Grid Integration in California


Grid Integration in California

Simon
Welcome to the episode. We’re unpacking a webinar about California’s path to a low-carbon electric grid—and two connected questions: what happens as renewable generation grows, and how can flexibility and storage help the system manage it?

Maria
The discussion brings together three studies. First, the California 2030 Low Carbon Grid Study looks at reaching a major emissions target. Then a solar-integration study explores the familiar duck curve and renewable curtailment. Finally, a storage study examines what energy storage can contribute and how its value changes under different conditions.

Simon
Let’s start with the first study. It was supported by a diverse group of funders, while a separate, independent technical review committee examined assumptions and methods. The study team was responsible for its conclusions, which didn’t necessarily represent the views of every sponsoring organization.

Maria
And what was the central question? Whether California could cut electric-sector carbon emissions by 50 percent below 2012 levels by 2030—and what integration challenges might arise as the state relied on more renewable energy.

Simon
The team considered both economics and grid integration, including the possibility of curtailment. They also ran many scenarios and sensitivities to understand which assumptions drive the results. The presentation focused mainly on bookend cases: one with conventional flexibility assumptions and one with enhanced flexibility.

Maria
Before we get to flexibility, there were three renewable portfolios. The baseline reflected California’s 2014 long-term procurement planning case with 33 percent renewables. It served as a counterfactual comparison, even though California later adopted a higher renewable requirement.

Simon
The other two were target portfolios designed to reach roughly 55 to 57 percent renewable penetration and meet the 50 percent carbon-reduction goal. One was more diverse; the other had more solar photovoltaic generation. Both also assumed the same rooftop solar generation—24 terawatt-hours.

Maria
The diverse portfolio substituted some of the high-solar case’s photovoltaic generation with out-of-state wind, mostly in-state geothermal, and a little biomass. The solar-heavy portfolio reflected procurement trends the researchers saw at the time. The comparison was meant to reveal how diversity could affect system operation, not to endorse one exact future portfolio.

Simon
There was also about a 20-terawatt-hour difference in energy efficiency between the baseline and the target portfolios. So the scenarios were not just about changing the mix of renewable generators; they also reflected different levels of efficiency.

Maria
Now to flexibility. The conventional case already assumed more flexibility than the grid had at the time, so it wasn’t simply a picture of the status quo. But compared with the enhanced case, it imposed stricter institutional rules and had less storage and less freedom for some resources.

Simon
One conventional assumption required 70 percent of certain out-of-state, California-titled renewable generation to be imported in every hour. That category also included Palo Verde nuclear power and Hoover hydro. The rule acted as a possible proxy for California’s import requirements, similar to assumptions used in some California ISO planning work.

Maria
The enhanced case removed that must-import rule and retained physical limits on imports and exports. That distinction matters: a state may have the physical ability to trade electricity without being required to import a set amount at every hour.

Simon
A second conventional constraint required at least 25 percent local generation in California balancing authorities, from local fossil-fuel and hydro resources. The concern behind that kind of rule involved issues such as controllability and dynamic operation. The enhanced case did not require a local-generation minimum.

Maria
The third difference was storage. The conventional case included about 1.5 gigawatts of batteries to meet a California Public Utilities Commission requirement. The enhanced case added a gigawatt of new pumped hydro in California and 1.2 gigawatts of compressed-air energy storage in Utah, near the Intermountain Power Project site.

Simon
The fourth difference concerned ancillary services—the support services that help keep the grid operating reliably. In the conventional case, limits on how much hydro and pumped storage could provide were calibrated to roughly match 2013 service levels. In the enhanced case, those limits were less strict.

Maria
Why limit hydro and pumped storage in the model? If their only restrictions were their physical capabilities, the model wanted to use them for a very large share of ancillary services. The researchers used limits so the modeled service provision would better reflect the intended assumptions.

Simon
And these assumptions interact. The combined effect of import rules, local-generation requirements, storage, and ancillary-service limits can be greater than simply adding up each rule’s individual effect. That’s why the study examined whole packages of flexibility assumptions.

Maria
The conventional case also included other important choices. The model optimized dispatch across the wider western system, with hurdle rates limiting how freely electricity could flow between regions. Diablo Canyon nuclear plant was assumed to retire, and the study included three million electric vehicles.

