Student Feedback on Course Changes
Heat Exchanger Analysis and Design
Choosing a Heat Exchanger Analysis Method
Heat exchanger problems commonly ask for either the size of the exchanger or its thermal performance.
Sizing problems ask for a required heat-transfer area or exchanger length.
Performance problems ask for heat-transfer rate or an outlet temperature.
Two major analysis methods are used:
Log mean temperature difference (LMTD) method
The LMTD method is especially convenient for parallel-flow and counterflow exchangers. It is most directly used when the temperatures at both ends of the exchanger are known, or can be found from an energy balance.
Effectiveness–NTU method
The effectiveness–NTU method is useful when one or more outlet temperatures are unknown. It is also convenient for more complicated geometries, such as shell-and-tube and crossflow exchangers, provided an appropriate geometry-specific correlation is available.
A practical way to begin a problem is to identify:
What quantity is being sought: size, heat-transfer rate, or outlet temperature?
Which method fits the known information and exchanger geometry?
Which fluid has the smaller and larger heat-capacity rates?
Which energy balance or exchanger correlation is needed?
Common Assumptions and Energy Balances
Heat exchanger analyses often use the following simplifying assumptions:
The exchanger operates at steady state.
Fluid and material properties are constant or evaluated at suitable average temperatures.
There is no heat loss to the surroundings; the exchanger is treated as adiabatic externally.
Axial conduction along the tube wall is negligible.
The tube wall is thin enough that its conduction resistance can be neglected.
Fouling resistance on either side of the wall is negligible.
In some shell-and-tube calculations, heat transfer at tube return bends is neglected relative to heat transfer along the straight tube passes.
With no heat loss to the surroundings, the heat lost by the hot fluid equals the heat gained by the cold fluid. If neither stream undergoes a phase change,
The temperature differences are written so that each expression gives a positive heat-transfer rate.
The heat-capacity rate of a stream is
so that a stream’s heat transfer can also be written as Q˙=CΔT.
A property value such as specific heat may need to be estimated at an average temperature. If the exact average temperature is not yet known, an initial estimate can be used. The outlet temperature can then be checked, and the estimate refined if greater accuracy is necessary. When using saturated-water property tables, the liquid value is identified by the saturated-liquid designation, while the vapor value is identified by the saturated-vapor designation. Liquid specific heat is often only weakly dependent on temperature over the ranges used in these examples.
Overall Heat-Transfer Coefficient
Heat transfer from one fluid to another is affected by the thermal resistances on both sides of the separating wall. If wall conduction resistance and fouling resistance are negligible, the overall heat-transfer coefficient U is given by
where hi and ho are the convection coefficients on the inside and outside of the tube. This form assumes the same reference heat-transfer area is used for both coefficients, as is appropriate for a thin wall with approximately equal inner and outer areas.
The relation between heat-transfer rate and area depends on the temperature-difference method used:
For LMTD analysis: Q˙=UAΔTlm.
For effectiveness–NTU analysis: NTU=UA/Cmin.
If the exchanger’s tube diameter is fixed, increasing the heat-transfer area generally means increasing the tube length. This can make the exchanger larger and may create packaging or installation constraints.
LMTD Analysis: Parallel-Flow and Counterflow Sizing
LMTD definition
The log mean temperature difference accounts for the fact that the temperature difference between the two fluids changes along the exchanger. It is calculated from the temperature differences at the two ends:
Once Q˙, U, and ΔTlm are known, the required area is
The main difference between parallel-flow and counterflow calculations is how the endpoint temperature differences are paired.
Parallel-flow endpoint differences
In a parallel-flow exchanger, both fluids enter at the same end and move in the same direction. The hot inlet is paired with the cold inlet, and the hot outlet is paired with the cold outlet:
Counterflow endpoint differences
In a counterflow exchanger, the fluids move in opposite directions. The hot inlet is paired with the cold outlet, while the hot outlet is paired with the cold inlet:
For the same inlet and outlet temperatures, counterflow often maintains a more uniform temperature difference along the exchanger. This generally produces a larger LMTD and therefore requires less area for the same heat-transfer rate.
