1. Home
  2. Explore
  3. Engineering
  4. Taum Sauk Dam Failure

Study methods

Flashcards
Quiz
Fill in the blanks
Written test
Lesson
Notes
Podcast
Content

Taum Sauk Dam Failure

  • 35Unfamiliar
  • 0Learning
  • 0Familiar
  • 0Mastered
Topic: Taum Sauk Failure
  • spaceFlip card
  • KI knew it
  • DI didn't know it
  • ←Previous card
  • →Next card

What was the initial event at the Taum Sauk power station on December 14, 2005, that led to the dam failure?

Tap to flipClick to flipspace

Pumps were nearly finished filling the upper reservoir, but one pump continued to run, causing water to overtop the concrete parapet wall.

Or swipe the card

35 cards

  1. What was the initial event at the Taum Sauk power station on December 14, 2005, that led to the dam failure?

    Pumps were nearly finished filling the upper reservoir, but one pump continued to run, causing water to overtop the concrete parapet wall.

  2. What happened after water began cascading over the parapet wall at Taum Sauk?

    The rockfill embankment slowly eroded, leading to a deeper and wider hole, undermining the parapet wall's footing, and eventually causing the wall to tip over.

  3. Where was the massive surge of water unleashed after the parapet wall collapsed at Taum Sauk?

    The water surged down the mountainside directly toward Johnson's Shut-Ins State Park.

  4. What was the primary function of the Taum Sauk pumped storage plant?

    It was designed to act as a battery, storing energy by pumping water uphill during low electricity demand and generating power during high demand.

  5. Why was Taum Sauk considered a 'net consumer' of electricity?

    It used more electricity to pump water uphill than it generated when the water flowed back down, but it was valuable for managing grid fluctuations.

  6. Describe the operational cycle of the Taum Sauk pumped storage facility.

    During low electrical demand, water was pumped from the lower to the upper reservoir. When demand spiked, the system reversed to generate hydropower from the stored water.

  7. What was the approximate overall efficiency of the Taum Sauk pumped storage facility?

    The overall efficiency was around 70%.

  8. What made the upper reservoir at Taum Sauk visually striking and unusual for dam construction?

    It was a circular dam, sometimes called a ring dike or ring levee, perched on top of a mountain, which is not usually an efficient way to build a dam.

  9. Why was an 'off-channel reservoir' design chosen for Taum Sauk despite its inefficiency?

    The height provided by the mountain top was essential for pumped storage, as greater height (head) reduces the amount of water needed to move for a specific power output.

  10. What material was the original Taum Sauk dam built from, and what was its main drawback?

    It was built as a rockfill embankment. Its main drawback was that rockfill does not hold back water well due to spaces between the rocks.

  11. How was the watertightness of the original rockfill embankment at Taum Sauk achieved?

    Concrete panels were installed all along the inside of the reservoir.

  12. What feature was included at the morning glory inlet of the Taum Sauk reservoir to prevent issues during draining?

    The inlet was set into a basin 20 feet (6 meters) below the bottom of the reservoir to suppress the potential for a vortex to form.

  13. What innovation in operation proved disastrous for the Taum Sauk plant?

    The project was designed to be operated remotely with no on-site technicians required, which proved to be one of many disastrous decisions.

  14. How did deregulation of electric power markets in the 1990s impact the operation of Taum Sauk?

    The plant's operation increased from around 100 days per year to 300 days, often cycling the upper reservoir twice per day.

  15. What major maintenance project was undertaken in the fall of 2004 to address leaks at Taum Sauk?

    Ameren spent over two million dollars to install a geomembrane liner to cover the entire reservoir.

  16. What problem arose with the level sensors after the geomembrane liner installation at Taum Sauk?

    The sensors' mounting system was underdesigned, causing the buoyant conduits to become dislodged and deflected, leading to inaccurate, lower-than-actual water level readings.

  17. How did operators respond to the initial overtopping event observed in September 2005?

    They switched to generation mode to lower the water, attributed the overtopping to high winds, and reprogrammed the control system to subtract two feet from the upper set point on the pumps.

  18. What was the original design's freeboard between the top of the wall and the maximum water surface at Taum Sauk?

    The original design called for two feet (600 millimeters) of freeboard.

  19. When did the final collapse of the Taum Sauk dam occur?

    Early in the morning of December 14, 2005.

  20. What was the estimated volume of water released during the Taum Sauk dam failure?

    Roughly 6 billion liters or 200 million cubic feet of water.

  21. Who was directly impacted by the surge of water from the Taum Sauk dam failure?

    The state park superintendent, his wife, and three children were swept away when their house was demolished, but they incredibly survived.

  22. What was a surprising conclusion of the Federal Energy Regulatory Commission (FERC) investigation into the Taum Sauk failure?

    A series of small oversights, individually minor, combined to cause the disaster.

  23. What construction flaw was identified regarding the rockfill embankment during the Taum Sauk investigation?

    The rockfill contained more soil than intended, leading to increased settlement over time, and unsound areas in the foundation were not properly cleaned out.

  24. How much did parts of the parapet wall settle from construction to failure at Taum Sauk?

    Some parts of the parapet wall were a full two feet (600 millimeters) lower than where they started.

  25. What was the issue with the failsafe probes installed on the parapet wall at Taum Sauk?

    They were installed in a location higher than settled parts of the embankment and incorrectly programmed to require both sensors to be activated before shutting off pumps.

  26. What significant design flaw, present from the facility's inception, contributed to the Taum Sauk disaster?

    The design had no spillway.

  27. What concept, coined by Charles Perrow, describes how failures become more likely in complicated systems like Taum Sauk?

    Normal accidents.

  28. What was the largest penalty FERC ever issued, and to whom?

    FERC fined Ameren (the owner of Taum Sauk) 15 million dollars for the failure.

  29. What was the outcome of the State of Missouri's lawsuit against Ameren for the Taum Sauk failure?

    A 177 million dollar settlement, much of which went toward restorations at Johnson's Shut-Ins State Park.

  30. How was the new dam at Taum Sauk rebuilt after the failure, and what material was used?

    The new dam was built on the same alignment and size using roller-compacted concrete (RCC).

  31. What innovative feature was included in the new Taum Sauk dam design that was absent in the original?

    They included a spillway this time.

  32. What major changes did FERC implement in dam safety oversight after the Taum Sauk collapse?

    FERC issued technical guidance for pumped storage facilities, updated rules requiring internal dam safety programs, and mandated a Chief Dam Safety Engineer role for owners.

  33. What crucial lesson did the Taum Sauk failure demonstrate regarding off-channel reservoirs?

    It demonstrated the need for overflow spillways, even for off-channel reservoirs with redundant control systems meant to avoid overfilling.

  34. Why is energy storage becoming increasingly important for the electrical grid?

    It is crucial for balancing mismatches in supply and demand, especially with the growing integration of intermittent power sources.

  35. How are the risks of pumped storage facilities compared to new battery storage solutions?

    Dams are among the riskiest structures humans build with severe consequences when they fail, while battery storage has a lot of technical differences and a different risk profile.

Card 1 of 35
Card 1 of 35

Ask anything

We've read this whole study set, so questions about it get the best answers.

FlashcardsQuizFill in the blanksWritten testLessonNotesPodcastContent