what is going on my friends this is Dustin   with electrician you and today we  are gonna talk about transformers [Music] so why do we even use transformers what are  they well transformers really are are useful for   a number of reasons but the most common usage is  that you need to take a high voltage and change it   into a lower voltage this can be for a specific  piece of equipment so say you have a building   that's 480 volts the whole service everything in  the building has to 77 lighting and 480 you know

appliances but you have something that is a 208  rated motor or a piece of equipment that shows   up and you're like [ __ ] we just paid a hundred  thousand dollars for this piece of equipment and   it doesn't match the voltage well ahead of time  somebody's gonna know that and have been like   all right we'll just take this transformer will  transform the voltage we'll get this voltage at   whatever this equipment is rated at so you just  drop a transformer in place and you say okay well I'm gonna take that 480 I'm gonna change it into  208 through this device and feed this thing 208   that's essentially why they're used most of the  time it can be inverse I mean you could take a   whole building that's 208 and you have no need  for anything 480 but then you get this big-ass   piece of equipment that's rated to around 480  well the only way to do that I mean you don't   have 480 run to your building so you just take one  of those 208 panels come off of a breaker and you

feed this transformer in 208 and you can get 480  out of it what you're doing when you're changing   the voltage you're also changing the amperage so  if you look at Ohm's law volts times amps equals   watts well that means to get watts or to get  VA you can change the relationship between the   V and the a so if you raise your voltage you're  gonna lower your amperage to get the same number   on the other side of that equation or inversely  you can lower your voltage raise your amperage to get that same number so a transformer is kind of a  constant power device or a constant wattage device   not really wattage and get a whole different video  about why transformers are rated in VA instead of   watts it's kind of the same thing but really not  but anyways it the whole idea is that you can get   a constant amount of power through this device by  feeding a different voltage through and getting a

different voltage out because when you do that  each one of those circuits is going to draw a   different amount of current based off of the  resistance or the reactance of the windings inside   of there so a transformer typically if we say like  a 480 volt Delta to a 240 volt Delta transformer   on one side you're gonna have a whole crapload  of windings and that's your 480 volt primary   side and then on your secondary side you're gonna  have a lot less whining you're gonna have thicker wire because what's happening is you're feeding a  high voltage at a low current through the primary   but since the wattage has to stay the same on  the secondary side automatically what happens   you've less of windings around the coil and you  have thicker wire so you're gonna end up having   a different resistance or reactance because  of that which is going to produce a different   voltage add a different amperage and it's going  to be inverse so if we have a transformer that's

got a two-to-one turns ratio means that on the  primary side we've got twice as many turns as we   do on the secondary side that means if we feed any  voltage in we're gonna get half the voltage out   just because of the number of turns so what that  also means since this thing keeps the wattage the   same that means that automatically it's going  to figure out the current that can run through   it and it's gonna change so if we're feeding a  480 volt circuit into the primary that draws a hundred amps well four hundred four hundred and  eighty times 100 equals forty eight thousand VA   so we're feeding that much power into this thing  well coming out of it because we have less turns   around the coil we're gonna get out 240 volts  but in doing so we're gonna raise the amperage of   that circuit but it's still the same forty-eight  thousand watts or forty eight thousand VA through

the device so what that means is that we have 480  coming in 240 coming out hundred amps coming in   two hundred amps going out 480 volts times 100  amps equals 48 thousand two hundred and forty   times two hundred amps equals 48 thousand so these  devices are always just trying to balance and keep   the same amount of power but it's really just  based off of how many windings how many times   they've won the primary versus the secondary  inside of this thing transformers are also really helpful in isolating the primary side from the  secondary side so if you have some sort of fault   or something happen on the primary side it doesn't  jump across to the secondary side because they're   they're completely isolated you have a one winding  and another winding that don't touch a good   example of this would be an isolation transformer  where we have the same voltage in and out so we

feed 120 volts in we get 120 volts out so if the  120 volt primary is really dirty power you have   120 volts second area which is really clean power  and you kind of have a fresh start really because   you're isolating the two circuits the typical dry  type transformers that you're gonna see out on   a job site are going to be a delta primary and a  whi secondary so you have Delta in and primary and you have secondary out that's why configuration  there may be times where you have something that   is a listed back feed transformer a back feed  transformer you can actually flip those and you   can feed Y in and get Delta out but I'm not gonna  go into all of the different types there's zigzag   transformers and there's Delta Delta and there's  y Delta Delta y YY there's a lot of different

