Grid Integration in California
Grid Integration of High Renewable Energy in California
Why grid integration becomes important
A power system must keep electricity supply and demand balanced at every moment. As solar and wind generation increase, their output varies with weather and time of day, while the electricity system must continue to meet demand and maintain reliable operation.
Two related challenges are especially important:
Curtailment occurs when renewable generation is available but cannot be used. Grid operators may reduce wind or solar output when there is more supply than the system can accept.
Flexibility is the ability of the power system to respond to changing supply and demand. It can come from flexible generators, storage, demand response, transmission, and changes to operating rules.
These challenges depend not only on physical equipment but also on institutional and operational rules. For example, rules requiring minimum levels of local generation or imports can limit the system’s ability to accommodate renewable electricity.
California’s 2030 low-carbon grid analysis
Study objective and emissions target
The analysis examined whether California could reduce emissions from its electric sector by 50% below 2012 levels by 2030 while integrating high levels of renewable generation. It assessed system operations, renewable curtailment, and the effects of different assumptions about portfolios and grid flexibility.
The analysis included economic assessment and operational modeling. It also examined a range of scenarios and sensitivities, although the results described here focus mainly on contrasting cases intended to show the effects of more- versus less-flexible operating conditions.
Renewable portfolios
Three broad portfolio cases were compared:
Baseline portfolio: Based on California’s 2014 long-term procurement planning assumptions for a 33% renewable case. It served as a counterfactual reference, even though California later established a higher renewable requirement.
Diverse target portfolio: Designed to achieve roughly 55–57% renewable penetration and the 50% carbon-reduction goal, using a broader mix of renewable resources.
High-solar target portfolio: Also designed to meet the target, but with more photovoltaic solar and less diversity than the diverse portfolio.
In the high-solar portfolio, some of the wind, geothermal, and biomass included in the diverse portfolio was replaced by photovoltaic generation. The portfolios all assumed the same rooftop solar contribution, estimated at about 24 terawatt-hours. The baseline differed from the target portfolios by about 20 terawatt-hours of energy efficiency.
The portfolios were used to test how resource diversity affects grid operation; they were not presented as a definitive recommended procurement plan. The study did not include additional offshore wind. Its near-term cost was considered a barrier, particularly because California offshore development would likely require floating platforms.
Conventional and enhanced flexibility assumptions
The study compared two packages of operating assumptions. Conventional flexibility included some improvement over conditions at the time, while enhanced flexibility removed or relaxed several constraints. The combined effect of these assumptions could be greater than the effect of any single change.
Import requirements
Conventional case: At least 70% of specified out-of-state generation had to be imported into California in every hour. The specified supply included qualifying renewable energy, nuclear generation from Palo Verde, and hydroelectric power from Hoover.
Enhanced case: Imports and exports were limited only by physical transmission capability; the hourly import requirement was removed.
The conventional requirement created a minimum level of imports. Under the assumptions described, California did not import less than roughly 2,000 megawatts. The enhanced case allowed imports to fall and also allowed California to export electricity in some periods.
Minimum local generation
Conventional case: Local fossil-fuel and hydroelectric generation had to meet a 25% minimum-generation requirement within California balancing authorities.
Enhanced case: No local-generation minimum was imposed.
The local-generation constraint reflected concerns about dynamic system behavior and controllability. The analysis noted that more detailed engineering work could support more precise requirements than a broad minimum.
Storage
Conventional case: Included about 1.5 gigawatts of battery storage to reflect a California storage requirement.
Enhanced case: Added approximately 1 gigawatt of new pumped hydro in California and 1.2 gigawatts of compressed-air energy storage outside California, near the Intermountain Power Project site in Utah.
Ancillary services
Ancillary services help maintain reliable operation, including by supporting frequency and system balance. The conventional case limited how much hydro and pumped storage could provide these services, with limits tuned to approximate 2013 provision. Without those limits, the model tended to assign a very large share of ancillary services to hydro and pumped storage. The enhanced case used less restrictive limits.
Other major modeling assumptions
The analysis also assumed:
System-wide western dispatch: The model optimized dispatch across the western system, while transmission hurdle rates constrained flows between regions.
