What emissions target did the California low-carbon grid study evaluate for 2030?
What emissions target did the California low-carbon grid study evaluate for 2030?
71 questions
- 1
What emissions target did the California low-carbon grid study evaluate for 2030?
- A
A 33% reduction in electric-sector carbon emissions below 2014 levels
- B
A 50% reduction in electric-sector carbon emissions below 2012 levels
- C
A 50% reduction in economy-wide carbon emissions below 2020 levels
- D
A 57% reduction in electric-sector carbon emissions below 2005 levels
Correct answer
BA 50% reduction in electric-sector carbon emissions below 2012 levels
Explanation
The study examined the feasibility of reducing California electric-sector carbon emissions by 50% below 2012 levels by 2030.
- A
- 2
What role did the study’s economic assessment play relative to its integration analysis?
- A
It replaced the integration analysis by estimating only renewable construction costs
- B
It assessed electricity reliability, while the integration analysis assessed fuel prices
- C
It determined the emissions target, while the integration analysis selected the study sponsors
- D
It was one component, while the presented analysis focused on integration issues from high renewable penetration
Correct answer
DIt was one component, while the presented analysis focused on integration issues from high renewable penetration
Explanation
The study included both an economic assessment and an analysis of integration issues, with the presentation focusing on integration challenges and potential curtailment.
- A
- 3
What was the study’s baseline renewable scenario based on?
- A
California’s 2014 long-term procurement planning 33% case
- B
A historical portfolio with the same generation mix as 2012
- C
California’s later 50% renewable portfolio standard case
- D
A 2030 portfolio with 55% renewable generation and no energy efficiency
Correct answer
ACalifornia’s 2014 long-term procurement planning 33% case
Explanation
The baseline was based on California’s 2014 long-term procurement planning process 33% case and served as a counterfactual for comparison.
- A
- 4
Which renewable penetration did the two target portfolios approximately achieve?
- A
About 55% to 57%
- B
About 33% to 35%
- C
About 40% to 42%
- D
About 65% to 70%
Correct answer
AAbout 55% to 57%
Explanation
Both target portfolios achieved approximately 55% to 57% renewable penetration and met the study’s 50% carbon-reduction target under most modeled conditions.
- A
- 5
How did the diverse target portfolio differ from the target high-solar portfolio?
- A
The diverse portfolio used less energy efficiency but more natural gas
- B
The diverse portfolio relied exclusively on in-state solar and excluded wind
- C
The high-solar portfolio replaced rooftop PV with nuclear generation
- D
The high-solar portfolio substituted more photovoltaic generation for a more diverse resource mix
Correct answer
DThe high-solar portfolio substituted more photovoltaic generation for a more diverse resource mix
Explanation
The target high-solar portfolio traded some resource diversity for more photovoltaic generation. The more diverse portfolio included more out-of-state wind, mostly in-state geothermal, and some biomass.
- A
- 6
Which statement describes rooftop photovoltaic generation across the study’s portfolios?
- A
It was excluded from the target portfolios because it could not be curtailed
- B
It was included only in the high-solar portfolio, at about 24 terawatt-hours
- C
It was assumed to be the same in all portfolios, at about 24 terawatt-hours
- D
It varied with the renewable target, ranging from 12 to 20 terawatt-hours
Correct answer
CIt was assumed to be the same in all portfolios, at about 24 terawatt-hours
Explanation
The study assumed the same rooftop PV generation—about 24 terawatt-hours—in every scenario.
- A
- 7
How did the baseline differ from the two target portfolios in assumed energy efficiency?
- A
Only the high-solar portfolio included energy-efficiency savings
- B
The target portfolios included about 20 terawatt-hours more energy efficiency
- C
The baseline included about 20 terawatt-hours more energy efficiency
- D
All three portfolios assumed identical energy-efficiency savings
Correct answer
BThe target portfolios included about 20 terawatt-hours more energy efficiency
Explanation
The target portfolios were assumed to have about 20 terawatt-hours more energy efficiency than the baseline.
- A
- 8
Why did the study retire Diablo Canyon in its modeled assumptions?
- A
The study treated nuclear generation as a source of renewable energy
- B
Retiring a zero-carbon plant was a conservative, more challenging assumption for system operation
- C
The study assumed the plant had already stopped producing electricity in 2012
- D
Retirement reduced the renewable generation required to meet the carbon target
Correct answer
BRetiring a zero-carbon plant was a conservative, more challenging assumption for system operation
Explanation
The team chose retirement as the more challenging of the two assumptions: replacing the zero-carbon plant with additional renewables could increase integration challenges.
- A
- 9
How did the study treat additional offshore wind in California?
- A
It included offshore wind only in the baseline portfolio
- B
It excluded additional offshore wind, noting that floating platforms were costly in the near term
- C
It included offshore wind as the largest source in both target portfolios
- D
It assumed offshore wind would replace all out-of-state wind by 2030
Correct answer
BIt excluded additional offshore wind, noting that floating platforms were costly in the near term
Explanation
The study did not include additional offshore wind. The speaker noted that California offshore wind would largely require floating platforms, which were considered cost-prohibitive in the near term.
