Topic: Basic Controller Types
  • spaceFlip card
  • KI knew it
  • DI didn't know it
  • ←Previous card
  • →Next card

What are the three basic control actions in a PID controller?

Tap to flipClick to flipspace

Proportional (P), Integral (I), and Derivative (D) actions.

Or swipe the card

26 cards

  1. What are the three basic control actions in a PID controller?

    Proportional (P), Integral (I), and Derivative (D) actions.

  2. What is the main drawback of a proportional-only controller?

    It may not be able to meet certain specifications and sometimes cannot even stabilize the system.

  3. What advantage does derivative control add to a proportional controller?

    It improves transient response and adds damping, allowing better control of closed-loop pole locations.

  4. What is a key benefit of integral control?

    Perfect tracking of constant reference inputs and rejection of constant disturbances.

  5. For a first-order plant with a proportional controller, can the steady-state error be zero when tracking a step input?

    No, it cannot be zero; the steady-state error is nonzero because a nonzero input is needed to maintain a nonzero output.

  6. How does increasing the proportional gain KpK_pKp​ affect the steady-state error in a proportional control system?

    It reduces the steady-state error but does not eliminate it completely.

  7. What practical issue can arise from choosing a very large proportional gain KpK_pKp​?

    Noise amplification and other practical limitations.

  8. How does an integral controller achieve zero steady-state error for a step input?

    The controller output is the integral of the error, so even after error becomes zero, the integral retains a nonzero value to maintain the output.

  9. What is the effect of integral control on the type of a system?

    It increases the system type by one (e.g., from Type 0 to Type 1).

  10. If a plant already has an integrator, is integral control necessary for zero steady-state error?

    No, it may not be necessary for zero steady-state error, but it may still be needed for disturbance rejection.

  11. What is integrator windup?

    A phenomenon where the integrator output continues to increase due to a persistent error when the actuator is saturated, leading to large overshoot and poor response.

  12. What is actuator saturation?

    When the control signal is limited to a maximum or minimum value by physical constraints of the actuator.

  13. What is the effect of integral control on the closed-loop response speed for a first-order system?

    It makes the response sluggish, as the dominant poles move closer to the origin.

  14. What is a potential drawback of derivative control regarding high-frequency noise?

    It amplifies high-frequency noise because the derivative of a noisy signal can be large.

  15. Why is a pure derivative controller KdsK_d sKd​s considered non-causal and not realizable in practice?

    It has more zeros than poles, making it an improper transfer function that cannot be implemented physically.

  16. How can we approximate a derivative controller to make it causal?

    By adding a pole far to the left: Td(s)=Kds⋅11+s/pT_d(s) = K_d s \cdot \frac{1}{1 + s/p}Td​(s)=Kd​s⋅1+s/p1​, where ppp is large.

  17. What is the effect of a large pole ppp in the approximate derivative controller Td(s)=Kds/(1+s/p)T_d(s) = K_d s/(1 + s/p)Td​(s)=Kd​s/(1+s/p)?

    As p→∞p \to \inftyp→∞, Td(s)→KdsT_d(s) \to K_d sTd​(s)→Kd​s (the ideal derivative), and the pole's effect becomes negligible.

  18. What is a lag compensator?

    An approximation of a PI controller of the form Ks+zs+pK \frac{s+z}{s+p}Ks+ps+z​ with ∣p∣<∣z∣|p| < |z|∣p∣<∣z∣ (pole closer to origin than zero).

  19. How does a lag compensator affect steady-state error compared to an ideal PI controller?

    It reduces steady-state error to a small nonzero value, but can make it arbitrarily small by choosing ppp very close to zero and large gain KKK.

  20. What is a lead compensator?

    An approximation of a PD controller of the form Ks+zs+pK \frac{s+z}{s+p}Ks+ps+z​ with ∣z∣<∣p∣|z| < |p|∣z∣<∣p∣ (zero closer to origin than pole).

  21. How does a lead compensator affect the root locus compared to a pure PD controller?

    It pulls the root locus to the left, similar to PD control, improving transient response and relative stability.

  22. What is the relationship between overshoot MpM_pMp​ in time domain and resonant peak MrM_rMr​ in frequency domain for a second-order system?

    Both depend only on damping ratio ζ\zetaζ; Mp=e−πζ/1−ζ2M_p = e^{-\pi \zeta / \sqrt{1-\zeta^2}}Mp​=e−πζ/1−ζ2​ and Mr=12ζ1−ζ2M_r = \frac{1}{2\zeta \sqrt{1-\zeta^2}}Mr​=2ζ1−ζ2​1​ for ζ<1/2\zeta < 1/\sqrt{2}ζ<1/2​.

  23. How is bandwidth related to rise time?

    Larger bandwidth results in smaller rise time.

  24. What are the time-domain performance specifications commonly used?

    Overshoot (MpM_pMp​), rise time (trt_rtr​), settling time (tst_sts​), and steady-state error (esse_{ss}ess​).

  25. What are the frequency-domain performance specifications commonly used?

    Resonant peak (MrM_rMr​), resonant frequency (ωr\omega_rωr​), bandwidth (ωb\omega_bωb​), gain margin, and phase margin.

  26. For second-order systems, can the bandwidth ωb\omega_bωb​ be expressed in terms of ωn\omega_nωn​ and ζ\zetaζ?

    Yes: ωb=ωn1−2ζ2+4ζ4−4ζ2+2\omega_b = \omega_n \sqrt{1 - 2\zeta^2 + \sqrt{4\zeta^4 - 4\zeta^2 + 2}}ωb​=ωn​1−2ζ2+4ζ4−4ζ2+2​​.