kinds of transformers that I can make several more  videos about but just know that there is different   wiring configurations that they wire the coils in  one side than they do on the second side and it   allows for some unique things to happen in doing  that [Music] all right so without going too crazy   into depth I just wanted to illustrate a little  bit what the difference between Delta and Y is so say we've got this transformer out there right  and we keep saying that we've got Delta primary   and that we've got Y secondary really what that  means is incoming we've got Delta outgoing we've   got Y so what Delta and Y means is that there's  three coils inside of a transformer so say we've   got a coil one you've got coil - we've got coil  three this is our secondary so we'll just write

secondary that means that these coils together are  wired a specific way so that they get a certain   amount of voltage out of them so that they have  a certain relationship and that we can provide a   neutral when we get power out of it to our load  so if you look this coil would be representative   of this one X - L would be a representative of  that one x3 would be this one so this is our low   voltage output this is our Y so what they do is  first obvious thing is every single one of the

coils is tapped together right like at one end of  every coil they're all combined so what we could   do is just take like this one this one and this  one boom so that is our EXO that is this point the   center point where all three coils come together  well then each one of them has another end of   the coil that's not hooked up to anything well  that's what we actually hook up our three phase   load to you inside of a panel so you know we'd  have conductors that go out from this thing and hook into a panel and do a breaker somewhere and  that's the secondary side and that's how you're   getting a neutral is you're just taking the center  point just like they do up in the streets you know   we got the transformers are up on pole the point  where all three of them come together is where we   put our grounded conductor and actually ground  that part of the transformer so now let's talk   about the primary side of this same exact device  so transformers on the inside they actually

have one coil on the inside and another coil that  goes around them on the outside so the primary is   always the one on the outside the primary is gonna  have twice as many windings as the secondary will   and the primary is going to be a smaller wire than  the secondary because when you're stepping down   your voltage you're going to be increasing your  amperage coming out so the Delta is wire a little bit different you still have three points one two  three but instead of taking all of the coils and   putting them together in the center they're taking  each coil and going end-to-end with them and then   we just tap off of each one of these points all  right so we've got h1 to h2 well this is our h1   and we have to connect that to h2 and then we take  h2 and go to H 3 H 2 to H 3 and then from H 3 we

go back to H 1 so it's kind of getting sloppy  sorry but at each one of these points then we   have a jumper that comes out and these are the  terminals that you would put your high voltage   on so these would be--you're your in in in and  these would be out out out probably should it   just represent a temp like I drew them right you  got X 1 X 2 X 3 and we've got X o up there we've   got H 1 H 2 and H 3 so that's how they're wound  really there they're wounded twice as much on the

primary half as much on the secondary that's how  you would get you know if it is the turret two to   one turns ratio sometimes transformers that like  4 to 1 turns ratios or whatever a lot of there's   so many different kinds of Transformers that have  so many different reasons to them but that's just   to show you it's the same coil of wire you know  there's one on the inside and one on the outside they put them inside of each other but depending  on how you wire them if you wire 3 ends together   or if you wire end to end in series you're gonna  get a different amount of voltage different ratio   of amperage there's a whole whole last video I  can do on that what's the difference I'll put on   a delta versus output on a why why you would have  240 volts coming out versus 208 coming out but   I'll get into that later I just wanted to show  you guys it's kind of the relationship to the

windings and how all of that works inside [Music]  now let's open up the guts of a transformer and   see what it looks like there's a couple of things  to take note of inside of a transformer now this   is a really old transformer you've got all your  taps here you can tell on a transformer that the   Y secondary is this point usually the actual strap  that everything hooks up to is thicker than all of the rest of the taps are but also you've got  these bands that all three come off to the same   point and the only place on a transformer where  that's going to be the case is at the neutral   so that's something just to kind of take note of  another thing is notice that you've got these thin   conductors and you've got these thick conductors  there's another one thin thick thin thick and then

all the neutrals are thick everything that's on  the secondary side since the secondary is the low   voltage in our case is going to need to be thicker  because the secondary is less voltage but more   amperage so that thicker conductor can handle more  amperage the thin conductor is on the primary side   so usually when a coils wrapped the high-voltage  primary is going to be a thin conductor so you can tell that this is like number 10 you know  th H n without any insulation on it whereas the   inside is your secondary and that is that really  really thick conductor so you can tell what your   secondary versus your primary is just you know if  none of these are labeled like in this transformer   not a single one of these is labeled so it's like  well [ __ ] how do I know where my primary wires   go or how do I know where my secondary go you  could sit and tone all of that out or you could

