Student Feedback on Course Changes


Student Feedback on Course Changes

Simon
Before we get into heat exchangers, there’s a request for course feedback. The Smart Evaluations have just gone live, and this year feedback is especially helpful because the course made a major change partway through.

Hope
And even if we’re all hoping the change won’t continue into the fall, it’s useful to know what worked and what didn’t in case the course has to run that way again. More than ten percent of the class has already filled out the evaluations, but written comments about the transition would be particularly valuable.

Simon
There’s also an anonymous discussion board on the MyCourses page. That’s a way to give more immediate feedback, since the instructor won’t see the Smart Evaluation responses until the course is over. All right, today’s main event: three heat exchanger problems.

Hope
Let’s start with the first one. A process fluid cools from 80 to 50 degrees Celsius. We’re given its specific heat and mass flow rate, along with the cooling fluid’s inlet temperature and mass flow rate. The cooling-fluid outlet temperature isn’t given, and we want to find the required heat-transfer area for both parallel-flow and counter-flow arrangements.

Simon
We’re also given the convection coefficients on the two sides: 3,500 and 4,500 watts per square meter-kelvin. The area here is the tube’s perimeter times its length, assuming its diameter stays fixed. So, for this setup, a larger required area means a longer heat exchanger—which could matter if there’s limited space.

Hope
Before calculating, set the assumptions: steady state, constant fluid and material properties, and no heat loss to the surroundings. That means heat leaving the hot fluid equals heat entering the cold fluid. We’ll also neglect axial conduction, assume a thin tube wall, and neglect fouling on either side.

Simon
Those last assumptions simplify the resistance between the fluids: we don’t include significant resistance from the tube wall or from deposits on it. A helpful routine for any heat exchanger problem is to ask two questions: are we sizing the exchanger, or finding its heat transfer, and which method fits the information we have?

Hope
The two methods are log mean temperature difference, or LMTD, and effectiveness-NTU. LMTD is especially convenient for parallel- and counter-flow exchangers when the inlet and outlet temperatures are known. Effectiveness-NTU is often a better fit for more complicated geometries. Here we’re finding area, and we’ll use LMTD.

Simon
With no phase change, the heat transfer on either side is the mass-flow rate times specific heat times the temperature change. The hot side loses the same amount of heat that the cold side gains. We can also write mass flow rate times specific heat as the heat-capacity rate, capital C.

Hope
Then the LMTD relation is heat transfer equals the effective heat-transfer coefficient times area times the log mean temperature difference. The log mean is the difference between two terminal temperature differences divided by the natural log of their ratio. We’ll calculate the heat first, find the missing cold outlet temperature, and then solve for area.

Simon
The key distinction between parallel and counter flow is how we pair the temperatures at the two ends. In parallel flow, both fluids enter at the same end: one terminal difference is hot-inlet minus cold-inlet, and the other is hot-outlet minus cold-outlet.

Hope
In counter flow, the hot inlet is next to the cold outlet, while the hot outlet is next to the cold inlet. So the terminal differences become hot-inlet minus cold-outlet and hot-outlet minus cold-inlet. The energy balance is unchanged; only those temperature pairings change.

Simon
On the hot side, all the needed information is given, so the heat released is 210 kilowatts. Because we’re assuming no losses, the cold side receives 210 kilowatts too. We can use that energy balance to calculate the cold-fluid outlet temperature.

Hope
We need the cold fluid’s specific heat, though, and it wasn’t provided. The example uses saturated-liquid water properties from a table, taking an initial average temperature estimate of 300 kelvin. For liquid water, use the saturated-liquid specific-heat column, labeled C-P-F, rather than the vapor column.

Simon
That first estimate corresponds to an outlet temperature of about 39 degrees Celsius, but using the energy balance gives an outlet of about 35 degrees. So the estimate was four degrees high. We could iterate using a better average temperature, but water’s liquid specific heat changes only weakly with temperature, so the example proceeds with the table value.

Hope
For parallel flow, the two terminal differences are 65 and 15 degrees Celsius. Their log mean is about 34.1 degrees. Once we have that, we can use the LMTD equation to find the area—provided we know the effective heat-transfer coefficient.

Simon
With a thin wall and no fouling, the overall resistance is just the convection resistance on each side. The effective coefficient is therefore the reciprocal of the sum of the reciprocals of the inside and outside convection coefficients. We’re given both, so we can calculate it without doing a separate convection analysis.

Hope
Putting that coefficient, the 210-kilowatt heat transfer, and the parallel-flow LMTD into the area equation gives about 3.13 square meters. That completes the parallel-flow sizing.

Simon
For counter flow, we keep the same heat transfer and outlet temperatures because the energy balance doesn’t depend on the exchanger’s flow arrangement. But the terminal temperature differences change: they’re 45 and 35 degrees Celsius.

Hope
Those closer terminal differences produce a larger log mean temperature difference, about 39.8 degrees. A larger LMTD means we need less area to transfer the same amount of heat with the same effective coefficient.