- A
- 10
What was the purpose of creating both diverse and high-solar target portfolios?
- A
To identify which portfolio had the greatest nuclear generation
- B
To compare how different resource mixes affect integration challenges, not to endorse one exact portfolio
- C
To compare portfolios with and without rooftop PV
- D
To prove that California should procure only photovoltaic generation
Correct answer
BTo compare how different resource mixes affect integration challenges, not to endorse one exact portfolio
Explanation
The portfolios were constructed to examine the effects of greater diversity versus more solar; they were not presented as specific procurement recommendations.
- A
- 11
Which set of sensitivities was included in the low-carbon grid analysis?
- A
Population growth, electric-vehicle battery chemistry, and international fuel exports
- B
Only hourly weather, rooftop PV adoption, and retail electricity tariffs
- C
Demand response, western renewable levels, gas and CO₂ prices, and wet- or dry-year hydro
- D
Only solar costs, transmission construction dates, and nuclear operating costs
Correct answer
CDemand response, western renewable levels, gas and CO₂ prices, and wet- or dry-year hydro
Explanation
The study varied demand-side flexibility, western-wide renewable penetration, gas prices, CO₂ prices, and hydro availability, including wet- and dry-year cases.
- A
- 12
Under the conventional flexibility case, what share of specified out-of-state generation had to be imported into California each hour?
- A
70%, including specified renewables, Palo Verde nuclear, and Hoover hydro
- B
100%, including every available out-of-state generator
- C
25%, including only out-of-state wind and solar
- D
50%, including all generation in the western region
Correct answer
A70%, including specified renewables, Palo Verde nuclear, and Hoover hydro
Explanation
The conventional case required 70% of specified out-of-state, California-titled renewable generation—along with Palo Verde nuclear and Hoover hydro—to be imported in every hour.
- A
- 13
How did the enhanced flexibility case treat imports and exports?
- A
It required the same minimum imports as the conventional case but allowed more exports
- B
It prohibited imports while requiring California to export renewable electricity
- C
It removed physical limits on imports and exports as well as all market constraints
- D
It imposed physical limits but did not require specified generation to be imported
Correct answer
DIt imposed physical limits but did not require specified generation to be imported
Explanation
The enhanced case retained physical import and export limits but removed the requirement to import specified generation at every hour.
- A
- 14
What did the conventional case’s 25% local-generation rule require?
- A
At least 25% generation within California balancing authorities from local fossil-fuel and hydro sources
- B
At least 25% of each hour’s demand to be met by storage
- C
At least 25% of out-of-state imports to come from local hydro plants
- D
At least 25% of California’s electricity to come from rooftop solar
Correct answer
AAt least 25% generation within California balancing authorities from local fossil-fuel and hydro sources
Explanation
The conventional case required a 25% minimum generation contribution within California balancing authorities from local fossil-fuel and hydro sources.
- A
- 15
What happened to the local-generation requirement in the enhanced flexibility case?
- A
It was applied only to renewable generators
- B
It was removed
- C
It was increased from 25% to 70%
- D
It was converted into a minimum storage requirement
Correct answer
BIt was removed
Explanation
The enhanced flexibility case had no local-generation requirement.
- A
- 16
What storage resources were assumed in the two flexibility cases?
- A
The conventional case had 1 GW of pumped hydro; the enhanced case replaced it with 1.5 GW of batteries
- B
Both cases had 1.2 GW of compressed-air storage and no batteries
- C
The conventional case had about 1.5 GW of batteries; the enhanced case added 1 GW of California pumped hydro and 1.2 GW of out-of-state compressed-air storage
- D
The conventional case had no storage; the enhanced case had only 1.5 GW of batteries
Correct answer
CThe conventional case had about 1.5 GW of batteries; the enhanced case added 1 GW of California pumped hydro and 1.2 GW of out-of-state compressed-air storage
Explanation
The conventional case included about 1.5 GW of battery storage. The enhanced case retained that assumption and added 1 GW of new California pumped hydro and 1.2 GW of out-of-state compressed-air energy storage.
- A
- 17
How did the cases differ in the ability of hydro and pumped-hydro resources to provide ancillary services?
- A
The conventional case limited their provision to approximate 2013 levels, while the enhanced case used less restrictive limits
- B
The conventional case allowed unlimited provision, while the enhanced case prohibited it
- C
Both cases required hydro to provide exactly the same amount of ancillary services
- D
The enhanced case limited hydro to 2013 levels, while the conventional case had no limits
Correct answer
AThe conventional case limited their provision to approximate 2013 levels, while the enhanced case used less restrictive limits
Explanation
The conventional case was tuned to approximate 2013 ancillary-service provision. The enhanced case allowed hydro and pumped hydro to provide more, subject to less strict limits.
