating point; for example, d~ is the duty-ratio variation and I~peak is the peak-current-reference variation.
Linearizing the geometric relation and using the steady-state slope relationship gives the boost-converter relation
This expression relates the small-signal duty-ratio variation to the peak-current command, inductor current, input voltage, and output voltage. Its exact form depends on the converter topology because the current slopes differ between topologies.
The expression can be substituted into the existing linearized state-space model in place of d~. The resulting model has the peak-current reference, rather than duty ratio, as its control input. It can then be used to obtain an inner-loop transfer function such as
Remaining right-half-plane zero and changed pole pattern
Current-mode control does not eliminate the boost converter’s right-half-plane zero. A change in the peak-current command can still produce an initial output-voltage response that is opposite to the eventual response, reflecting the converter’s physical energy-transfer process.
What commonly changes is the pole pattern. The inner current loop tends to produce a dominant low-frequency pole and a much higher-frequency pole. The dominant behavior is approximately governed by the inductor current charging or discharging the output capacitor. The system remains second order, but its response is often substantially easier to compensate than the original lightly damped response.
Why a compensating ramp is needed
Using only a fixed peak-current threshold can make the switching ripple unstable. Even if the output voltage remains regulated, the inductor-current waveform may fail to repeat from one switching cycle to the next.
Subharmonic oscillation and ripple instability
Without a compensating ramp, the inductor current can begin each cycle at a different value, reach the peak threshold at a different time, and end the cycle with a different current error. The pattern may repeat every other cycle, producing a subharmonic oscillation. In some operating conditions, the ripple can behave chaotically rather than settling into a simple repeating pattern.
This behavior is called ripple instability. It can cause:
Larger current ripple than in regular periodic operation
Cycle-to-cycle variation in duty ratio
Lower-frequency ripple components that can disturb the converter’s output
A compensating ramp makes the current threshold change during each cycle. With an appropriate ramp slope, deviations from the desired periodic waveform decay over successive cycles.
Cycle-to-cycle error model
Suppose the current at the start of cycle n differs from its periodic steady-state value by Δin. With the compensating ramp, the error at the start of the next cycle is related to the current error in the previous cycle by
After n cycles, the initial error is multiplied repeatedly by this factor. The error decays if
A larger MC generally makes the error decay faster. If MC=M2, the idealized model predicts that the error disappears in one cycle.
For a boost converter with no compensating ramp, the magnitude of the cycle-to-cycle factor is M2/M1. In steady-state operation, this ratio exceeds 1 when the duty ratio is above 0.5. Thus, without slope compensation, a boost converter can experience ripple instability at duty ratios above 0.5; operation below that threshold does not have this particular instability in the idealized analysis.
Choosing the compensating-ramp slope
The ramp slope must be large enough to suppress cycle-to-cycle ripple instability, but making it unnecessarily large is not desirable.
The compensating-ramp slope appears in the small-signal current-mode model, so changing it also changes the converter’s averaged dynamics. A sufficiently large slope can move the system’s poles and reduce the favorable pole separation created by current-mode control. If the ramp is made too large, the transfer function can begin to resemble the less favorable duty-ratio or voltage-mode case.
A practical design therefore balances two goals:
Choose MC large enough that current-ripple deviations decay at an acceptable rate.
Avoid making MC larger than needed, so the averaged converter dynamics retain their favorable pole locations.
The appropriate slope depends on the converter’s current slopes and operating conditions. It is commonly set using a circuit component such as a resistor; wide operating ranges may require more careful adjustment.
Key points
Current-mode control uses fast, cycle-by-cycle current control inside a slower voltage-regulation loop.
Peak current-mode control turns the switch off when the sensed inductor current reaches a threshold derived from the peak-current command.
The inner current loop often gives the voltage response a more manageable pole pattern, while the boost converter’s right-half-plane zero remains.
A compensating ramp suppresses subharmonic oscillation and ripple instability by making cycle-to-cycle current errors decay.
The ramp must be selected as a compromise: enough to stabilize the ripple, but not so large that it undermines the converter’s improved dynamics.