Diablo Canyon retirement: Diablo Canyon was assumed to retire. The study chose this more challenging assumption because replacing a zero-carbon nuclear resource would require additional generation and could increase integration challenges. Relicensing costs, site conditions, and cooling-system issues were among the uncertainties discussed.
Electric vehicles: Three million electric vehicles were assumed to be on the road. They added about 13 terawatt-hours of annual electricity demand and could provide up to 3,000 megawatts of additional load, particularly during periods of renewable surplus.
Changes in the generation fleet: The analysis included coal retirements outside California and assumed that the Intermountain Power Project plant would retire in 2025.
Transmission additions: The target portfolios included transmission intended to bring in out-of-state renewable power, including a north–south connection from Idaho to southern Nevada and transmission to bring New Mexico generation into the Western grid.
Hydro conditions and market assumptions: Sensitivities included wet and dry hydro years, changes in gas and carbon prices, different western renewable levels, and different levels of demand response.
The diverse target portfolio included about 12 terawatt-hours of Wyoming wind and roughly 9–10 terawatt-hours of New Mexico wind. In the conventional case, the 70% import requirement applied to specified out-of-state energy, including those resources. The enhanced case did not require that energy to be imported at all times.
Emissions, costs, and curtailment
The study found that California could achieve the 50% emissions reduction in a wide range of scenarios. The main exception was the dry-hydro case under conventional flexibility assumptions, which did not meet the target.
The enhanced-flexibility cases generally had lower emissions than the conventional cases. One reason was that conventional constraints could force renewable curtailment and require more fossil-fuel generation to replace the unused renewable energy.
Portfolio diversity also mattered. The high-solar portfolio tended to have more curtailment than the more diverse portfolio under conventional flexibility assumptions. In some conventional, high-solar scenarios, curtailment approached 10%. More diverse portfolios and greater flexibility could keep curtailment much lower, in some cases below 1%.
The value of flexibility depended on renewable penetration:
In the baseline case, enhanced flexibility reduced operating costs by about 65 million per year compared with conventional flexibility—a relatively small difference against total annual operating costs of more than 10 billion.
At higher renewable penetration, flexibility became substantially more valuable. The presentation described benefits exceeding 500 million in the target-portfolio context.
The combination of a less diverse, high-solar portfolio and restrictive operating rules could increase operating costs by as much as 800 million and emissions by as much as 14% relative to more favorable conditions.
The cost analysis for the enhanced target portfolio estimated annualized capital costs of about 5.1 billion for incremental renewables, transmission, and storage. This was about 230 million greater than the estimated reduction in production costs. The difference was estimated at approximately 0.6% of California’s annual revenue requirement. Depending on gas prices, discount rates, and other economic assumptions, the broader cost-benefit result ranged from a small cost benefit to a cost increase of several percent of annual revenue requirements.
Key takeaway: High renewable penetration does not by itself determine integration difficulty. The generation mix, transmission access, storage, and flexibility of operating rules all influence curtailment, costs, and emissions.
Dynamic stability and system inertia
Production-cost modeling can estimate dispatch, costs, and curtailment, but it does not by itself establish whether every scenario will satisfy detailed dynamic-stability requirements. A separate qualitative review considered issues such as synchronous and nonsynchronous generation and identified possible risks as well as mitigation options.
Questions remain about how little synchronous generation a local area can operate with while connected to a much larger grid. The analysis did not fully answer these questions, and additional engineering studies are needed. It emphasized that reliability solutions may be available at lower cost and emissions than simply increasing curtailment, but they require appropriate engineering assessment.
The solar “duck curve” and renewable curtailment
Net load and the duck-shaped pattern
Net load is the electricity demand that must be served by resources other than the renewable generation being subtracted from demand. As solar production rises during the day, net load falls. When solar output declines in the late afternoon while demand remains high, net load rises rapidly.
This produces the characteristic duck-shaped pattern:
A deep midday dip in net load as solar output peaks.
A steep late-afternoon and evening ramp as solar output falls and other resources must increase generation.