Example: cooling a process fluid
A process fluid is cooled from 80∘C to 50∘C. The cooling fluid enters at 15∘C. The hot-fluid flow rate and specific heat are known, as are the convection coefficients on both sides of the tube. The objective is to compare the required area for parallel flow and counterflow.
The hot-side energy balance gives a heat-transfer rate of approximately
With no heat loss to the surroundings, this is also the heat gained by the cold fluid. The cold-fluid outlet temperature is found from
The cold-fluid specific heat is obtained from property data using an estimated average temperature. This calculation gives a cold outlet temperature of approximately 35∘C. The estimate can be checked against the mean temperature implied by the inlet and outlet values; because liquid-water specific heat changes only weakly over the relevant range, a small mismatch has little effect on the result.
Parallel-flow result
The endpoint differences are
Therefore,
Using the heat-transfer rate, the LMTD, and the effective overall heat-transfer coefficient gives a required area of approximately 3.13 m2.
Counterflow result
For counterflow, the endpoint differences are
Thus,
The required area is approximately 2.68 m2.
Counterflow therefore uses about 14% less heat-transfer area than parallel flow in this example. The improvement results from its larger LMTD: the temperature difference remains more uniform along the exchanger.
Effectiveness–NTU Method
Heat-capacity rates and capacity ratio
For the two streams, define the smaller and larger heat-capacity rates as
The capacity ratio is
so Cr≤1.
The maximum possible heat-transfer rate is the heat transfer that would occur if the stream with the smaller heat-capacity rate experienced the largest possible temperature change:
The effectiveness compares actual heat transfer with this maximum:
The number of transfer units is defined by
Effectiveness is related to NTU and capacity ratio through a correlation that depends on the exchanger geometry. Therefore, the appropriate correlation must be selected for the exchanger type and flow arrangement.
General workflow
A typical effectiveness–NTU calculation proceeds as follows:
Identify the exchanger geometry and select its appropriate correlation.
Find each stream’s heat-capacity rate, C=m˙cp.
Determine Cmin, Cmax, and Cr.
Find effectiveness or NTU from whichever quantity can be calculated from the known information.
Use the geometry-specific correlation to find the other quantity.
Use Q˙max and effectiveness to find actual heat transfer.
Use an energy balance to calculate any unknown outlet temperature.
If sizing is required, use NTU to solve for area.
Shell-and-Tube Exchanger: Finding Tube Length
A shell-and-tube exchanger can have many tube passes inside one shell. Such an arrangement is not simply parallel flow or counterflow, so an exchanger-specific effectiveness–NTU correlation is used.
In the example, the cold stream is water flowing through the tubes. Its inlet temperature and mass flow rate are known, and its outlet temperature is specified. The hot stream is oil flowing through the shell; its inlet and outlet temperatures are known, but its mass flow rate is not. The exchanger has one shell pass, ten tubes, and eight tube passes per tube. The desired length is interpreted as the length of one straight tube pass.
A tube pass is one traverse through the shell. Thus, eight passes represent eight straight lengths per tube, not eight complete back-and-forth cycles.
Determine the hot-side mass flow rate
The cold-side heat transfer can be found from its known flow rate, specific heat, and temperature change:
The same heat-transfer rate applies to the hot side. Solving the hot-side energy balance for the unknown oil flow rate gives
Property values are evaluated at estimated average fluid temperatures. In the example, the resulting heat transfer is about 190 kW, and the oil mass flow rate is about 5.2 kg/s.
Determine capacity rates and effectiveness
The water and oil capacity rates are found from C=m˙cp. The example gives approximately
Water: just over 10,000 W/K.
Oil: approximately 12,152 W/K.