- A
- 18
Why were limits placed on hydro’s modeled ancillary-service contribution?
- A
Hydro plants were assumed to be unable to provide ancillary services
- B
Without the limits, the model relied on hydro and pumped storage for a very large share of ancillary services
- C
The limits were needed to prevent hydro from meeting renewable targets
- D
The model assumed that ancillary services could only come from fossil-fuel plants
Correct answer
BWithout the limits, the model relied on hydro and pumped storage for a very large share of ancillary services
Explanation
When constrained only by physical limits, the model tended to use hydro and pumped storage for a very large percentage of ancillary-service provision, so the study imposed limits in the conventional case.
- A
- 19
What does the study indicate about combining multiple grid-flexibility constraints?
- A
Their combined impact is smaller than every individual impact
- B
Their combined impact disappears when renewable penetration increases
- C
Their combined impact can be greater than the sum of their separate impacts
- D
Their combined impact is always equal to the largest individual impact
Correct answer
CTheir combined impact can be greater than the sum of their separate impacts
Explanation
The study noted that the combined effect of the four flexibility assumptions could be more significant than the sum of their individual effects.
- A
- 20
How did the model represent power exchange across western regions?
- A
It used west-wide optimization while applying hurdle rates to constrain interregional flows
- B
It optimized only California and treated all neighboring systems as fixed
- C
It assumed unlimited transmission and no constraints on interregional flows
- D
It optimized each region independently and prohibited power exchange
Correct answer
AIt used west-wide optimization while applying hurdle rates to constrain interregional flows
Explanation
The model assumed optimal west-wide dispatch but used hurdle rates to represent constraints on power flows and their optimization between regions.
- A
- 21
What was the modeled effect of three million electric vehicles on California’s electricity system?
- A
They added about 3 TWh of load but could not shift charging to other hours
- B
They reduced annual load by about 13 TWh and provided 3,000 MW of generation
- C
They added about 13 TWh of annual load and could provide up to 3,000 MW of additional load, especially during curtailment
- D
They added 13 TWh of load only during summer evenings
Correct answer
CThey added about 13 TWh of annual load and could provide up to 3,000 MW of additional load, especially during curtailment
Explanation
The study assumed three million EVs, adding 13 TWh of load and creating the possibility of up to 3,000 MW of additional load, particularly at times when renewable energy might otherwise be curtailed.
- A
- 22
Which transmission additions were assumed in the target portfolios?
- A
A north-south line from Idaho to Southern Nevada and transmission from New Mexico to the Western grid
- B
A line from California to British Columbia and a direct link to eastern Canada
- C
A line from Texas to Northern California and a direct offshore-wind connection
- D
New transmission only within California, with no out-of-state connections
Correct answer
AA north-south line from Idaho to Southern Nevada and transmission from New Mexico to the Western grid
Explanation
The target portfolios included a north-south line from Idaho to Southern Nevada, approximating the Swift line, and transmission to bring New Mexico generation onto the Western grid.
- A
- 23
How did the study assess whether California could meet its 50% carbon-reduction target?
- A
None of the cases met it unless offshore wind was added
- B
All modeled scenarios met it except the dry-hydro case
- C
Only the diverse target portfolio met it
- D
Only the enhanced flexibility cases met it
Correct answer
BAll modeled scenarios met it except the dry-hydro case
Explanation
The study found the target achievable across a wide range of scenarios, with the exception of the dry-hydro assumption.
- A
- 24
Why were emissions lower in the enhanced flexibility cases than in the conventional cases?
- A
Reduced curtailment meant less fossil generation was needed to replace unused renewable energy
- B
The conventional cases had higher renewable penetration than the enhanced cases
- C
Enhanced flexibility cases included more nuclear generation than the conventional cases
- D
The enhanced cases assumed lower electricity demand in every hour
Correct answer
AReduced curtailment meant less fossil generation was needed to replace unused renewable energy
Explanation
Conventional-case curtailment required more fossil-fuel operation to make up for renewable generation that could not be used. Enhanced flexibility reduced this effect.
- A
- 25
How did the high-solar portfolio affect curtailment under conventional flexibility compared with the more diverse portfolio?
- A
It eliminated curtailment by spreading solar output across more hours
- B
It reduced curtailment by replacing solar with geothermal generation
- C
It produced the same curtailment because all portfolios had identical resource mixes
- D
It produced somewhat more curtailment
Correct answer
DIt produced somewhat more curtailment
Explanation
The high-solar portfolio had somewhat more curtailment than the more diverse portfolio, particularly under conventional flexibility.
- A
- 26
What production-cost reduction was estimated for the target portfolio?
- A
About 5.1billionto6.0 billion
- B
About 65millionto80 million
- C
About 4.3billionto4.8 billion
- D
About 500millionto800 million
Correct answer
CAbout 4.3billionto4.8 billion
Explanation
The target portfolio showed a production-cost reduction of approximately 4.3billionto4.8 billion.