just look and be like okay well this is a tiny  little wire that that goes to this coil so I know   that this is a primary this is thick so that's  gonna be a secondary that's a primary that's a   secondary that's a primary that's a secondary the  order the phasing you know from a phase B phase C   phase none of that really matters essentially as  long as you are in the same coil for everything so you know if you have an a phase primary this is  going to be your a phase secondary because they   both go down into the same place now another thing  to look at these are the taps for the transformer   so you notice every one of these is tapped on the  left side second post down same thing here and   same thing here so each one of these represents a  different a different post or different voltage if

you have to make minor adjustments so if you need  208 but you're getting like 273 or something like   that you can actually move these around this is  changing the primary windings so instead of you   being all the way at the highest potential you can  lower it slightly and you can tell each of these   these bands there's like individual bands it's all  one solid conductor but what they did is they they wrapped that conductor all the way around this  coil and at a certain point they twist it out   a little bit and then they just kept going and  then they twist it out a little bit twisted out   a little bit and they kept doing that so wherever  you tap this it's going to change the difference   in potential just slightly so it's going to bring  it from a higher to a lower potential and that's   how you can make small little adjustments in your  voltage when you have a higher or lower secondary

voltage coming out now another thing to take  note of is the neutral so a lot of people say   that you derive a neutral when you're talking  about a delta to Weiss transformer so you're   bringing Delta in you're getting a Y out well  this is the common point or the center point for   that Y configuration so you see this conductor is  going down it's wrapping the inside of that coil   and it's coming back out to this common point  same thing with the next winding you've got a

phase conductor that you hook up here it goes  down wraps are on that coil and it comes back   to the same exact point same thing for the third  one so all three of your secondary windings are   coming back to a common point and that is where  we get our neutral from that's where we hook up   neutral right here that goes out to our load and  then you'll notice that there is a bonding jumper   that goes all the way down to ground so in this  transformer it's really really important in all transformers to bond this is called your EXO  terminal this is where your neutral and your   ground need to be bonded together so you bond to  EXO that's all your neutrals are gonna hook your   load neutral to it you're gonna make sure that you  run a bonding jumper all the way down to the can   itself you know the metal of this enclosure and  then any other grounds that come in or out of the   transformer also have to bond to that plus if you  have building steel that you're trying to bond to

you're gonna have a jumper that goes out and then  goes up somewhere to building steel and you might   even have a ground rod that's coming out same  thing that ground rod is going to come so all of   those things all those grounds equipment grounds  grounding electrodes building steel and neutral   all of them need to be bonded together in the same  exact place at the centre point of that secondary   and that is always on the EXO terminal most of  the Transformers you're going to come across

newer ones at least are gonna say like h1 h2 h3 X  1 X 2 X 3 and X 0 they're going to label what each   thing is but it's just kind of cool that I have  this one that is really really old and shows how   all of its wound [Music] now let's talk a little  bit about sizing transformers so there's a pretty   easy calculation that we need to go by to size one  of them it's for single-phase at least it's just voltage times amperage equals your VA that's what  the transformer is going to be rated in that's the   power rating the three-phase it's the same thing  I just wrote these threes so that you knew we were   talking about three-phase there's nothing to do  with the calculation but you're going to take   your voltage times your amperage times the square  root of 3 which is 1.73 - just a good number to

memorize anytime you're dealing with three-phase  loads you need to use this talk an efficiency   horsepower anything like that you always need to  use a square root of 3 or 1.73 - that'll give you   your three-phase VA for the transformer so let's  start out with single things we're going to use   the secondary so reason I use the secondary is the  load that you're trying to feed is coming out of the secondary side of that transformer so you need  to know what the the voltage of that equipment is   and what the amperage is and then you can figure  out what the primary side is based off of that so   we've got voltage and amperage of our load let's  say that we have a 208 volt single phase load that   is a 200 amp piece of equipment so we know we have  208 for our voltage we've got 200 amps so what is

the VA so we've got 208 times 200 which is going  to equal 40 1,600 VA so transformers are always   rated in kV a which just means thousands of VA  so it's really gonna be a 41.6 kVA transformer   now you're gonna always upsize like they only  make just a 41.6 v8 right here kVA transformer   so they do make a 45 though so you can round up  to 45 KVA and have that be your the size of your   transformer that's pretty easy right so you know  45 kV a is gonna handle the load coming out of

