External Convection and Heat Transfer
Convection and Internal Flow
External Convection: Key Concepts
A convection coefficient depends on the conditions governing the fluid motion and heat transfer. Important factors include:
Fluid velocity
Fluid properties
Flow conditions, such as whether the flow is laminar or turbulent
Operating temperature
Surface geometry
The convection coefficient is therefore not a property of the fluid alone; it reflects the interaction between the fluid, the flow, and the surface.
Dimensionless parameters
The Prandtl number compares momentum diffusivity with thermal diffusivity. Momentum diffusivity influences the growth of the hydrodynamic, or velocity, boundary layer, while thermal diffusivity influences the growth of the thermal boundary layer. The Prandtl number therefore indicates the relative development of these two boundary layers.
The Nusselt number represents dimensionless convective heat transfer. It is related to the dimensionless temperature gradient at the surface: a larger dimensionless gradient corresponds to a larger Nusselt number and stronger convective heat transfer.
Flat-plate flow
For laminar flow parallel to a flat plate, the local convection coefficient is greatest near the leading edge and decreases downstream. As the boundary layer grows along the plate, the local heat-transfer behavior changes.
If the flow transitions to turbulence, the convection coefficient increases substantially. Thus, the downstream decrease describes the laminar region; after transition, the coefficient can rise.
For a flat plate in parallel flow, a critical Reynolds number of approximately 5×105 is often used as a guideline for transition from laminar to turbulent flow. This is not a sharp boundary: actual transition depends on the flow and surface conditions, so transition can occur below or above this value.
Internal Convection: Developing and Fully Developed Flow
Internal convection occurs when fluid flows through a pipe or duct. Unlike external flow over a plate, the boundary layers grow inward from the channel walls. As they grow, they eventually meet and occupy the full cross-section.
Hydrodynamic development
At the entrance to a pipe, the velocity profile is still developing. Boundary layers form along the walls, while a central core initially retains approximately the inlet velocity. As the boundary layers grow, the core narrows. Once they meet, the velocity profile is fully developed: its shape no longer changes with position along the pipe.
For fully developed laminar flow in a circular pipe, the velocity profile is parabolic.
The distance from the entrance to the point where the velocity profile becomes fully developed is the hydrodynamic entrance length, denoted xfd,h.
Thermal development
A thermal boundary layer also develops when the fluid temperature differs from the wall temperature or the wall supplies heat. The fluid’s temperature profile changes along the thermal entrance region. Once the profile is fully developed, its shape no longer changes with position along the pipe.
The distance required for this to occur is the thermal entrance length, denoted xfd,t.
Thermal and hydrodynamic development are distinct. Their entrance lengths depend on the flow regime and fluid properties, and they do not necessarily end at the same position. In the fully developed thermal region, the temperature profile’s shape remains the same, although the bulk fluid temperature may still change along the pipe.
The wall boundary condition affects the temperature profile:
Constant wall temperature: The wall temperature remains fixed, and the temperature gradient at the wall adjusts along the developing flow.
Constant heat flux: The wall supplies a fixed heat flux, producing a specified temperature gradient at the wall.
Entrance lengths and the Prandtl number
For laminar flow in a circular pipe, approximate entrance lengths are:
Here, D is the pipe diameter and ReD is the Reynolds number based on that diameter. These relations show that the thermal entrance length is approximately the hydrodynamic entrance length multiplied by the Prandtl number.
The Prandtl number gives a qualitative indication of the relative development of the two boundary layers:
Pr≫1, as for oil: the hydrodynamic boundary layer is thinner than the thermal boundary layer.
Pr≈1, as for air: the two boundary layers have relatively similar development lengths.
Pr≪1, as for mercury: the hydrodynamic entrance length can be much greater than the thermal entrance length.
For turbulent pipe flow, the entrance lengths are often approximated as equal, with both the velocity and temperature profiles treated as fully developed after roughly 10D.
Developing versus fully developed heat transfer
The friction factor and heat-transfer coefficient can vary with distance through the entrance region. Once the flow is fully developed, each becomes constant along the pipe for the relevant conditions. This is one reason fully developed flows are more straightforward to analyze.
Internal-Flow Calculation Strategy
A practical sequence for analyzing internal convection is:
Identify the geometry and wall boundary condition.
Determine the appropriate characteristic length: the pipe diameter for a circular pipe, or the hydraulic diameter for a noncircular duct.
Calculate the Reynolds number and determine whether the flow is laminar or turbulent.
Determine whether the location of interest is in the developing or fully developed region.
Choose a Nusselt-number correlation appropriate to the flow regime, geometry, and boundary condition.
Calculate the convection coefficient from the Nusselt number.
Apply an energy balance or convection relation to find the unknown heat-transfer quantity or temperature.
Temperature for evaluating fluid properties
For internal flow, fluid properties are often evaluated at the average of the inlet and outlet temperatures:
If both temperatures are known, this average is direct to calculate. If the outlet temperature is unknown, it may be estimated and then updated by iteration: calculate the heat transfer and resulting outlet temperature, compare it with the estimate, and repeat if needed. Iteration is most important when the properties vary substantially with temperature or the required accuracy is high.