Simon
Those vehicles added about 13 terawatt-hours of annual load and could provide as much as 3,000 megawatts of additional demand, especially at times when renewable generation might otherwise be curtailed. The study also included some coal retirements elsewhere in the West and assumed the Intermountain Power Project plant would retire in 2025.

Maria
For the target portfolios, the team added transmission assumptions, including a north-south line from Idaho to southern Nevada and transmission to bring New Mexico generation onto the Western grid. Across 23 modeled scenarios, they varied portfolios, storage, import rules, local generation, ancillary services, import-schedule flexibility, demand response, gas and carbon prices, and wet- or dry-year hydro conditions.

Simon
The choice to retire Diablo Canyon was deliberately conservative in one sense: the researchers chose the more challenging integration assumption. Replacing a zero-carbon nuclear plant with additional renewable generation could make system operation harder. They also noted that relicensing costs and the plant’s site and cooling issues were part of the uncertainty.

Maria
And offshore wind? It wasn’t included as additional generation in this study. The presenter noted that near-term California offshore wind would largely require floating platforms, which were considered cost-prohibitive at the time, though they might be an option later as the state went beyond 50 percent renewables.

Simon
So what did the scenarios show about the emissions target? California met the 50 percent reduction in almost all modeled cases. The exception was a dry-hydro-year case using the conventional flexibility assumptions: under those conditions, the modeled build-out did not reach the target.

Maria
The flexibility assumptions affected emissions partly through curtailment. When renewable energy was curtailed in the conventional cases, fossil-fuel generation had to make up more of the energy, leading to higher emissions than in the enhanced cases. The high-solar portfolio also tended to have more curtailment than the more diverse portfolio under conventional flexibility.

Simon
The value of the renewable energy and efficiency depended on the rest of the system and its rules. In the target portfolios, the study found production-cost reductions of about 4.3 to 4.8 billion dollars. That’s an operating-cost result, though; it doesn’t by itself tell us whether the investments’ full capital costs are covered.

Maria
That distinction is important. In the baseline case, enhanced flexibility saved about 65 million dollars a year in operating costs compared with conventional flexibility—a modest amount relative to more than 10 billion dollars in total operating costs. In the higher-renewable target cases, the modeled value of enhanced flexibility grew substantially, to more than 500 million dollars in operating benefits.

Simon
Curtailment showed a similar pattern. The combination of a 25 percent local-generation minimum and the 70 percent must-import rule was a major driver in the conventional cases. In the solar-heavy conventional case, curtailment approached 10 percent; several more diverse or flexible cases were below 1 percent.

Maria
A steep evening ramp helps explain why flexibility matters. As the sun sets, solar output falls while electricity demand must still be served, creating a duck-shaped net-load curve. In one target enhanced-flexibility scenario, physical imports, storage, gas generation, demand response, and hydro all helped meet the ramp, though their contributions varied across days and hours.

Simon
The study compared emissions with 2012. The presenter said California emissions had been relatively flat across several nearby years, so choosing a different year in that period would not change the study’s main takeaways much. The assumed gas prices came from projections adjusted for western conditions; changing gas prices could affect the economics of renewables, even if it didn’t alter the central integration findings.

Maria
The overall message was conditional. A low-carbon grid—50 percent below 2012 emissions by 2030—looked achievable with relatively limited curtailment if the system had flexible institutional rules and a diverse generation mix. With less flexibility and a less diverse, solar-heavy portfolio, curtailment could reach 10 percent, operating costs could be up to 800 million dollars higher, and carbon emissions up to 14 percent higher.

Simon
There were companion studies too. One estimated annualized capital costs for incremental renewables, transmission, and storage in the target enhanced portfolio at about 5.1 billion dollars—roughly 230 million dollars more than its production-cost reduction. That difference was estimated at about 0.6 percent of California’s annual revenue requirement, with other economic assumptions producing a range from a small cost benefit to a cost increase.

Maria
Another companion study looked qualitatively at dynamic grid issues rather than fully quantifying them. It identified possible risks but also discussed mitigation options that could support reliability at lower cost and emissions than simply curtailing more renewable energy. The takeaway was to use sound engineering practices and continue studying these questions.

Simon
A question from the webinar audience was why geothermal wasn’t represented at the same level as solar and wind. The answer was that the diverse portfolio was built as a reasonable blend of procurement trends and operational considerations, while the high-solar portfolio helped reveal the effects of a less diverse mix. Neither was presented as a definitive recommendation.