Thus, water has the smaller capacity rate, and
The effectiveness is calculated from the definition:
Because the cold stream is Cmin in this example, substituting its actual heat-transfer expression and cancelling Cmin gives
For a one-shell-pass exchanger with an even number of tube passes, an appropriate shell-and-tube correlation relates effectiveness and Cr to NTU. Applying that correlation gives approximately
Estimate the tube-side convection coefficient
The effective heat-transfer coefficient requires the convection coefficient on both sides of the tube. The hot-side coefficient is provided, but the tube-side coefficient must be calculated using internal-flow convection.
The Reynolds number characterizes the tube flow:
where ρ is fluid density, V is mean velocity, D is tube diameter, and μ is dynamic viscosity. The tube-side flow rate and fluid properties are used to assess whether the flow is laminar or turbulent.
The example identifies turbulent flow and checks that the tube length is sufficient for the flow to be fully developed. It uses the stated rule that fully developed conditions are reached after roughly ten tube diameters. A suitable turbulent-flow Nusselt-number correlation is then used with the Reynolds and Prandtl numbers. The Nusselt number is related to the convection coefficient by
where k is fluid thermal conductivity. Using the relevant fluid properties and correlation gives a tube-side convection coefficient that, combined with the known shell-side coefficient, yields an effective coefficient of approximately 354 W/(m2K).
Calculate area and length
Rearranging the NTU definition gives the required area:
The example requires nearly 30 m2 of heat-transfer area. For ten tubes, each with eight straight passes, the area is
where Nt is the number of tubes, D is tube diameter, and Lpass is the length of one pass. This calculation neglects the extra heat-transfer area at the tube return bends.
Solving for the length of one pass gives approximately 4.7 m. The interpretation of length matters: this is the length of one tube pass, not the combined length of all tube segments.
Crossflow Exchanger with Both Fluids Unmixed
In a crossflow exchanger, the fluids move approximately perpendicular to one another. A fluid is described as unmixed when its flow remains separated into channels or tubes and does not mix laterally with neighboring flow paths as it passes through the exchanger. In the example, both the air and the water are unmixed.
The exchanger is specified by its inlet temperatures, mass flow rates, overall heat-transfer coefficient, and area. Neither outlet temperature is known. Because the outlet temperatures are unknown, the LMTD cannot be calculated directly. The effectiveness–NTU method is therefore appropriate.
Calculate capacity rates and NTU
Specific heats are estimated using average temperatures. Since the outlet temperatures are initially unknown, these average temperatures must also be estimated. The example uses approximately
Air specific heat: 1,008 J/(kgK).
Water specific heat: 4,181 J/(kgK).
The resulting capacity rates show that water has the smaller heat-capacity rate. The example gives
The known area and overall heat-transfer coefficient are used to calculate
An appropriate effectiveness correlation for single-pass crossflow with both fluids unmixed then gives
Calculate heat transfer and water outlet temperature
The inlet temperatures are approximately 75∘C for water and 30∘C for air. Therefore,
Actual heat transfer is
The water outlet temperature follows from the hot-side energy balance:
Solving gives a water outlet temperature of approximately 58.3∘C.
The air outlet temperature could be calculated in the same way using its capacity rate and the same heat-transfer rate. Checking both outlet temperatures is also useful for assessing the initial average-temperature assumptions. If high accuracy is required, the property estimates can be updated and the calculation repeated until the assumed and calculated average temperatures agree sufficiently closely.
Key Relationships
Energy balance: Under the adiabatic-exchanger assumption, heat lost by one stream equals heat gained by the other.
Capacity rate: C=m˙cp measures how much heat a stream must gain or lose to change its temperature.
LMTD: The logarithmic mean of the two endpoint temperature differences is used with U and area to calculate heat transfer.
Effectiveness: ε=Q˙actual/Q˙max measures exchanger performance relative to the maximum possible heat transfer.
NTU: NTU=UA/Cmin relates exchanger conductance and area to the smaller stream capacity rate.
Geometry matters: LMTD endpoint pairings depend on whether flow is parallel or counterflow, while effectiveness–NTU correlations depend on the specific exchanger arrangement.