Electrical Transformers Explained
- 21Unfamiliar
- 0Learning
- 0Familiar
- 0Mastered
- spaceFlip card
- KI knew it
- DI didn't know it
- ←Previous card
- →Next card
What is the primary purpose of a transformer?
To change voltage levels, either stepping up or stepping down, to match equipment requirements.
Or swipe the card
21 cards
What is the primary purpose of a transformer?
To change voltage levels, either stepping up or stepping down, to match equipment requirements.
How does changing voltage affect current in a transformer?
Voltage and current are inversely proportional; raising voltage lowers current and lowering voltage raises current, keeping power (VA) constant.
What is a turns ratio in a transformer?
The ratio of the number of turns in the primary winding to the number of turns in the secondary winding, which determines the voltage change.
Calculate the secondary amperage for a transformer with a 2:1 turns ratio, 480V primary and 100A primary.
200A. Since power is constant (48,000 VA), 240V out requires 200A to maintain the same VA.
What is an isolation transformer and its purpose?
An isolation transformer has the same voltage in and out (e.g., 120V to 120V) and isolates the primary side from the secondary side to provide clean power and prevent faults from crossing.
What is the most common configuration for dry-type transformers?
Delta primary, Wye secondary.
How are the coils connected in a delta configuration?
Coils are connected end-to-end in a loop, with taps at the connection points.
How are the coils connected in a wye (Y) configuration?
One end of each coil is connected together at a common point (neutral), and the free ends are the phase terminals.
How can you identify primary vs secondary windings by wire thickness?
Primary windings use thinner wire; secondary windings use thicker wire.
What are taps on a transformer and their purpose?
Taps are points along the primary winding that allow fine adjustments to the output voltage by changing the effective turns ratio.
Where is the neutral derived in a delta-wye transformer?
At the common center point (X0) of the wye secondary, where all three secondary windings connect.
What must be bonded together at the X0 terminal?
Neutral, equipment grounds, grounding electrodes, building steel, and any ground rods must all be bonded together at the X0 terminal.
How do you size a single-phase transformer?
VA = voltage × amperage. Then round up to the next standard kVA rating.
How do you size a three-phase transformer?
VA = voltage × amperage × √3 (1.732). Then round up to the next standard kVA.
What are standard single-phase transformer kVA sizes?
15, 25, 37.5, 50, 75, 100 kVA.
What are standard three-phase transformer kVA sizes?
15, 25, 45, 75, 100, 125 kVA.
Why is it important to check if a transformer comes with lugs?
Many transformers do not include lugs; you may need to supply your own lugs that match the terminal holes.
Why must transformer lugs be torqued to specification?
Because transformers vibrate, proper torque prevents connections from loosening over time, reducing fire risk.
What should you do after energizing a transformer?
Check the output voltage and adjust primary taps if necessary to ensure it is within the equipment's tolerance (typically ±5% or ±10%).
Why use vibration pads under a transformer?
To reduce noise and vibration when the transformer is mounted on concrete or metal surfaces.
What should you measure and document when replacing a transformer?
Physical dimensions (height, width, depth) and the nameplate information (voltage, kVA, configuration).

Ask anything
We've read this whole study set, so questions about it get the best answers.