- A
- 27
How did flexibility assumptions affect operating costs in the baseline case?
- A
Enhanced flexibility was worth about $65 million per year, a modest share of total operating costs
- B
Enhanced flexibility was worth more than $500 billion per year
- C
Conventional flexibility reduced costs by about $4.8 billion per year
- D
The two flexibility cases had identical operating costs in the baseline
Correct answer
AEnhanced flexibility was worth about $65 million per year, a modest share of total operating costs
Explanation
In the baseline case, enhanced flexibility was worth about 65millionperyearinoperatingcosts,smallcomparedwithtotaloperatingcostsexceeding10 billion.
- A
- 28
How did the value of flexibility change between the baseline and target portfolios?
- A
Its operational value was modest in the baseline but much larger above 50% renewable penetration
- B
It mattered only when renewable penetration was below 33%
- C
It was large in the baseline but disappeared in the target portfolios
- D
It was identical across all renewable penetration levels
Correct answer
AIts operational value was modest in the baseline but much larger above 50% renewable penetration
Explanation
The value of flexibility was relatively modest at low renewable penetration but increased substantially in the target portfolios, where renewable penetration exceeded 50%.
- A
- 29
What combination primarily drove high curtailment in the conventional flexibility cases?
- A
The transmission additions combined with the enhanced import rules
- B
The electric-vehicle load combined with the rooftop PV assumption
- C
The lower gas prices combined with the wet-hydro assumption
- D
The 25% local-generation requirement combined with the 70% import requirement
Correct answer
DThe 25% local-generation requirement combined with the 70% import requirement
Explanation
The combination of the local-generation minimum and the requirement to import a specified share of out-of-state generation was a major driver of curtailment.
- A
- 30
What range of adverse outcomes was associated with less flexible institutions and a less diverse, high-solar portfolio?
- A
Curtailment up to 20%, operating costs up to $4.8 billion higher, and emissions up to 50% higher
- B
Curtailment up to 10%, operating costs up to $800 million higher, and emissions up to 14% higher
- C
Curtailment eliminated, operating costs unchanged, and emissions reduced by 14%
- D
Curtailment up to 1%, operating costs up to $65 million higher, and emissions up to 2% higher
Correct answer
BCurtailment up to 10%, operating costs up to $800 million higher, and emissions up to 14% higher
Explanation
The study concluded that a less flexible institutional framework combined with a less diverse portfolio could lead to curtailment as high as 10%, operating costs up to $800 million higher, and emissions up to 14% higher.
- A
- 31
How did the estimated annualized capital cost of the target enhanced portfolio compare with its production-cost reduction?
- A
It was about 10billion,roughly4.8 billion more than the production-cost reduction
- B
It was about 65million,roughly5.1 billion less than the production-cost reduction
- C
It was about 4.3billion,roughly800 million less than the production-cost reduction
- D
It was about 5.1billion,roughly230 million more than the production-cost reduction
Correct answer
DIt was about 5.1billion,roughly230 million more than the production-cost reduction
Explanation
The companion cost analysis estimated annualized capital costs of about 5.1billion,approximately230 million above the production-cost reduction.
- A
- 32
How did the companion capital-cost analysis describe the possible range of economic outcomes?
- A
Depending on assumptions, from a 3% cost benefit to a 6% cost increase in annual revenue requirement
- B
Always a 3% cost increase, regardless of gas prices or discount rates
- C
From a 30% cost benefit to a 60% cost increase in annual revenue requirement
- D
Always a 6% cost benefit, regardless of economic conditions
Correct answer
ADepending on assumptions, from a 3% cost benefit to a 6% cost increase in annual revenue requirement
Explanation
Depending on gas prices, discount rates, and economic conditions, the analysis found a range from a 3% cost benefit to a 6% cost increase relative to annual revenue requirements.
- A
- 33
What was the nature of the study’s assessment of dynamic grid issues?
- A
It measured only the cost of replacing Diablo Canyon
- B
It was a quantitative stability simulation proving that no risks existed
- C
It demonstrated that curtailment was the only way to maintain stability
- D
It was qualitative and identified potential risks as well as mitigation options
Correct answer
DIt was qualitative and identified potential risks as well as mitigation options
Explanation
The dynamic-issues companion analysis was qualitative. It identified potential risks and noted that mitigation options could provide reliability at lower cost and emissions than curtailment alone.
- A
- 34
What is meant by “overgeneration” in the solar-integration analysis?
- A
Generating more electricity during winter than during summer
- B
Producing more electricity than a generator’s nameplate capacity
- C
Using electricity storage to supply more power than it receives
- D
Having more electricity available than the system can use or otherwise accommodate
Correct answer
DHaving more electricity available than the system can use or otherwise accommodate
Explanation
Overgeneration occurs when the system has more energy than it knows what to do with, often because demand and system flexibility cannot accommodate available generation.
