What carbon-reduction target did the California 2030 low-carbon grid study examine?
A 50% reduction in California electric-sector carbon emissions below 2012 levels by 2030.
Or swipe the card
68 cards
What carbon-reduction target did the California 2030 low-carbon grid study examine?
A 50% reduction in California electric-sector carbon emissions below 2012 levels by 2030.
What renewable share did the study’s two target portfolios achieve?
Approximately 55–57% renewable penetration.
What was the study’s baseline renewable portfolio based on?
California’s 2014 Long-Term Procurement Planning (LTPP) 33% renewable case.
How did the two target renewable portfolios differ?
The diverse target portfolio used more varied resources; the high-solar portfolio substituted more solar PV for some of that diversity.
Which resources in the diverse target portfolio replaced some of the high-solar portfolio’s PV?
Out-of-state wind, mostly in-state geothermal, and a small amount of biomass.
What rooftop PV and energy-efficiency assumptions were shared across the portfolios?
All portfolios assumed 24 TWh of rooftop PV; the baseline had about 20 TWh less energy efficiency than the two target portfolios.
Why did the study include both a diverse and a high-solar portfolio?
To compare a more diverse resource mix with one reflecting stronger solar procurement trends and assess their differing integration impacts.
Why did the study assume Diablo Canyon nuclear plant would retire?
Retirement was a conservative, more challenging integration assumption that required replacing a zero-carbon resource with more renewables.
How did the study treat additional offshore wind?
It included no additional offshore wind, citing the near-term cost barriers of floating platforms; offshore wind might become an option later.
What electric-vehicle deployment did the study assume, and how could it affect load?
Three million EVs, adding 13 TWh of annual load and potentially up to 3,000 MW of additional load, especially during curtailment periods.
What transmission additions were modeled in the target portfolios?
A north–south line from Idaho to Southern Nevada, approximating the Swift North line, and transmission from New Mexico to the Western grid.
What major categories of sensitivities did the study examine?
Resource investments, grid operations and institutional rules, demand-side flexibility, gas and CO₂ prices, western renewable penetration, and wet- or dry-year hydro conditions.
What import rule defined conventional flexibility in the study?
At least 70% of specified out-of-state California-titled renewable generation, Palo Verde nuclear power, and Hoover hydro had to be imported every hour.
How did enhanced flexibility change the import assumption?
It removed the must-import requirement and retained only physical limits on imports and exports.
What local minimum-generation rule was used in the conventional flexibility case?
A requirement that 25% of generation in California balancing authorities come from local fossil-fuel and hydro resources.
How did enhanced flexibility treat the local-generation requirement?
It had no local-generation requirement.
What storage was included in the conventional flexibility case?
Approximately 1.5 GW of battery storage, corresponding to the CPUC requirement.
What additional storage was included in the enhanced flexibility case?
One GW of new California pumped hydro and 1.2 GW of out-of-state compressed-air energy storage in Utah.
How did the two flexibility cases differ in hydro and pumped-storage ancillary-service assumptions?
Conventional flexibility limited their provision to roughly match 2013 levels; enhanced flexibility allowed less restrictive provision.
Why can combined flexibility constraints have a larger effect than their individual effects?
Their impacts compound when several constraints operate together.
What regional dispatch assumption did the low-carbon grid model use?
Optimal west-wide dispatch, subject to hurdle rates that constrained power flows between regions.
What nonrenewable fleet changes were included in the study assumptions?
Coal retirements outside California and retirement of the Intermountain Power Project plant in 2025, in addition to previously announced retirements.
How did the study represent Diablo Canyon and hydro flexibility in the later duck-curve analysis?
Diablo Canyon was treated as a constant-output baseload plant; hydro flexibility used the limits from the LTPP model.
What carbon-emissions benchmark did the study use?
California’s 2012 electric-sector emissions.
Did the study meet its 50% carbon-reduction target in every scenario?
It met the target in all modeled scenarios except the dry-hydro case.
Why were emissions lower in the enhanced-flexibility cases?
They had less renewable curtailment, so less fossil-fuel generation was needed to replace curtailed energy.
What production-cost reduction did the target portfolios produce?
About 4.3–4.8 billion.
How valuable were enhanced flexibility assumptions in the baseline case?
They reduced annual operating costs by about $65 million relative to conventional flexibility.
How did the value of flexibility change at higher renewable penetration?
In the target portfolio, flexibility benefits rose to more than $500 million.
Which assumptions were associated with curtailment approaching 10%?
The high-solar portfolio combined with conventional flexibility, especially the 25% local-generation and 70% must-import rules.
What were the reported worst-case impacts of inflexible rules and a less diverse, high-solar portfolio?
Curtailment could reach 10%, operating costs could be up to $800 million higher, and carbon emissions could be up to 14% higher.
What annualized capital cost did the companion analysis estimate for the target enhanced portfolio?
About $5.1 billion for incremental renewables, transmission, and storage.
How did the estimated portfolio costs compare with California’s annual revenue requirement?
The net difference was about 0.6% of the annual revenue requirement; alternative assumptions produced a range from a 3% benefit to a 6% cost increase.
