Topic: General Methods

When solving a heat-exchanger problem, how does identifying the objective help determine the analysis?

47 questions

  1. 1

    When solving a heat-exchanger problem, how does identifying the objective help determine the analysis?

    Model answer

    First determine whether the problem asks for exchanger size or heat-transfer rate. Sizing problems seek area, while performance problems may seek heat transfer or outlet temperatures.

    Explanation

    The objective guides the choice of method and the quantities that must be calculated.

  2. 2

    What are the two heat-exchanger analysis methods described, and when is each especially useful?

    Model answer

    The methods are log mean temperature difference (LMTD) and effectiveness–NTU. LMTD is especially convenient for parallel- and counter-flow exchangers when the inlet and outlet temperatures are known; effectiveness–NTU is useful for more complicated geometries or unknown outlet temperatures.

    Explanation

    The known temperatures and exchanger geometry determine which method is most practical.

  3. 3

    Why can an energy balance determine the heat transfer in an insulated heat exchanger without knowing its size?

    Model answer

    At steady state with no heat loss to the surroundings, heat lost by the hot fluid equals heat gained by the cold fluid. This energy balance does not depend on the exchanger area.

    Explanation

    Area affects the exchanger’s ability to transfer heat, but the energy balance relates the heat changes of the two fluid streams.

  4. 4

    Define the heat-capacity rate of a flowing fluid and give its usual expression when there is no phase change.

    Model answer

    The heat-capacity rate is the product of mass flow rate and specific heat: C=�dotmcpC = �dot{m}c_pC=�dotmcp​.

    Explanation

    It relates a fluid’s heat-transfer rate to its temperature change through Q = C igma{\Delta T} in magnitude.

  5. 5

    What does the smaller heat-capacity rate, Cmin⁡C_{\min}Cmin​, signify in an effectiveness–NTU analysis?

    Model answer

    Cmin⁡C_{\min}Cmin​ is the smaller of the two fluid heat-capacity rates. It is used to calculate the maximum possible heat transfer and the number of transfer units.

    Explanation

    The fluid with the smaller heat-capacity rate undergoes the larger temperature change for a given amount of heat transfer.

  6. 6

    What assumptions were commonly made when analyzing the heat exchangers in the examples?

    Model answer

    The analyses assumed steady state, constant fluid and material properties, and no heat loss to the surroundings. They also generally assumed a thin tube wall with no fouling and negligible axial conduction.

    Explanation

    These assumptions simplify the energy balance and thermal-resistance calculations.

  7. 7

    How is an effective heat-transfer coefficient related to thermal resistances when wall conduction and fouling are neglected?

    Model answer

    The effective coefficient is found by adding the reciprocals of the hot- and cold-side convection coefficients and then taking the reciprocal: U=(1hh+1hc)−1U = \left(\frac{1}{h_h}+\frac{1}{h_c}\right)^{-1}U=(hh​1​+hc​1​)−1.

    Explanation

    With wall and fouling resistances neglected, the two convection resistances remain in series.

  8. 8

    What kinds of heat-transfer analyses were identified as relevant to the course’s cumulative material?

    Model answer

    Relevant analyses include conduction, transient conduction, internal and external flows used to determine convection coefficients, heat exchangers, and thermal-resistance networks.

    Explanation

    These topics were identified as connected parts of the course’s heat-transfer material.

  9. 9

    How is heat-transfer area related to the length of a cylindrical tube when its diameter is fixed?

    Model answer

    The area is the tube perimeter multiplied by its length: A=πDLA = \pi D LA=πDL. At fixed diameter, increasing area means increasing tube length.

    Explanation

    This relationship makes exchanger length a practical packaging constraint.

  10. 10

    For a fluid with no phase change, how can the magnitude of heat transfer be calculated from its flow conditions?

    Model answer

    Use Q=m˙cpΔTQ = \dot{m}c_p\Delta TQ=m˙cp​ΔT, or equivalently Q=CΔTQ = C\Delta TQ=CΔT, where C=m˙cpC = \dot{m}c_pC=m˙cp​.

    Explanation

    The heat transfer equals the mass flow rate times specific heat times the fluid’s temperature change.

  11. 11

    Write the LMTD expression used to represent the temperature driving force in a heat exchanger.

    Model answer

    The log mean temperature difference is ΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2)\Delta T_{\mathrm{lm}} = \frac{\Delta T_1-\Delta T_2}{\ln(\Delta T_1/\Delta T_2)}ΔTlm​=ln(ΔT1​/ΔT2​)ΔT1​−ΔT2​​.

    Explanation

    It combines the two terminal temperature differences into a single effective temperature difference.

  12. 12

    How are ΔT1\Delta T_1ΔT1​ and ΔT2\Delta T_2ΔT2​ defined for a parallel-flow heat exchanger?