- A
- 35
Why is renewable curtailment technically straightforward but still undesirable?
- A
Turning down wind and solar always creates more electricity than the system needs
- B
Curtailment requires fossil-fuel generators to operate at full output
- C
Wind and utility-scale solar can be turned down, but doing so wastes zero-cost, zero-carbon energy
- D
Wind and solar cannot be controlled, but curtailment increases their output
Correct answer
CWind and utility-scale solar can be turned down, but doing so wastes zero-cost, zero-carbon energy
Explanation
Large-scale wind and solar can generally be curtailed, making overgeneration technically manageable. However, curtailment throws away energy with no fuel cost and no direct carbon emissions.
- A
- 36
Why can curtailing residential rooftop PV be more complicated than curtailing utility-scale solar?
- A
Residential systems produce electricity only at night
- B
Utility-scale solar cannot be controlled by grid operators
- C
Rooftop PV is always connected directly to long-distance transmission lines
- D
Controlling large numbers of distributed rooftop systems may be difficult at very high penetration
Correct answer
DControlling large numbers of distributed rooftop systems may be difficult at very high penetration
Explanation
The analysis noted that curtailing utility-scale solar is straightforward, while managing residential rooftop PV could become more complicated at very high penetration.
- A
- 37
What did the duck-curve analysis modify before examining higher solar penetration?
- A
It made the low-carbon grid framework more like the contemporary grid, including restoring Diablo Canyon and adjusting geothermal
- B
It removed all existing storage and added offshore wind
- C
It replaced California’s grid with an isolated system without imports
- D
It assumed California had already reached 50% solar generation
Correct answer
AIt made the low-carbon grid framework more like the contemporary grid, including restoring Diablo Canyon and adjusting geothermal
Explanation
The analysis reused much of the low-carbon grid study’s modeling framework but adjusted assumptions to resemble the grid of the time, including bringing Diablo Canyon back into the modeled system.
- A
- 38
What did the duck-curve analysis assume about the energy imbalance market?
- A
It did not explicitly model the market’s short-term balancing function
- B
It assumed the market prevented California from exchanging power with neighbors
- C
It modeled the market as the only source of interregional flexibility
- D
It assumed the market eliminated all transmission constraints
Correct answer
AIt did not explicitly model the market’s short-term balancing function
Explanation
The model allowed California to interact with neighboring systems using hurdle rates, but it did not explicitly model the energy imbalance market’s short-term balancing function.
- A
- 39
Why did the modelled net load on the spring day not fall as low as the duck curve might suggest?
- A
The system had no renewable generation available during midday
- B
The model assumed that all solar generation was exported
- C
Summer air-conditioning demand kept the spring load unusually high
- D
Minimum-generation constraints prevented thermal and hydro plants from ramping down far enough
Correct answer
DMinimum-generation constraints prevented thermal and hydro plants from ramping down far enough
Explanation
Thermal and hydro generators could not be reduced below their assumed minimum generation levels, so net load could not fall to the lowest theoretical values.
- A
- 40
In the 11% annual-solar example, what happened on the spring day with low midday net load?
- A
About 25% of annual electricity demand was curtailed
- B
The system shut down all hydro and thermal generation
- C
About 5% of potential wind and solar generation was curtailed
- D
All wind and solar generation was used without curtailment
Correct answer
CAbout 5% of potential wind and solar generation was curtailed
Explanation
On the example spring day, minimum-generation constraints led to curtailment of about 5% of potential wind and solar generation.
- A
- 41
How did existing pumped-hydro storage help reduce curtailment in the spring example?
- A
It generated at maximum output during the midday surplus
- B
It exported its stored energy to neighboring regions during the surplus
- C
It replaced all thermal generation during the evening ramp
- D
It pumped during the midday surplus, absorbing some low-cost electricity
Correct answer
DIt pumped during the midday surplus, absorbing some low-cost electricity
Explanation
Changing the usual pumping and discharge pattern allowed existing pumped hydro to pump during the day, absorbing low-cost energy and avoiding some midday curtailment.
- A
- 42
Why was curtailment limited during summer in the analyzed grid conditions?
- A
Hydro plants were assumed to provide unlimited storage
- B
Solar generation was assumed to stop during summer
- C
The model required all summer renewable energy to be exported
- D
Midday air-conditioning demand kept electricity demand relatively high
Correct answer
DMidday air-conditioning demand kept electricity demand relatively high
Explanation
Summer air-conditioning demand increased midday electricity demand, so the low-demand conditions associated with spring curtailment were less pronounced.
- A
- 43
What is marginal curtailment, and why does it matter as solar penetration rises?