What did the dynamic-stability review conclude about high-renewable scenarios?
It identified potential risks but also existing mitigation options that could provide reliability at lower cost and emissions than relying on additional curtailment.
What is overgeneration in an electricity system?
A condition in which more energy is available than the system can use or accommodate.
Why is renewable curtailment technically straightforward but economically undesirable?
Wind and utility-scale solar can generally be turned down, but doing so discards zero-cost, zero-carbon energy.
Why can curtailing residential rooftop PV be more complicated than curtailing utility-scale solar?
At very high penetration, controlling many distributed rooftop systems is more difficult than controlling large-scale installations.
What did the duck-curve analysis modify from the low-carbon grid study?
It used much of the same modeling framework but restored Diablo Canyon and adjusted geothermal assumptions to better resemble the grid of the time, then added solar.
What happened on the modeled March day at 11% annual solar penetration?
Net load fell below 10,000 MW, but minimum-generation constraints kept the thermal and hydro fleet near 12,600 MW, causing curtailment of about 5% of potential wind and solar generation.
How did existing pumped hydro reduce curtailment in the midday solar period?
Changing pumping and discharge schedules allowed it to pump during the day, avoiding a couple thousand megawatts of curtailment.
Why was curtailment limited during summer in the duck-curve analysis?
High air-conditioning demand created substantial midday electricity use.
Why does adding solar beyond the system’s minimum-generation limits lead to more curtailment?
The system cannot reduce thermal and hydro output below their minimum levels, so additional solar exceeds what the remaining load can absorb.
What is marginal curtailment, and what did the analysis find near 20% solar?
Marginal curtailment is the share of incremental solar energy that is curtailed; near 20% solar, about 30–40% of additional solar could be wasted.
How can curtailment affect the effective cost or value of solar?
Curtailment lowers the amount of energy sold, increasing the effective cost per unit of energy used and reducing solar’s value.
What does it mean to “fatten the duck”?
Reduce minimum-generation constraints so the system can accommodate more midday solar output.
What does it mean to “flatten the duck”?
Shift or add demand during midday and use storage or demand response to move that energy use to later hours.
How can storage help flatten the duck curve?
It can absorb midday energy and discharge it later, reducing instantaneous curtailment.
How can storage help fatten the duck curve as well as flatten it?
Local storage can provide operating reserves and grid-stability services, reducing the need to keep thermal generators partially loaded and lowering minimum-generation constraints.
How much did the modeled minimum-generation level fall when flexibility was increased?
From about 12,600 MW to about 10,000 MW.
How did increased operational flexibility affect instantaneous curtailment in the analyzed day?
It reduced instantaneous curtailment from about 7,000 MW to less than 4,000 MW.
What solar penetration range could be accommodated with relatively low curtailment after improving system flexibility?
About 20–25%, with the potential to reach roughly 25–30% when demand response is also used.
What additional options could help integrate more solar beyond storage and demand response?
More electricity storage, concentrating solar power with thermal storage, greater regional interchange, and building thermal storage.
How did the duck-curve study represent Diablo Canyon’s operating flexibility?
As a baseload plant whose output did not change.
What storage deployment did California’s mandate specify?
1.325 GW of storage, with procurement timing and sector allocations specified but no single storage technology required.
What renewable-generation cases were used in the storage study?
Cases with 33% and 40% renewable generation.
What did the storage study’s production-cost model simulate?
Unit commitment, energy dispatch, and reserve provision at an hourly time step.
What additional modeling approach was used to assess storage revenues?
A six-price optimization model using historical prices.
How were the storage study’s base cases structured?
They compared a no-storage case with storage removed from the system against a case adding the mandated storage, then varied whether storage provided energy, reserves, or both.
What types of sensitivities did the storage study examine?
Regulation-focused operation, longer duration, different values assigned to curtailed energy, removal of export limits, and different storage capacities.
How much did mandated storage reduce system-wide production costs in the modeled cases?
About 78–144 million, depending on renewable penetration.
What share of storage’s production-cost benefit came from avoiding generator start-up costs?
About 30–67%.
How much of the modeled storage value could be captured by providing ancillary services alone?
About 90%; adding energy-market operation as well increased value by roughly another 10%.
Why may storage’s ancillary-service value decline as more storage enters the market?
Ancillary-service markets are relatively shallow, so additional storage can saturate demand and push prices down.
How did storage affect California and western-system emissions?
It reduced in-state California emissions, but its effect on the entire western system was mixed and could be negative if charging increased coal generation.
How did the marginal value of storage change as more capacity was added?
Each additional unit of storage had less value than the preceding unit.
What storage durations were compared, and what happened when duration increased?
Two-, four-, and six-hour storage were modeled; adding one or four hours of duration produced a relatively modest increase in production-cost savings.
How did removing California’s export limitation affect curtailment and storage value?
It reduced curtailment by allowing freer regional energy exchange, but also relieved flexibility constraints and therefore reduced storage’s value.
How might renewable development elsewhere in the West affect California’s ability to export surplus solar?
It could reduce export opportunities because neighboring regions would also have surplus solar at the same time, increasing the value of storage.