the secondary and then coming out of the primary  you would just may have to make sure that you're   running for a 480 to it and then your breaker size  conductor size and everything's gonna be based   off of whatever that's going to draw so that's  pretty easy to figure that out as well now let's   do three phase so three phase is the same deal  say that we've got 208 three-phase instead of   208 single-phase like we had in this one 208  we'll say that we still have a 200 amp load times 1.73 - which is the square root of 3 and  that's going to give us our VA and the total is   72 thousand 51 which would be our VA so then our  que VA would be 72 kPa again you're gonna want to   round up so there's a seventy-five kVA transformer  then that's the one that you're gonna want to use   so pretty easy right like it's not that difficult  to figure out what the transformer size should be

what the load is you you just need to know it's  Ohm's law it's you know your your e times I equals   P it's your power same thing over here e times  five times square root of 3 equals power now when   I said that a 45k VA would be the next size up for  a single phase transformer that's technically not   correct so the 45k VA is a three-phase transformer  sighs so within single-phase usually you're going

to be working with like 15 kV a 25 kV a 37 half  50 75 and a hundred those are the typical sizes   they go above that three-phase you're usually  working with like the fifteen twenty five forty   five seventy five hundred and twelve point  five but those are the typical sizes within   three-phase so just understand when you're sizing  the transformer and you get your calculation to   go look up single transformer sizes or three-phase  transformer sizes or damn chart to remind you what

all of them are but if you order a 45 kV a single  for his transformer it's gonna show up three-phase   so understand what you're getting into before you  order one [Music] some really important things to   consider when working with transformers is make  sure that you look in the transformer to see if   it comes with lugs or not a lot of transformers  out there don't come with lugs they just come   with holes that you can bolt your own lugs on  some of them do come with lugs another thing to pay attention to is the actual positioning of the  lugs so that way you're not screwing yourself and   then out in the field you don't have enough wire  because you didn't plan for how those conductors   were going to come in another important thing to  do because this is a vibrating piece of equipment   is to make sure that you you tighten everything  to the torque specs of the equipment this is

something important to do on all big equipment on  all lugs at services it's something that I do all   the time because our code here we actually have  to mark our torque settings so an inspector can   look at them but with especially with vibrating  equipment it's really important to torque all of   your lugs down get a torque wrench out look at  what the specs of the equipment call out for and   and torque everything to spec another important  thing to think about is once you've hooked up a transformer and you've turned everything on check  your voltage and make sure that you have the right   voltage for the piece of equipment that you're  going to be running out to you if it calls for   208 and you have like 222 for your voltage but  it's still connected in Y configuration you can   go into the primary taps where it'll say like  500 volts 460 volts you know like 340 volts you   can actually change the taps on the primary to  get a different voltage out if you need to kind

of bump your voltage up a little bit or bump  your voltage down a little bit there's a lot   of equipment out there that cannot be hooked up  you know there's certain tolerances of voltages   so if the voltage you're getting is plus or minus  5% or plus or minus 10% you may ruin that piece   of equipment or the equipment down the line that  you're feeding so make sure that you check your   voltage check the equipment to see if you're  within your values and if there's any question about it you can always call the manufacturer  of the equipment and make sure and say this is   the voltage I'm getting out do you do I need  to change these taps or am I good within the   warranty they'll be able to tell you that but  just know that you can change the taps on these   transformers on the primary side another thing  to pay attention to you is vibration so taking   pads and putting them underneath the transformer  when a metal transformer is sitting on concrete

it's gonna vibrate it's gonna be loud so putting  transformer pads underneath your transformers   even if it's something that you're hanging from  a ceiling on a strut rack put transformer or put   a put rubber pads underneath the transformer that  way it's not vibrating metal on metal it'll just   make it a little bit quieter the last thing to  note when ordering a transformer is pay attention to the actual physical size of the transformer not  every 75 kVA transformer is going to be the exact   same size some of them are taller some of them are  wider you know make sure that you pay attention to   the size measure if you're trying to replace a  transformer especially measure the dimensions of   everything take a picture of the nameplate of that  transformer get as much information as you can so

that you can match it exactly for what was there  alright so that's pretty much it I could have done   like 13 videos in 20 different directions covering  a lot of this stuff way more in-depth there's so   much to know with transformers but I just wanted  to get like give you guys kind of a basic flow   understanding how to size them how to change  them out things to think about how to know what   is on the nameplate somehow to just understand  all of it so let me know if you guys have any other questions appreciate your attention thank  you so much I'll see you the next one [Music]