- A
It is the share of total electricity demand served by storage; a rising share lowers solar costs
- B
It is the share of additional solar energy that is curtailed; a rising share makes each added unit less valuable
- C
It is the share of annual solar generation occurring at midday; a rising share eliminates overgeneration
- D
It is the share of existing thermal capacity retired; a rising share increases solar output
Correct answer
BIt is the share of additional solar energy that is curtailed; a rising share makes each added unit less valuable
Explanation
Marginal curtailment refers to curtailment of the incremental solar energy added to the system. As it increases, a smaller share of new solar energy is usable, reducing its value.
- A
- 44
At about 20% solar penetration in the modeled system, what happened to the value of incremental solar?
- A
Roughly 30% to 40% of incremental solar energy could be curtailed
- B
All incremental solar energy remained usable in every hour
- C
Curtailment fell to zero because solar generation became more diverse
- D
The system required every incremental unit to be stored for later use
Correct answer
ARoughly 30% to 40% of incremental solar energy could be curtailed
Explanation
At around 20% solar, marginal curtailment was about 30% to 40%, meaning only roughly 60% to 70% of incremental solar energy could be used.
- A
- 45
Why can high marginal curtailment raise the effective cost of solar energy that is actually sold?
- A
The investment cost is spread over fewer usable kilowatt-hours
- B
Curtailment forces solar generators to buy additional fuel
- C
Curtailment increases the fuel cost of each solar kilowatt-hour
- D
Solar panels require more energy to produce electricity after curtailment
Correct answer
AThe investment cost is spread over fewer usable kilowatt-hours
Explanation
When more generated energy is curtailed, the costs of the solar installation are recovered over fewer usable kilowatt-hours, increasing the effective cost of the energy sold.
- A
- 46
What does “fattening the duck” mean in the solar-integration discussion?
- A
Shifting more demand from midday to evening through storage
- B
Allowing more midday solar output by reducing minimum-generation constraints
- C
Increasing solar curtailment to preserve thermal-generator output
- D
Increasing the amount of nighttime solar generation
Correct answer
BAllowing more midday solar output by reducing minimum-generation constraints
Explanation
Fattening the duck means accommodating the midday solar surplus by making the system able to operate with lower minimum generation.
- A
- 47
What does “flattening the duck” generally involve?
- A
Shifting or adding demand in the middle of the day for use at other times
- B
Restricting electricity exchange with neighboring regions
- C
Moving all solar generation from midday to nighttime
- D
Increasing thermal minimum-generation levels during midday
Correct answer
AShifting or adding demand in the middle of the day for use at other times
Explanation
Flattening the duck involves shifting or adding demand during the solar-rich middle of the day, for example through demand response or storage, and using that energy later.
- A
- 48
How can storage help flatten the duck?
- A
It can increase minimum thermal generation during midday
- B
It can charge during midday and discharge later, shifting energy to higher-demand hours
- C
It can generate additional energy without first charging
- D
It can prevent renewable generators from producing during the evening
Correct answer
BIt can charge during midday and discharge later, shifting energy to higher-demand hours
Explanation
Storage can absorb energy during the midday surplus and deliver it later, shifting energy use away from the low-net-load period.
- A
- 49
How can storage also help fatten the duck, beyond shifting energy?
- A
It can make solar generators produce more energy at night
- B
It can provide some grid services, reducing the need to keep thermal plants partially loaded
- C
It can increase the minimum output required from hydro plants
- D
It can eliminate the need for all transmission and generation
Correct answer
BIt can provide some grid services, reducing the need to keep thermal plants partially loaded
Explanation
Storage can provide services such as operating reserves and support for frequency and voltage stability, potentially reducing reliance on partially loaded thermal generators and lowering minimum-generation constraints.
- A
- 50
What was the modeled effect of adding the California storage mandate’s storage on the example spring day?
- A
It reduced instantaneous curtailment by a little over 1,000 MW
- B
It reduced annual electricity demand by 1,325 TWh
- C
It increased instantaneous curtailment by about 7,000 MW
- D
It eliminated all curtailment without changing system operations
Correct answer
AIt reduced instantaneous curtailment by a little over 1,000 MW
Explanation
Adding the mandated storage allowed energy to be shifted and reduced instantaneous curtailment by a little over 1,000 MW in the example.
- A
- 51
What was the effect of lowering the modeled minimum-generation level using added flexibility?
- A
It forced the system to export all solar energy generated in California
- B
It had no effect on the system’s ability to use midday solar
- C
It allowed the system to reach about 10,000 MW instead of roughly 12,600 MW and reduced curtailment
- D
It raised the minimum to about 12,600 MW from roughly 10,000 MW and increased curtailment
Correct answer
CIt allowed the system to reach about 10,000 MW instead of roughly 12,600 MW and reduced curtailment
Explanation
With added flexibility, the modeled minimum-generation level fell from about 12,600 MW to about 10,000 MW, allowing more solar energy to be accommodated.
- A
- 52
How much did instantaneous curtailment fall in the example when operational flexibility was increased?