Maria
Imports were another key issue. The diverse target portfolio included about 12 terawatt-hours of wind from Wyoming and roughly 9 or 10 terawatt-hours from New Mexico. Under conventional assumptions, 70 percent of certain out-of-state energy had to be imported in every hour; under enhanced assumptions, that requirement was relaxed.

Simon
That rule kept California from importing below roughly 2,000 megawatts in the conventional cases. In the enhanced cases, California could sometimes export. Allowing imports and exports to respond more freely made a significant difference to integration outcomes, because energy didn’t have to flow into California just because a must-import rule said it should.

Maria
Now let’s turn to the solar-integration study and the duck curve. The California ISO’s 2013 duck chart drew attention to overgeneration risk. Overgeneration simply means there is more electricity available than the system can use at a given time.

Simon
Curtailment is technically straightforward for large wind and solar plants: operators can turn down their output. The challenge is economic and environmental, because curtailment throws away zero-fuel-cost, zero-carbon energy. Managing rooftop solar can become more complicated at high penetrations, since it isn’t controlled in the same way as a large power plant.

Maria
The researchers adapted the Low Carbon Grid Study’s modeling framework to examine a grid closer to the situation they wanted to represent. They added Diablo Canyon back in and adjusted geothermal assumptions, then increased solar generation to see how the duck curve and curtailment changed.

Simon
On a spring day in a scenario with 11 percent annual solar generation, net load fell sharply around midday. But the thermal and hydro fleets could not simply ramp down as far as the curve suggested. Given the modeled minimum-generation constraints, they could only fall to about 12,600 megawatts, and roughly 5 percent of the potential wind and solar generation on that day was curtailed.

Maria
Existing pumped hydro helped, though it couldn’t eliminate the problem. By changing its usual pumping and generation schedule—pumping during the day when solar energy was plentiful—the system could avoid a couple of thousand megawatts of midday curtailment. In summer, high daytime demand, including air-conditioning load, meant the modeled curtailment problem was much smaller or absent.

Simon
As solar increased from 11 percent to 15 percent, the modeled net load dipped even lower—toward 5,000 megawatts in theory. But the minimum-generation constraints meant the conventional fleet couldn’t follow it all the way down. More solar therefore meant more curtailment unless the system became more flexible.

Maria
The study distinguished average curtailment from marginal curtailment. Average curtailment measures how much of the overall renewable energy is lost; marginal curtailment asks how much of the next increment of solar is lost. At around 20 percent solar in the modeled cases, only about 60 to 70 percent of incremental solar energy could be used, meaning 30 to 40 percent was curtailed.

Simon
That makes additional solar less valuable: the project may still generate energy, but the system can use a smaller share of it. The researchers described this as lower energy value or, from another perspective, a higher effective cost for the energy that is actually sold.

Maria
They grouped possible responses into two memorable ideas: flatten the duck or fatten the duck. Flattening means shifting demand away from the evening and toward sunny midday hours, using tools like storage or demand response. Fattening means allowing more of the midday dip by reducing minimum-generation constraints on thermal and hydro resources.

Simon
The storage mandate offered one example of flattening. With the mandated storage added to existing storage, the model shifted some energy from midday to later in the day and reduced instantaneous curtailment by a little over 1,000 megawatts in the example.

Maria
Storage can also help fatten the duck, because it may provide some services otherwise supplied by partially loaded thermal generators. Those generators can be kept online for operating reserves, frequency stability, or voltage stability. If storage provides some of those services, the system may be able to lower minimum-generation requirements.

Simon
In the study’s example, that kind of added flexibility reduced the minimum-generation level from about 12,600 to roughly 10,000 megawatts. Combined with local storage and other changes, instantaneous curtailment on the day fell from around 7,000 megawatts to below 4,000 megawatts.

Maria
With these flexibility changes, the curtailment curves shifted so that higher solar penetrations could be accommodated before curtailment became as significant. The researchers discussed levels around 20 to 25 percent, and potentially more. Demand response could shift additional load and support solar penetrations in the range of roughly 25 to 30 percent.

Simon
Those are not universal limits or guarantees. The presenter described the analysis as an initial look, and pointed to other possibilities—including more electricity storage, concentrating solar power with thermal storage, and greater interchange between regions. More research would be needed to understand how to accommodate even higher solar levels.