Simon
The counter-flow area is about 2.68 square meters, compared with 3.13 for parallel flow—roughly a 14 percent reduction. Just changing how the tubes are connected can make the exchanger smaller, which can affect its cost and practicality.

Hope
The second problem is a shell-and-tube exchanger, which is more complex than simple parallel or counter flow. A bundle of tubes snakes through a shell, while another fluid occupies the shell side.

Simon
On the cold side, we’re given water entering at 15 degrees Celsius at 2.5 kilograms per second, and we’re also given its outlet temperature. On the hot side, engine oil enters at a known temperature, and its outlet temperature is known, but its mass-flow rate is not. We’re asked for the length of a tube pass.

Hope
The exchanger has ten tubes, each making eight passes, and the tube diameter is given. A pass means one trip along the exchanger; returning to the starting side takes two passes. We’ll interpret the requested length as the length of one pass, though the problem should really define that more explicitly.

Simon
We assume steady state, constant properties, no heat loss, a thin tube wall, and no fouling. We also neglect heat transfer where the tubes turn around, focusing on the straight pass length. The flow is stated to be fully developed, but we’ll check that assumption numerically.

Hope
For this complicated geometry, we’ll use effectiveness-NTU. The roadmap is: identify the exchanger geometry, find the heat-capacity rates, calculate effectiveness from its definition, use the appropriate correlation to find NTU, and then use NTU to find area.

Simon
The geometry is one shell pass and an even number of tube passes—eight. A shell pass refers to the shell-side flow going through the shell once. If baffles forced that flow to cross the tubes repeatedly, that would mean multiple shell passes; this problem has no such baffles.

Hope
We use the shell-and-tube correlation for one shell pass and an even number of tube passes. It gives NTU as a function of effectiveness and the capacity-rate ratio, C-r. The correlation introduces an intermediate quantity, capital E, which is itself calculated from effectiveness and C-r.

Simon
To get the capacity rates, we need each fluid’s mass-flow rate and specific heat. The oil’s flow rate is the missing piece, so we’ll first look up the oil and water properties at estimated average temperatures. The example uses about 403 kelvin for the oil and about 323 kelvin for the water.

Hope
Keep the units straight when reading the property tables: the specific heats may be listed in kilojoules per kilogram-kelvin, while the heat calculations use watts. Convert to joules per kilogram-kelvin, or track the units consistently throughout.

Simon
The cold-side properties are also needed for the internal convection calculation later: density, viscosity, thermal conductivity, and Prandtl number, in addition to specific heat. Finding them early helps avoid having to stop midway through the problem.

Hope
The water’s capacity rate is just over 10,000 watts per kelvin. We can use the energy balance to find the hot-oil flow rate: first calculate the actual heat transfer from the fully known cold side, which is about 190 kilowatts, then set the heat lost by the oil equal to it.

Simon
Solving the hot-side energy balance gives an oil mass-flow rate of about 5.2 kilograms per second. Now, using the oil specific heat, its capacity rate is about 12,152 watts per kelvin.

Hope
So the hot side has the larger capacity rate, and the cold side has the smaller one. C-min is the cold-side capacity rate; C-max is the hot-side rate. The ratio C-r is C-min divided by C-max, so it’s less than one—about 0.86 here.

Simon
Next comes effectiveness. Its definition is actual heat transfer divided by the maximum possible heat transfer. The maximum is C-min times the largest inlet-temperature difference, which is hot-inlet temperature minus cold-inlet temperature.

Hope
Because we already know the actual heat transfer and C-min, we can calculate effectiveness. The example simplifies the expression using the cold-side energy balance, since the cold side is C-min; that lets the capacity rate cancel. The resulting effectiveness is 0.483.

Simon
Now use the shell-and-tube correlation. First calculate capital E from the effectiveness and C-r, which gives about 1.73. Then substitute that value, along with C-r and effectiveness, into the NTU expression. The result is an NTU of about 1.

Hope
The definition of NTU is the effective heat-transfer coefficient times area divided by C-min. We know NTU and C-min, but we still need the effective coefficient. Since the hot-side coefficient is given, the remaining task is to calculate the cold-side coefficient inside the tubes.

Simon
We start with the Reynolds number, using the cold-fluid flow rate, tube diameter, and viscosity. The result indicates turbulent flow. The example checks that the tube length is long enough for fully developed flow, using the rule that turbulent flow becomes fully developed after about ten diameters.

Hope
Assuming the tube is much longer than ten diameters, we can use a turbulent-flow Nusselt-number correlation. With Reynolds number and the table’s Prandtl number, the Nusselt number is about 120. Then Nusselt number equals the inside coefficient times diameter divided by the fluid’s thermal conductivity.

Simon
That gives us the inside convection coefficient. Combining it with the known hot-side coefficient using the reciprocal-resistance relation gives an effective heat-transfer coefficient of about 354 watts per square meter-kelvin.