The shape matters because conventional generators may not be able to reduce output indefinitely. If renewable supply exceeds what demand, storage, exports, and flexible resources can absorb, renewable generation must be curtailed.
Why curtailment is technically simple but economically important
Large-scale wind and solar facilities can generally be turned down when needed, making curtailment technically straightforward. Curtailing rooftop solar at very high penetration can be more complicated because those systems are distributed across many customers and may be less directly controllable.
Although curtailment can protect system operation, it wastes available zero-fuel-cost, zero-carbon energy. As curtailment rises, a smaller share of each additional unit of renewable production is used, weakening the economic value of further renewable development.
Illustrative midday operating conditions
In one modeled case with approximately 11% annual solar penetration, a spring day had a midday net load that would theoretically have fallen below 10,000 megawatts. However, minimum-generation limits on thermal, hydro, nuclear, and other generators prevented the system from ramping down that far. Under the assumptions used, the thermal and hydro fleet could be reduced only to about 12,600 megawatts.
The result was curtailment of about 5% of potential wind and solar generation on that day. Existing pumped-hydro storage could reduce the problem by pumping during midday, when low-cost electricity was available, rather than following its usual operating pattern. This avoided some curtailment, but did not eliminate it.
Summer conditions were different: higher midday demand, including air-conditioning load, helped absorb solar output, so the modeled summer period had little or no curtailment.
Average and marginal curtailment
Two measures help explain how rising solar penetration affects the value of solar:
Average curtailment measures the share of all available renewable energy that is not used.
Marginal curtailment measures the share of the additional energy from the next increment of solar capacity that is not used.
Marginal curtailment can become high even when average curtailment is lower. In the modeled analysis, as solar penetration approached 20%, roughly 30–40% of the incremental solar energy could be curtailed. In other words, only about 60–70% of the additional energy was used in that case.
This reduces the value of new solar generation. If the cost of solar energy is spread over a smaller quantity of energy actually sold, its effective cost rises. The analysis illustrated how solar that begins near 0.06 per kilowatt-hour could have a higher effective cost—around 0.08–0.10 per kilowatt-hour—at higher penetration and curtailment levels.
Two broad ways to accommodate solar
Grid flexibility can be increased by either flattening the duck or fattening the duck.
Flattening the duck
Flattening means shifting or adding demand during periods of high solar production, then reducing demand later. Options include:
Charging electric storage during midday and discharging it in the evening.
Demand response that moves consumption to solar-rich hours.
Thermal storage that stores cooling or heating for later use.
These approaches reduce the midday surplus and can lower the steepness of the evening ramp.
Fattening the duck
Fattening means allowing the midday solar-driven decline in net load to occur by reducing minimum-generation constraints. The system becomes more able to accommodate high solar output without requiring conventional generators to remain at unnecessarily high output.
Storage can contribute to this as well as flattening. If storage provides services such as operating reserves, frequency support, or voltage support, fewer partially loaded thermal generators may be needed to provide those services. That can allow minimum conventional generation to fall.
In one modeled example, improved flexibility reduced the minimum-generation level from about 12,600 megawatts to around 10,000 megawatts. Along with local storage and photovoltaic resources providing grid services, this reduced instantaneous curtailment on the example day from about 7,000 megawatts to less than 4,000 megawatts.
How much solar can be integrated
The analysis suggested that existing system flexibility could accommodate solar penetration on the order of 25–30% before curtailment began increasing substantially. Beyond that range, more aggressive flexibility measures may be needed, including additional storage, demand response, thermal storage, and greater exchange of electricity between regions.
The analysis used assumptions based on the long-term procurement planning model. Diablo Canyon was included as a baseload nuclear plant in the solar-integration analysis, and hydro flexibility was represented using the hydro limits in that modeling framework. Those assumptions affect the results; detailed studies are needed to represent the operating limits of individual hydro resources and assess nuclear flexibility.
Greater western cooperation can help California export surplus electricity, but the benefit may shrink if neighboring states also develop substantial solar generation. If several regions experience solar surplus at the same time, there may be fewer buyers for California’s excess power. Regional wind patterns may offer more variation than simultaneous solar output, but the value of exports still depends on the generation mix and operating conditions across the West.