    Model answer

    For parallel flow, ΔT1=Th,in−Tc,in\Delta T_1 = T_{h,in}-T_{c,in}ΔT1​=Th,in​−Tc,in​ and ΔT2=Th,out−Tc,out\Delta T_2 = T_{h,out}-T_{c,out}ΔT2​=Th,out​−Tc,out​.

    Explanation

    The hot and cold fluids enter at the same end and leave at the same end, so the terminal differences pair the two inlets and the two outlets.

  13. 13

    How are the terminal temperature differences paired in a counter-flow heat exchanger?

    Model answer

    For counter flow, ΔT1=Th,in−Tc,out\Delta T_1 = T_{h,in}-T_{c,out}ΔT1​=Th,in​−Tc,out​ and ΔT2=Th,out−Tc,in\Delta T_2 = T_{h,out}-T_{c,in}ΔT2​=Th,out​−Tc,in​.

    Explanation

    The hot inlet is adjacent to the cold outlet, while the hot outlet is adjacent to the cold inlet.

  14. 14

    Why can the cold-fluid outlet temperature be found from an energy balance before calculating exchanger area?

    Model answer

    The energy balance equates heat lost by the hot fluid with heat gained by the cold fluid, independently of exchanger area. If the cold-side flow rate and specific heat are known, that balance gives its outlet temperature.

    Explanation

    Area is needed for the heat-transfer relation, not for conservation of energy between the fluid streams.

  15. 15

    If a fluid’s specific heat is not provided, how can it be estimated when calculating an outlet temperature?

    Model answer

    Estimate the fluid’s average temperature, look up its specific heat at a nearby table value, and use that value in the energy balance. If greater accuracy is needed, repeat the calculation using the resulting average temperature.

    Explanation

    This is an iterative estimate; the examples note that a weak dependence of specific heat on temperature can make the initial estimate adequate.

  16. 16

    In saturated-water property tables, what do the labels cp,fc_{p,f}cp,f​ and cp,gc_{p,g}cp,g​ indicate?

    Model answer

    cp,fc_{p,f}cp,f​ is the specific heat of saturated liquid, while cp,gc_{p,g}cp,g​ is the specific heat of saturated vapor.

    Explanation

    The phase indicated by the table label determines which property value should be selected.

  17. 17

    State the LMTD heat-transfer relation and rearrange it to find the required area.

    Model answer

    The relation is Q=UAΔTlmQ = UA\Delta T_{\mathrm{lm}}Q=UAΔTlm​, so the required area is A=QUΔTlmA = \frac{Q}{U\Delta T_{\mathrm{lm}}}A=UΔTlm​Q​.

    Explanation

    Once heat transfer, the effective coefficient, and LMTD are known, the area follows by rearranging the relation.

  18. 18

    In the cooling example, what heat-transfer rate was calculated from the hot-fluid temperature change?

    Model answer

    The hot fluid lost 210 kW210\,\mathrm{kW}210kW, so the cold fluid gained the same amount under the assumed insulated conditions.

    Explanation

    The equal heat-transfer magnitudes follow from the energy balance for the two sides.

  19. 19

    What cold-fluid outlet temperature and parallel-flow LMTD were obtained in the cooling example?

    Model answer

    The estimated cold-fluid outlet temperature was 35∘C35^\circ\mathrm{C}35∘C, and the parallel-flow LMTD was 34.1∘C34.1^\circ\mathrm{C}34.1∘C.

    Explanation

    The outlet temperature was estimated using the cold-side energy balance before the terminal temperature differences were calculated.

  20. 20

    Compare the required areas calculated for parallel flow and counter flow in the cooling example.

    Model answer

    The parallel-flow exchanger required 3.13 m23.13\,\mathrm{m^2}3.13m2, while the counter-flow exchanger required 2.68 m22.68\,\mathrm{m^2}2.68m2.

    Explanation

    The counter-flow arrangement had a larger LMTD for the same heat-transfer requirement and effective coefficient.

  21. 21

    Why did the counter-flow arrangement require less area in the cooling example?

    Model answer

    Counter flow produced a larger LMTD because the temperature difference remained more nearly constant along the exchanger. Consequently, less area was needed to transfer the same amount of heat.

    Explanation

    The calculated counter-flow LMTD was 39.8∘C39.8^\circ\mathrm{C}39.8∘C, compared with 34.1∘C34.1^\circ\mathrm{C}34.1∘C for parallel flow.

  22. 22

    By approximately what percentage did changing the cooling example from parallel flow to counter flow reduce the required area?

    Model answer

    The required area decreased by approximately 14%14\%14%.

    Explanation

    The reduction follows from comparing the calculated areas of 3.13 m23.13\,\mathrm{m^2}3.13m2 and 2.68 m22.68\,\mathrm{m^2}2.68m2.

