Topic: Purpose and Basic Principle

What is the primary reason for using a transformer in an electrical system?

20 questions

  1. 1

    What is the primary reason for using a transformer in an electrical system?

    Model answer

    To change a given voltage to a different voltage, typically to match equipment requirements (e.g., stepping 480 V down to 208 V or stepping 208 V up to 480 V).

    Explanation

    Transformers are most commonly used to convert voltage levels to suit specific loads, such as powering a 208 V motor from a 480 V service.

  2. 2

    Explain the relationship between voltage and current in a transformer regarding power.

    Model answer

    In an ideal transformer, power (VA) is constant: if voltage increases, current decreases proportionally, and vice versa, maintaining the product V×IV \times IV×I equal on both sides.

    Explanation

    Transformers are constant power devices. For example, 480 V × 100 A = 48,000 VA on the primary yields 240 V × 200 A = 48,000 VA on the secondary.

  3. 3

    How does the turns ratio of a transformer affect voltage and current?

    Model answer

    The turns ratio determines the voltage ratio; if the primary has twice the turns of the secondary, the secondary voltage is half the primary. Current inversely follows the same ratio so that power remains constant.

    Explanation

    A 2:1 turns ratio means primary voltage is twice secondary voltage, and primary current is half secondary current.

  4. 4

    What is the purpose of an isolation transformer?

    Model answer

    To isolate the primary circuit from the secondary circuit, providing clean power by preventing faults or electrical noise from passing between sides.

    Explanation

    Isolation transformers have the same voltage in and out (e.g., 120 V to 120 V) but separate the windings so dirty or noisy power on the primary does not affect the secondary.

  5. 5

    Describe the typical winding arrangement in a step-down transformer regarding conductor size and number of turns on the primary versus secondary.

    Model answer

    The primary has more turns of smaller wire (high voltage, low current), while the secondary has fewer turns of larger wire (low voltage, high current).

    Explanation

    In a step-down transformer, the primary is wound with fine wire for high voltage, and the secondary with thicker wire to handle higher current.

  6. 6

    What is the common wiring configuration for a dry-type transformer on the primary and secondary sides?

    Model answer

    Primary is typically delta-connected, and secondary is wye-connected.

    Explanation

    Most dry-type transformers found on job sites use a delta primary and wye secondary configuration.

  7. 7

    Draw (describe) how three coils are connected in a wye (Y) configuration on the secondary of a transformer.

    Model answer

    All three coils are connected at one common point (the neutral, X0), and the other ends of each coil are the three phase outputs.

    Explanation

    In a wye connection, each coil has one end tied to a common neutral point, and the free ends become the phase terminals.

  8. 8

    Draw (describe) how three coils are connected in a delta configuration on the primary side of a transformer.

    Model answer

    The coils are connected end-to-end in a closed loop, with a tap at each junction point for the three line terminals.

    Explanation

    Delta connection: the end of coil 1 connects to the start of coil 2, and so on, forming a triangle. Each corner is a phase terminal.

  9. 9

    How can you visually identify the primary and secondary windings inside an unlabeled transformer?

    Model answer

    The primary winding uses thinner wire (smaller gauge), while the secondary uses thicker wire (larger gauge) to handle higher current.

    Explanation

    Conductor thickness indicates the current capacity; high-voltage, low-current primary uses thin wire; low-voltage, high-current secondary uses thick wire.

  10. 10

    What are taps on a transformer primary winding used for?

    Model answer

    To make small adjustments to the secondary voltage by changing the number of primary turns in use, compensating for variations in supply voltage.

    Explanation

    Taps allow fine-tuning of the voltage ratio. For example, if the secondary voltage is too high, moving the tap to a higher-voltage primary connection reduces the secondary voltage.

  11. 11

    Where must the neutral and ground be bonded in a delta-wye transformer, and what is that terminal called?

    Model answer

    At the X0 terminal (the common point of the wye secondary), where the neutral, equipment grounds, building steel, and ground rods are all bonded together.

    Explanation

    In a wye secondary, X0 is the center point where all secondary windings meet. All grounding and bonding conductors must connect to this point to establish a solid reference.

  12. 12

    Write the formula for sizing a single-phase transformer in VA.

    Model answer

    VA=V×IVA = V \times IVA=V×I, where VVV is the secondary voltage and III is the load current.

    Explanation

    Single-phase VA is simply voltage times current. Then round up to the next standard kVA rating (e.g., 41.6 kVA → 45 kVA).

  13. 13

    Write the formula for sizing a three-phase transformer in VA.

    Model answer

    VA=V×I×3VA = V \times I \times \sqrt{3}VA=V×I×3​ (or ×1.732\times 1.732×1.732), using the line-to-line voltage and line current.

    Explanation

    Three-phase power calculation includes the square root of 3 factor. For example, 208 V × 200 A × 1.732 = 72,051 VA, rounded up to 75 kVA.

  14. 14

    List the standard kVA sizes for single-phase transformers mentioned in the video.

    Model answer

    15, 25, 37.5, 50, 75, and 100 kVA.

    Explanation

    These are the typical single-phase transformer sizes available in the market.

  15. 15

    List the standard kVA sizes for three-phase transformers mentioned in the video.

    Model answer

    15, 25, 45, 75, 100, and 12.5 kVA.

    Explanation

    Common three-phase sizes include 12.5 kVA and the others listed; always verify with manufacturer charts.

  16. 16

    Why should you check if a transformer comes with lugs before installation?

    Model answer

    Many transformers do not include lugs; they only have holes for bolting your own lugs, so you must plan accordingly.

    Explanation

    If lugs are not included, you need to purchase them separately and ensure proper size and type for the conductors.

  17. 17

    Why is it important to torque all lugs on a transformer to the specified torque?

    Model answer

    Transformers vibrate during operation, and loose connections can cause overheating or failure; torquing ensures secure connections.

    Explanation

    Vibration can loosen connections over time. Proper torque maintains low resistance and prevents arcing or fire hazards.

  18. 18

    What should you do after energizing a transformer to verify correct operation?

    Model answer

    Measure the output voltage to ensure it is within the required range for the connected equipment (e.g., ±5% or ±10%).

    Explanation

    Check secondary voltage against equipment specifications. If out of range, adjust primary taps or contact the manufacturer.

  19. 19

    What is the purpose of using vibration pads under a transformer?

    Model answer

    To reduce noise and vibration transfer from the transformer to the mounting surface (e.g., concrete floor or steel strut).

    Explanation

    Rubber pads dampen vibration, making the installation quieter and reducing mechanical stress.

  20. 20

    Why should you measure the physical dimensions of an existing transformer when replacing it?

    Model answer

    Transformers of the same kVA rating can have different physical sizes; measuring ensures the new unit fits in the same space.

    Explanation

    Take photos of the nameplate and measure height, width, depth to match the replacement exactly.