Reynolds number and characteristic length
For a circular pipe, the Reynolds number uses the pipe diameter as its characteristic length. For a noncircular duct, it uses the hydraulic diameter:
Here, Ac is the cross-sectional flow area and Pw is the wetted perimeter—the part of the perimeter in contact with the fluid. The hydraulic diameter is used in both Reynolds-number and Nusselt-number definitions.
Nusselt-Number Correlations
The Nusselt number connects the convection coefficient to the characteristic length and fluid thermal conductivity:
For a circular pipe, the characteristic length in this definition is the diameter D. In a noncircular duct, the hydraulic diameter Dh is used instead.
Fully developed laminar flow in a circular pipe
For fully developed laminar flow, the Nusselt number is constant for the stated wall boundary conditions:
Constant heat flux: Nu=4.36
Constant wall temperature: Nu=3.66
Once the appropriate Nusselt number is selected, the convection coefficient follows from the definition of Nu.
Turbulent flow in a smooth circular pipe
For turbulent flow in a smooth pipe, a commonly used correlation is:
The exponent depends on whether the fluid is being heated or cooled:
Fluid being cooled: use n=0.3.
Fluid being heated: use n=0.4.
In this context, cooling means the fluid is warmer than the surface; heating means the surface is warmer than the fluid. If the surface roughness or transitional nature of the flow calls for a different correlation, another appropriate relation must be used. When a problem does not specify a rough pipe, the smooth-pipe assumption is commonly used in the discussed approach.
Developing-region flow
The fully developed correlations do not apply throughout the entrance region, where the Nusselt number changes with position. Developing-flow Nusselt numbers can be obtained from a suitable table or from a correlation involving the Graetz number. Many practical problems use fully developed correlations when the pipe is sufficiently long and the location of interest lies beyond the entrance region.
Temperature and Heat-Transfer Relations
Constant heat flux
For a constant heat flux q′′, the total heat transferred over a pipe length x is:
For a circular pipe, Pw is the pipe perimeter. The same expression applies to a noncircular duct when Pw is taken as the wetted perimeter.
An energy balance on the fluid gives:
Here, m˙ is the mass flow rate, cp is the fluid specific heat, and Tm(x) is the bulk fluid temperature at position x. Equating the two expressions allows the bulk fluid temperature at that location to be determined. The length x must match the position being analyzed; for the pipe outlet, use the full length L.
If the flow is thermally fully developed under constant heat flux, the wall-to-fluid temperature difference is consistent with the applied heat flux and convection coefficient, as expressed by Newton’s law of cooling:
where Ts is the surface temperature and Tm is the bulk fluid temperature at the position of interest.
Constant wall temperature
For a constant wall temperature, the difference between the surface and bulk-fluid temperatures decreases exponentially along the pipe. The dimensionless temperature difference is:
This relation can be rearranged to find the bulk-fluid temperature at any position, including the outlet at x=L.
For the overall heat-transfer rate, an energy balance on the fluid gives:
The convection relation can also be written using a log-mean temperature difference:
where As=PwL is the heat-transfer surface area for a uniform cross-section, and
For heating or cooling against a constant-temperature surface, the end differences are the positive magnitudes of the wall-to-fluid temperature differences:
The logarithm must use a dimensionless ratio of temperature differences. Temperature differences can be expressed in Celsius or kelvins, provided the units are used consistently.
Example: Cooling Air in a Constant-Temperature Pipe
Compressed air enters a pipe with an inner diameter of 10mm and a length of 2m. The pipe surface is maintained at 45∘C, while the incoming air is at 125∘C. The air is therefore being cooled. The given fluid properties and flow rate are used to determine the flow regime, convection coefficient, and outlet temperature.
Determine the flow regime
The flow rate can be converted to an average velocity using:
For a circular pipe, Ac=4πD2. The Reynolds number is then calculated using the pipe diameter and the fluid properties:
The example gives a Reynolds number of approximately 60,000. The commonly used transition guideline for flow in a pipe is approximately 2,300, much lower than the approximate flat-plate guideline of 5×105. The pipe flow is therefore turbulent.
Check whether the flow is fully developed
For turbulent flow, both profiles are treated as fully developed after approximately 10D. With D=0.01m, this distance is 0.1m. Since the pipe is 2m long, the outlet is well beyond this entrance region, so a fully developed turbulent correlation is appropriate there.
Select the Nusselt-number correlation
The pipe is treated as smooth, and the fluid is being cooled because it enters hotter than the pipe surface. Therefore, the turbulent smooth-pipe correlation uses n=0.3:
The example calculation gives Nu≈137.3. Using Nu=hD/k with the given diameter and thermal conductivity gives:
Find the outlet temperature
For a constant-temperature wall, apply the constant-wall-temperature relation at x=L. The example obtains:
Substituting Ts=45∘C and Tin=125∘C gives an outlet temperature of approximately:
The air cools toward the pipe’s surface temperature as it travels through the pipe, while remaining warmer than the surface at the outlet.