- A
From 4,000 MW to about 7,000 MW
- B
From about 12,600 MW to exactly 10,000 MW
- C
From 1,325 MW to zero
- D
From about 7,000 MW to less than 4,000 MW
Correct answer
DFrom about 7,000 MW to less than 4,000 MW
Explanation
The analysis showed instantaneous curtailment falling from about 7,000 MW to below 4,000 MW after changes that increased flexibility.
- A
- 53
Which other options were identified as potentially helping accommodate higher solar penetration?
- A
Less transmission, fewer flexible loads, and higher minimum thermal generation
- B
Replacing all utility-scale solar with residential rooftop systems
- C
More coal generation, fewer interconnections, and reduced hydro flexibility
- D
More electricity storage, concentrating solar power with thermal storage, and greater regional interchange
Correct answer
DMore electricity storage, concentrating solar power with thermal storage, and greater regional interchange
Explanation
The discussion identified additional electricity storage, concentrating solar power with thermal storage, and greater interchange between regions as possible flexibility options.
- A
- 54
What California storage mandate was examined in the storage study?
- A
1.325 GW of storage, with procurement timing and sector specified but technology type not prescribed
- B
1.325 GW of battery storage, all required at transmission substations
- C
1 GW of pumped hydro, with no distribution or customer-sited resources
- D
3 GW of storage, with all procurement required in a single year
Correct answer
A1.325 GW of storage, with procurement timing and sector specified but technology type not prescribed
Explanation
The mandate called for 1.325 GW of storage. It specified when procurement would occur and across which sectors, but did not prescribe a particular storage technology.
- A
- 55
Which storage locations or sectors were represented in the California mandate?
- A
Only customer-side batteries and residential rooftop solar
- B
Transmission-sited, distribution-sited, and customer-side or behind-the-meter storage
- C
Only large power plants and out-of-state storage facilities
- D
Only transmission-sited pumped hydro and industrial thermal storage
Correct answer
BTransmission-sited, distribution-sited, and customer-side or behind-the-meter storage
Explanation
The mandate’s procurement was divided among transmission, distribution, and customer-side or behind-the-meter sectors.
- A
- 56
Which renewable penetration cases were used in the storage study’s production-cost modeling?
- A
40% and 55% renewable generation
- B
50% and 57% renewable generation
- C
15% and 20% renewable generation
- D
33% and 40% renewable generation
Correct answer
D33% and 40% renewable generation
Explanation
The storage study used long-term procurement planning information and examined 33% and 40% renewable-generation cases.
- A
- 57
What did the production-cost model simulate, and at what time step?
- A
Generator siting, market bidding, and storage manufacturing at a monthly time step
- B
Retail billing, customer adoption, and fuel extraction at a daily time step
- C
Transmission construction, equipment maintenance, and emissions at a yearly time step
- D
Unit commitment, energy dispatch, and reserves at an hourly time step
Correct answer
DUnit commitment, energy dispatch, and reserves at an hourly time step
Explanation
The production-cost model simulated unit commitment, energy dispatch, and provision of reserves using hourly time steps.
- A
- 58
What additional modeling approach was used to estimate storage revenues?
- A
A capacity-expansion model using projected fuel reserves
- B
A six-price optimization model using historical prices
- C
A transmission-planning model using annual average prices
- D
A reliability model using only generator outage records
Correct answer
BA six-price optimization model using historical prices
Explanation
Alongside the production-cost model, the study used a six-price optimization model based on historical prices to examine revenues.
- A
- 59
Why did the study compare storage cases that provided energy, reserves, or both?
- A
To isolate how the value of storage changed with the services it provided
- B
To compare renewable portfolios without modeling storage operation
- C
To ensure every storage technology had the same discharge duration
- D
To determine which storage type required the fewest transmission lines
Correct answer
ATo isolate how the value of storage changed with the services it provided
Explanation
The study tested different service configurations—energy, ancillary services, both, or reserves only—to identify where storage value came from.
- A
- 60
What range of system-wide operating-cost reductions was associated with adding storage?
- A
About 230millionto500 million
- B
About 4.3billionto4.8 billion
- C
About 5.1billionto10 billion
- D
About 78millionto144 million
Correct answer
DAbout 78millionto144 million
Explanation
Compared with a system without storage, adding storage reduced modeled system-wide production costs by approximately 78millionto144 million, depending on renewable penetration.
- A
- 61
What share of the production-cost reduction from storage came from avoided generator start-up costs?
- A
About 30% to 67%
- B
About 1% to 3%
- C
About 70% to 90%
- D
About 5% to 10%
Correct answer
AAbout 30% to 67%
Explanation
Avoided generator start-up costs accounted for approximately 30% to 67% of the production-cost reduction, even though these savings were not then typically compensated through energy or other markets.
- A
- 62
How did the study characterize the value of storage providing ancillary services alone?
- A
It captured about 90% of the value of adding storage
- B
It was worth more than all energy and capacity services combined
- C
It captured about 10% of the value of adding storage
- D
It provided no value until storage also supplied energy
Correct answer
AIt captured about 90% of the value of adding storage
Explanation
The study found that storage providing ancillary services alone could achieve about 90% of the value of adding storage.