Maria
There were also modeling caveats. Diablo Canyon was treated as a baseload plant whose output did not change. Hydro flexibility was represented using limits from the planning model, rather than a detailed, plant-by-plant analysis. And the study did not explicitly model the Energy Imbalance Market’s short-term balancing function.

Simon
The discussion also touched on thermal storage in buildings. The researchers had compared concentrating solar power thermal storage, but had done less work on building thermal storage. Shifting air-conditioning demand could be an interesting opportunity, especially given California’s large summer cooling demand.

Maria
Let’s move to the storage-value study. California had a mandate for 1.325 gigawatts of storage, with procurements assigned to different years and sectors. The mandate did not specify a single storage technology; deployments could be transmission-sited, distribution-sited, or customer-side.

Simon
The study used a production-cost model based on planning data, examining cases with 33 and 40 percent renewable generation. It simulated unit commitment, energy dispatch, and reserves on an hourly basis, letting the researchers estimate system operating costs, prices, emissions, and changes in how resources were used.

Maria
They also used a six-price optimization model with historical prices to estimate storage revenues. One modeling feature was that curtailed renewable energy had an assigned value, which could influence the results. The presenter noted that this was one modeling choice among possible approaches.

Simon
The base cases compared a system with storage removed against one with storage added back according to the mandate. Other cases isolated whether storage provided energy, reserves, both, or reserves only. Sensitivities looked at regulation, longer-duration storage, different storage capacities, and relaxing California’s export limitation.

Maria
Adding the mandated storage reduced modeled production costs across California and the wider western system. Depending on renewable penetration, the reduction was estimated at about 78 to 144 million dollars. Avoided generator start-up costs made up a notable share—roughly 30 to 67 percent—even though those costs were not being repaid through the energy or other markets discussed.

Simon
A particularly interesting result was the role of ancillary services. Providing those services alone captured about 90 percent of the modeled value of storage. Adding energy provision as well raised the value by around another 10 percent.

Maria
But ancillary-service markets are relatively shallow. If storage capacity saturates a service such as regulation, prices may fall. In the model, saturation showed up as zero prices in some cases, though the presenter cautioned that this outcome reflected the model and might not occur in exactly the same way in real markets.

Simon
Storage also reduced renewable curtailment in the study, particularly in the cases discussed, but its emissions effect depended on where it charged. California’s in-state emissions could fall while the wider system’s emissions had a mixed result. If storage charged using electricity from coal generation elsewhere, overall emissions could even rise.

Maria
More storage didn’t mean each additional unit was equally valuable. As capacity increased, the value of the next increment declined. Increasing duration from the modeled two-, four-, and six-hour configurations produced a relatively modest additional reduction in production costs.

Simon
The export sensitivity reveals a trade-off. If California can export more freely, it can send surplus energy to neighboring regions and reduce curtailment. But that added regional flexibility can also ease some of the system pressures that storage would otherwise address, reducing the modeled value of storage.

Maria
That leads to the question of what happens as the rest of the West adds renewables. If neighboring regions have fewer renewables, California may be able to rely on some of their generation and flexibility. If the whole West adds similar solar portfolios, everyone may have surplus solar at the same time, leaving fewer places to send it.

Simon
Regional wind patterns might offer some diversity, but the presenters suggested that broader renewable development could increase storage’s value. The key is that storage value depends not just on California’s own generation, but on the resource mix and flexibility of the wider system.

Maria
Finally, the webinar addressed concerns about inertia and system stability. A companion engineering analysis examined potential dynamic issues, but it was not a complete model of every scenario. The presenters said early work had not shown a major problem, while emphasizing that more precise analysis was still needed.

Simon
In particular, they raised the question of how much synchronous versus nonsynchronous generation is needed in a region. A smaller area, such as southern California, might have little synchronous generation while remaining connected to a much larger grid. The presenters said those questions had not yet been fully answered.

Maria
So the connecting idea across all three studies is flexibility. Diverse generation, workable import and export rules, storage, demand response, and the ability of conventional resources to operate flexibly can all affect how much renewable energy the grid can use—and at what cost.

Simon
And the studies don’t claim that one technology solves everything. They show that outcomes depend on how technologies, operating rules, and neighboring systems fit together. The more detailed reports were offered as the place to explore additional scenarios and assumptions.

Ask anything