  23. 23

    Why is counter flow often an efficient arrangement in an industrial heat exchanger?

    Model answer

    Counter flow tends to maintain a more consistent temperature difference along the exchanger, allowing the desired heat transfer with less area and potentially a smaller device.

    Explanation

    A smaller required area can reduce exchanger size and cost.

  24. 24

    What distinguishes a shell-and-tube heat exchanger from a simple parallel- or counter-flow exchanger?

    Model answer

    A shell-and-tube exchanger has multiple tubes running through a shell, and the tube fluid may make several passes through the shell.

    Explanation

    The shell contains the fluid outside the tubes, while the tube-side fluid travels through the tube bundle.

  25. 25

    In a multipass tube arrangement, what counts as one tube pass?

    Model answer

    One pass is one traversal along the shell; two passes are needed for the tube flow to return to where it started.

    Explanation

    The number of passes describes how many times the tube fluid travels through the exchanger lengthwise.

  26. 26

    What does one shell pass mean in the shell-and-tube example, and how are baffles related to shell passes?

    Model answer

    One shell pass means the shell-side fluid makes a single pass through the exchanger; the example had no baffles. Baffles direct shell-side flow across the tubes and can create additional shell passes.

    Explanation

    Baffles cause the shell-side flow to change direction across the tube bundle.

  27. 27

    Why was the effectiveness–NTU method selected for the shell-and-tube problem?

    Model answer

    The exchanger had a more complicated, multipass geometry than a simple parallel- or counter-flow exchanger. Effectiveness–NTU correlations were therefore used to relate its performance to its geometry.

    Explanation

    The method can use geometry-specific correlations for shell-and-tube exchangers.

  28. 28

    What sequence of calculations was used to find the tube-pass length in the shell-and-tube example?

    Model answer

    The analysis identified the geometry, found both heat-capacity rates, calculated effectiveness and NTU, determined the required area, and then used the tube geometry to calculate pass length.

    Explanation

    Area is connected to length through the tube surface area, so the thermal and geometric calculations are performed in sequence.

  29. 29

    How was the unknown hot-oil mass flow rate determined in the shell-and-tube example?

    Model answer

    The heat transfer was first calculated from the known cold-water conditions, then set equal to the heat lost by the hot oil to solve for its mass flow rate.

    Explanation

    The energy balance links the two streams even though the hot-side flow rate was initially unknown.

  30. 30

    For one shell pass and an even number of tube passes, what kind of relationship was used to obtain NTU?

    Model answer

    A shell-and-tube correlation expressing NTU as a function of effectiveness and the heat-capacity-rate ratio was used.

    Explanation

    The applicable correlation is selected based on the shell-pass and tube-pass configuration.

  31. 31

    How is effectiveness defined in the effectiveness–NTU method?

    Model answer

    Effectiveness is the ratio of actual heat transfer to maximum possible heat transfer: ε=QactualQmax⁡\varepsilon = \frac{Q_{\mathrm{actual}}}{Q_{\max}}ε=Qmax​Qactual​​.

    Explanation

    It measures how much of the maximum thermodynamically possible heat transfer the exchanger achieves.

  32. 32

    How is maximum possible heat transfer calculated in the effectiveness–NTU method?

    Model answer

    It is calculated as Qmax⁡=Cmin⁡(Th,in−Tc,in)Q_{\max}=C_{\min}(T_{h,in}-T_{c,in})Qmax​=Cmin​(Th,in​−Tc,in​).

    Explanation

    The largest possible temperature change is bounded by the hot- and cold-inlet temperature difference, and the limiting heat-capacity rate is Cmin⁡C_{\min}Cmin​.

  33. 33

    State the definition of the number of transfer units, NTU.

    Model answer

    The number of transfer units is NTU=UACmin⁡\mathrm{NTU} = \frac{UA}{C_{\min}}NTU=Cmin​UA​.

    Explanation

    This dimensionless quantity relates exchanger conductance to the smaller fluid heat-capacity rate.

  34. 34

    Why was an internal-convection calculation needed in the shell-and-tube example?

    Model answer

    The cold-side fluid flowed inside the tubes, but its convection coefficient was not given. An internal-flow analysis was needed to calculate that coefficient and then determine the effective heat-transfer coefficient.

    Explanation

    The overall coefficient depends on the convection resistance on both fluid sides.

  35. 35

    What did the Reynolds-number calculation indicate about the tube-side flow, and how was fully developed flow treated?

    Model answer

    The tube-side flow was turbulent. The analysis assumed fully developed flow and checked that the tube length was sufficient, noting that turbulent flow becomes fully developed after about 101010 tube diameters.

    Explanation

    The problem’s fully developed-flow assumption was checked against the estimated entrance length.