Storage mandate and the value of energy storage
California’s storage requirement
California established a requirement to procure 1.325 gigawatts of energy storage. The requirement specified procurement timing and sectors—transmission, distribution, and customer-side installations—but did not prescribe one particular storage technology.
Storage can help by shifting energy over time, providing ancillary services, reducing renewable curtailment, and changing how generators are committed and operated.
Modeling approach and scenarios
The storage analysis used a production-cost model based on California long-term procurement planning data. This kind of model simulates unit commitment, energy dispatch, and reserve provision at hourly intervals. It estimates operating costs, prices, emissions, and resource operations.
A separate optimization model used historical prices to estimate storage revenues. The analysis examined systems with renewable penetration levels of 33% and 40%, comparing cases without storage to cases with storage reflecting the mandate.
The scenarios also separated the services storage could provide:
Energy only.
Ancillary services only.
Energy and ancillary services together.
Reserves only.
Sensitivities examined regulation-focused operation, longer storage duration, different amounts of storage, different values assigned to curtailed renewable energy, and the effect of relaxing California export constraints.
Operating-cost benefits and generator start-ups
Adding storage reduced modeled system-wide production costs by approximately 78–144 million, depending on renewable penetration. A substantial part—roughly 30–67%—of this reduction came from avoided generator start-up costs.
This result is important because start-up savings may not be directly compensated through conventional energy or ancillary-service market payments. A storage project may therefore create system value that is not fully reflected in its market revenue.
Ancillary services and market saturation
In the modeled cases, providing ancillary services alone could capture about 90% of storage’s modeled value. Adding energy arbitrage to ancillary-service provision increased the value by roughly another 10%.
Ancillary-service markets can be relatively shallow. If a large amount of storage competes to provide the same service, the market may become saturated and prices may fall. In one regulation sensitivity, the model produced zero prices after storage supply filled the modeled regulation requirement. That outcome partly reflected the model’s representation of the market and should not automatically be treated as a precise prediction of actual market prices.
Curtailment and emissions effects
Storage reduced renewable curtailment in the modeled cases. The effect depended on system conditions, including whether California could export surplus electricity.
Storage generally reduced in-state California emissions in the analysis, but the effect on emissions across the entire western system was mixed. The result depended on the generation used to charge storage. If storage charging increased generation from coal plants outside California, total system emissions could rise even while California’s own emissions fell.
Storage capacity and duration
The marginal value of storage declined as more storage was added: each additional unit generally provided less value than the previous one. This is expected when storage begins to meet the most valuable opportunities, such as the highest-priced ancillary services or the most significant surplus periods.
The model compared two-, four-, and six-hour storage durations. Increasing duration by one or four hours produced a relatively modest additional reduction in production costs in the cases examined. Duration can still matter in particular applications, but the benefit depends on the timing and length of the system need.
Export flexibility and storage value
Relaxing export constraints allowed California to exchange electricity more freely with neighboring regions and reduced renewable curtailment. However, greater regional flexibility also reduced some of the system needs that storage would otherwise serve. Thus, more export capability can lower storage’s value in some circumstances even as it benefits the system overall.
The reverse can apply when neighboring regions also add substantial renewable generation. If much of the West has similar solar output at the same time, neighboring systems may be less able to absorb California’s surplus. In that situation, storage may become more valuable because regional exports provide less relief.
Overall conclusions
California’s modeled 50% electricity-sector emissions reduction below 2012 levels by 2030 was feasible under many assumptions, but not in every case; the dry-hydro case with conventional flexibility missed the target.
Renewable curtailment and operating costs depended strongly on portfolio diversity, minimum-generation requirements, import rules, storage, and access to exports.
High solar output creates a midday surplus and a steep evening ramp. Both demand shifting and more flexible generator operation can help accommodate it.
Storage can provide energy shifting and ancillary services, reduce start-ups and curtailment, and help lower minimum-generation constraints. Its value depends on market depth, regional conditions, emissions outside California, and the services it is allowed to provide.
System-wide planning matters: California’s ability to manage high renewable penetration depends not only on its own resources, but also on the generation mix and flexibility of neighboring regions.