Hope
Now the NTU definition gives a required heat-transfer area of almost 30 square meters. To convert that area into the length of one pass, use total area equals number of tubes times the circumference of one tube times the number of passes times the pass length.

Simon
There are ten tubes and eight passes each, so that’s 80 tube-pass lengths, each with circumference pi times the diameter. Solving for the pass length gives about 4.7 meters. If instead someone asked for the combined length of all tube passes, it would be 80 times the length of one pass.

Hope
The final heat exchanger is a cross-flow exchanger that cools truck coolant with air. Both fluids are unmixed. That means each fluid is kept in separate tubes or channels, so it can’t mix with fluid in neighboring passages as it flows through.

Simon
Air enters at 30 degrees Celsius with a given mass-flow rate, and water enters at 75 degrees Celsius with another given mass-flow rate. We’re also given the tube diameter, overall heat-transfer coefficient, and total heat-transfer area. The requested result is the water outlet temperature.

Hope
Neither outlet temperature is known, so we can’t directly find the heat transfer using an inlet-to-outlet energy balance. Although LMTD can sometimes be used for more complicated geometries with a suitable correction factor, here we don’t know either outlet temperature, so effectiveness-NTU is the natural choice.

Simon
The plan is to identify the geometry, calculate both capacity rates, find NTU from its definition, use the cross-flow correlation to get effectiveness, and then use effectiveness to find the actual heat transfer.

Hope
This is a single-pass cross-flow exchanger, unmixed on both the hot and cold sides. That matches the correlation for both fluids unmixed. It gives effectiveness in terms of NTU and C-r.

Simon
To calculate the capacity rates, we need specific heats, but we don’t know the outlet temperatures yet. So we estimate average temperatures for both fluids and look up their specific heats at those values.

Hope
For air, the specific heat varies only slightly over the expected range, so the example uses about 1,008 joules per kilogram-kelvin. For the water, it estimates an average temperature near 325 kelvin and uses a specific heat of about 4,181 joules per kilogram-kelvin.

Simon
Using the mass-flow rates gives the two capacity rates. The hot-side capacity rate is the smaller one, around one-fifth of the cold-side rate, so C-min is on the hot side and C-r is about 0.2.

Hope
NTU equals the given overall heat-transfer coefficient times the given area, divided by C-min. With those values, NTU is about 0.5. Substituting NTU and C-r into the both-unmixed cross-flow correlation gives an effectiveness of about 0.37.

Simon
To turn effectiveness into heat transfer, we need Q-max. It’s C-min times the largest possible temperature difference, which is the hot inlet minus the cold inlet. The example gets a maximum possible heat transfer of about 4.8 kilowatts.

Hope
Actual heat transfer is effectiveness times Q-max, so it’s roughly 0.37 times 4.8 kilowatts. Once we know that, the hot-side energy balance gives the water outlet temperature: heat transfer equals the hot-side capacity rate times the hot-side temperature drop.

Simon
Solving gives a water outlet temperature of about 58.3 degrees Celsius. We can also use the cold-side energy balance to find the air outlet temperature, even though the question doesn’t ask for it. That gives us a way to check our temperature estimates.

Hope
The check is reasonably close to the assumed averages. If an application demanded greater accuracy, we could iterate the property estimates and calculations. But because the specific heats change only weakly with temperature, that refinement isn’t necessary for this example.

Simon
That’s the end of the heat exchanger examples—and the last formal example in the course. The instructor planned to review the whole course the following Tuesday, and students were invited to suggest topics or send feedback.

Hope
The final exam will be cumulative. The review is intended to cover the whole course, including the general heat-transfer material from the first module, conduction and transient conduction, internal and external flows for finding convection coefficients, and heat exchangers.

Simon
Students should also be ready for resistance-network problems, which connect to the first module. The review was expected to be extensive—around 70 slides—and could potentially continue into Thursday if needed.

Hope
The exam format was still being finalized. The department was gathering feedback from the first round of virtual midterms, and the instructor expected to share the plan the following week. One possibility under consideration was separating the multiple-choice portion from the scheduled exam time.

Simon
The class discussed giving students enough time not only to complete an exam but also to prepare and upload their work. Scanning or photographing solutions and submitting them can take time, and a technical problem during upload can add stress.

Hope
One student described another course that let students submit answers during the exam window and upload their full solutions afterward. The instructor welcomed feedback about that approach and about exam experiences in other courses.

Simon
The goal was to settle on a process that worked for students and avoided unreasonable schedules across time zones. The instructor said students shouldn’t have to get up in the middle of the night to take the heat exam.

Hope
So the big takeaways are: use LMTD when the relevant terminal temperatures are known, especially for parallel and counter flow; use effectiveness-NTU when outlet temperatures are unknown or the geometry is more involved; and keep checking assumptions, properties, units, and the definition of the area you’re solving for.