  36. 36

    How were the tube-side Nusselt number and convection coefficient connected in the shell-and-tube analysis?

    Model answer

    The Nusselt number was obtained from a turbulent-flow correlation, then related to the convection coefficient by Nu=hDk\mathrm{Nu}=\frac{hD}{k}Nu=khD​.

    Explanation

    With the tube diameter and fluid thermal conductivity known, this relation gives hhh.

  37. 37

    How was total tube area related to the number of tubes, tube passes, and pass length in the example?

    Model answer

    The total area was calculated as A=NtubesπDNpassesLA=N_{\mathrm{tubes}}\pi D N_{\mathrm{passes}}LA=Ntubes​πDNpasses​L, neglecting heat transfer where the tubes turn around.

    Explanation

    Each tube contributes its circumference multiplied by the length of each pass.

  38. 38

    What area and length of one tube pass were found in the shell-and-tube example?

    Model answer

    The required tube area was nearly 30 m230\,\mathrm{m^2}30m2, giving a pass length of about 4.7 m4.7\,\mathrm{m}4.7m.

    Explanation

    The length was calculated using the total area, 101010 tubes, 888 passes, and the tube diameter.

  39. 39

    How would the reported length differ if it represented the total length of all tube passes rather than the length of one pass?

    Model answer

    The total length would be 808080 times the length of one pass because there are 101010 tubes and 888 passes per tube.

    Explanation

    The example defined LLL as the length of a single pass, so the total length sums all 808080 tube-pass lengths.

  40. 40

    What does “unmixed” mean for each fluid in the cross-flow heat exchanger?

    Model answer

    A fluid is unmixed when it is divided among separate tubes or channels and cannot mix with fluid in neighboring passages. In the example, the tube-side fluid and the air-side fluid were both unmixed.

    Explanation

    The tubes separate one stream, while fins or plates separate the other stream’s channels.

  41. 41

    Why was the effectiveness–NTU method required for the cross-flow problem when neither outlet temperature was known?

    Model answer

    The LMTD method requires the terminal temperature differences, which depend on outlet temperatures. Since neither outlet temperature was known, effectiveness–NTU was used to find the heat transfer and then the outlet temperatures.

    Explanation

    The exchanger area and effective coefficient were given, allowing NTU to be calculated without first knowing the outlets.

  42. 42

    Which cross-flow correlation was selected for the example, and what characteristics justified its use?

    Model answer

    The correlation for a single-pass cross-flow exchanger with both fluids unmixed was selected.

    Explanation

    The flow configuration and unmixed conditions must match the correlation being used.

  43. 43

    How were specific heats estimated in the cross-flow example when the outlet temperatures were unknown?

    Model answer

    An average temperature was estimated for each fluid, and the specific heat was selected from the property table near that temperature.

    Explanation

    Because the specific heats varied only weakly with temperature in the ranges considered, approximate values were adequate for the example.

  44. 44

    In the cross-flow example, which fluid had Cmin⁡C_{\min}Cmin​, and what was the approximate heat-capacity-rate ratio?

    Model answer

    The hot water had Cmin⁡C_{\min}Cmin​, and the ratio Cr=Cmin⁡/Cmax⁡C_r=C_{\min}/C_{\max}Cr​=Cmin​/Cmax​ was approximately 0.20.20.2.

    Explanation

    The hot-side heat-capacity rate was about one-fifth of the air-side rate.

  45. 45

    What NTU and effectiveness were obtained for the cross-flow exchanger?

    Model answer

    The calculated values were approximately NTU=0.5\mathrm{NTU}=0.5NTU=0.5 and ε=0.37\varepsilon=0.37ε=0.37.

    Explanation

    Effectiveness was calculated from the single-pass, both-unmixed cross-flow correlation using NTU and CrC_rCr​.

  46. 46

    What maximum heat-transfer rate and hot-water outlet temperature were obtained in the cross-flow example?

    Model answer

    The maximum possible heat transfer was about 4.8 kW4.8\,\mathrm{kW}4.8kW, and the hot-water outlet temperature was approximately 58.3∘C58.3^\circ\mathrm{C}58.3∘C.

    Explanation

    Actual heat transfer was found from effectiveness and the maximum heat transfer, then used in the hot-side energy balance.

  47. 47

    How could the cold-fluid outlet temperature be found in the cross-flow problem?

    Model answer

    Use the calculated actual heat transfer in the cold-side energy balance, Q=Cc(Tc,out−Tc,in)Q=C_c(T_{c,out}-T_{c,in})Q=Cc​(Tc,out​−Tc,in​), and solve for Tc,outT_{c,out}Tc,out​.

    Explanation

    The same heat transfer gained by the cold stream is lost by the hot stream under the insulated, steady-state assumption.