- A
- 63
What happened when storage was additionally allowed to provide energy as well as ancillary services?
- A
The modeled value increased by about 100%
- B
The modeled value remained exactly unchanged
- C
The modeled value increased by about another 10%
- D
The modeled value fell by about 90%
Correct answer
CThe modeled value increased by about another 10%
Explanation
Allowing storage to provide energy in addition to ancillary services increased the value by about 10% in the modeled cases.
- A
- 64
Why may the value of storage in ancillary-service markets be limited as storage deployment grows?
- A
Ancillary services can only be supplied by fossil-fuel plants
- B
Storage cannot respond quickly enough to provide ancillary services
- C
These markets are relatively shallow and can become saturated
- D
Ancillary-service prices always rise when more storage enters the market
Correct answer
CThese markets are relatively shallow and can become saturated
Explanation
Ancillary-service markets are relatively shallow, so large amounts of storage can saturate them and reduce the value available to additional storage.
- A
- 65
What was the modeled effect of storage on emissions within California compared with the entire western system?
- A
It increased California emissions but always reduced western emissions
- B
It reduced emissions equally in California and every neighboring region
- C
It had no possible effect on emissions in either area
- D
It reduced California emissions, but its effect across the full system could be mixed
Correct answer
DIt reduced California emissions, but its effect across the full system could be mixed
Explanation
Storage could reduce in-state emissions, while the system-wide effect was mixed because charging could increase generation from higher-emitting resources elsewhere.
- A
- 66
How could storage charging potentially worsen emissions outside California?
- A
Discharging could increase the fuel use of every hydro plant
- B
Charging could increase generation from coal plants in neighboring regions
- C
Charging could eliminate the need for regional electricity exchange
- D
Charging could force California to retire all renewable generators
Correct answer
BCharging could increase generation from coal plants in neighboring regions
Explanation
Depending on the resource mix outside California, charging storage could increase generation from coal and thereby have a negative effect on system-wide emissions.
- A
- 67
What was the general effect of adding more storage capacity on the value of each additional unit?
- A
The incremental value became negative as soon as storage was installed
- B
The incremental value declined as more storage was added
- C
The incremental value remained exactly the same at every capacity level
- D
The incremental value increased at a constant rate
Correct answer
BThe incremental value declined as more storage was added
Explanation
The study found diminishing incremental value: each additional unit of storage was worth less than the previous one as total storage increased.
- A
- 68
What storage durations were compared, and what was the general effect of increasing duration?
- A
One, two, and three days; longer duration doubled cost savings
- B
Two, four, and six hours; longer duration produced a relatively modest increase in cost savings
- C
One, four, and eight hours; longer duration eliminated operating costs
- D
Four, eight, and twelve hours; duration had no effect in any scenario
Correct answer
BTwo, four, and six hours; longer duration produced a relatively modest increase in cost savings
Explanation
The model compared two-, four-, and six-hour storage. Increasing duration by one or four hours produced a relatively modest increase in production-cost reductions.
- A
- 69
What did the storage study find when storage was focused specifically on providing regulation?
- A
Regulation prices rose continuously as storage entered the market
- B
Storage could not provide regulation under any modeled condition
- C
The regulation market could become saturated, producing zero prices in the model
- D
Regulation eliminated all renewable curtailment in California
Correct answer
CThe regulation market could become saturated, producing zero prices in the model
Explanation
The modeled regulation market was shallow enough that storage could saturate it, producing zero prices in the model. The presenter cautioned that this result partly reflected the model and might not occur identically in actual markets.
- A
- 70
How did removing California’s export limitation affect curtailment and storage value?
- A
It reduced curtailment through greater regional exchange, but also reduced storage’s value by easing flexibility constraints
- B
It increased curtailment and increased storage’s value by isolating California
- C
It eliminated exports and raised storage value by increasing local constraints
- D
It had no effect on either curtailment or storage value
Correct answer
AIt reduced curtailment through greater regional exchange, but also reduced storage’s value by easing flexibility constraints
Explanation
Allowing freer imports and exports improved regional cooperation and reduced curtailment, but also relieved some flexibility constraints that otherwise increased the value of storage.
- A
- 71
How could greater renewable development across the West affect California’s ability to export surplus energy?
- A
It would guarantee that neighboring regions could absorb all California surplus
- B
It could reduce export opportunities because neighboring regions may have surplus renewable energy at the same time
- C
It would increase California’s export opportunities because solar output occurs at different times everywhere
- D
It would eliminate the need for storage by increasing fossil-fuel output
Correct answer
BIt could reduce export opportunities because neighboring regions may have surplus renewable energy at the same time
Explanation
If neighboring regions add similar renewable portfolios, they may have surplus solar generation at the same time as California and be less able to absorb California’s exports. This can increase the value of storage.
- A